Home
>
American Water Heater
>
Water Heater
>
American Water Heater Common Vent Kit for HCG3 Series User Manual
American Water Heater Common Vent Kit for HCG3 Series User Manual
Have a look at the manual American Water Heater Common Vent Kit for HCG3 Series User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
11 Supports - You will need enough supports so that you can install one every 3 feet of horizontal run and every 5 feet of vertical run for both the inlet and vent pipe. Supports may be field supplied metal strapping or equivalent. Condensate Drain - Each water heater must have a separate condensate drain line running to an open drain. Follow the directions in the water heater’s Instruction Manual. Do not use a common condensate drain line for multiple heaters. INSTRUCTIONS Physical Layout - General The requirements for the layout of the Polypropylene common vent system, required lengths and terminal locations are the same as for the PVC vent. The overall layout is shown in Figure 4. Consult the previous instructions for additional requirements. INDIVIDUAL VENTCONNECTOR OUTLET VENT ADAPTER(KIT SUPPLIED PARTS) (SEE TABLES 3A & 3B FOR RESPECTIVE MODELS AND KITS) 6Ø ELBOW UV RESISTANT + 6Ø BIRD SCREEN(FIELD SUPPLIED PARTS) 6Ø BIRD SCREEN (FIELD SUPPLIED PARTS) 6Ø PIPE 36 UV RESISTANT (FIELD SUPPLIED PARTS) TERMINAL SECTIONS(UV RESISTANT)COMMON VENTING6 TEE W/CAP (FIELD SUPPLIED PARTS)6Ø ELBOW (FIELD SUPPLIED PARTS)INLET VENT ADAPTER (KIT SUPPLIED PARTS) (SEE TABLES 3A & 3B)ADAPTER CONNECTOR (KIT SUPPLIED PARTS) 6Ø PIPE12” (FIELD SUPPLIED PARTS) FIGURE 4. DEFINITION OF SYSTEM SECTIONS - POLYPROPYLENE NOTE: In both the air inlet and vent outlet sides, the female end of the pipe or fitting is always towards the terminations. Servicing should only be performed by a 4ualified Service Technician
12 The general instructions for penetrating the side wall are found in the Side Wall Terminations sections of the water heater’s Instruction Manual. The common vent system may not be used with concentric or low profile vent terminals. All pipe and terminations that are outside the structure should be UV pr\ otected (black) parts. For each penetration, cut a 7” diameter hole through the structure. First, attach the final termination for the air intake to its final straight pipe. Outside the building, insert the male end of the last straight pipe section through the wall plate and then, through the penetration. This last section should be the UV protected pipe. Run a bead of field-supplied silicone sealant around the wall plate and press it in place. Inside the building, place a second wall plate over the male end and seal the plate to the wall with silicone sealant. After the vent system is completely set up, finish the penetration by sealing the gap between the pipe and wall plates with a bead of silicone sealant. Remove the rubber gasket at the end of the inlet and outlet and inse\ rt the bird screen into the groove that is now available. VENT The vent adapter and backflow preventer (See Figure 5) is connected to the aluminum heater outlet and condensate trap by inserting the male end of the vent outlet adapter into the outlet and securing it with the rubber boot and hose clamps (supplied with the water heater). Straight pipe to tee - Use field-supplied straight vent sections to reach the horizontal part of the system that runs above the heaters. The total height from the bottom of the heater to the centerline of the horizontal must be from 80” to 110”. FIGURE 5. OUTLET VENT ADAPTER TO POLYPROPYLENE 150 - 250 MODELS300 - 500 MODELS LOCKING RING Servicing should only be performed by a 4ualified Service Technician
13 INLET AIR SIDE Adapter to inlet - The male end of the air inlet adapter (See Figure 6) is inserted into the water heater air inlet (a PVC coupling). It is held in place with the connector adapter supplied in this kit. A 90° elbow is inserted into the female end adapter to turn the system in a vertical direction. Straight pipe to tee - A straight pipe section is used to run from the elbow to the bottom of the tee. The length may be adjusted so that the height to the center line of the horizontal run is 80” to 110” from the base of the heater. A straight section is not required – you may insert the base of the tee\ into the female end of the elbow. Terminations The placement of the vent and air terminals must follow the guidelines for terminal location found in the water heater’s Instruction Manual. All required clearances to building features are the same as found in the water heater’s Instruction Manual. The combustion vent terminal is a coupling with a screen that finishes the end of the pipe. The air inlet terminal must use the 90° elbow pointed down as shown in Figure 2. Clearances to the ground and to anticipated snow level must be as shown in Figure 2. The ends of both terminals must be protected with the bird screens supplied with the terminations. FIGURE 6. AIR INLET ADAPTER Servicing should only be performed by a 4ualified Service Technician
14 NOTES 0036004800550059004C0046004C0051004A00030056004B00520058004F0047000300520051004F005C000300450048000300530048005500490052005500500048004700030045005C000300440003003400580044004F004C00BF0048004700030036004800550059004C004600480003
15 NOTES 0036004800550059004C0046004C0051004A00030056004B00520058004F0047000300520051004F005C000300450048000300530048005500490052005500500048004700030045005C000300440003003400580044004F004C00BF0048004700030036004800550059004C004600480003
For additional information contact: 1-800-527-1953 www.hotwater.com 332199-001
3RXUGHSOXVDPSOHVLQIRUPDWLRQVFRQWDFWHU ZZZKRWZDWHUFRP 332199-001
15/ HQWUHWLHQQHGHYUDLWrWUHHIIHFWXpTXHSDUXQWHFKQLFLHQGHVHUYLFHTXDOL¿p NOTES
/ HQWUHWLHQQHGHYUDLWrWUHHIIHFWXpTXHSDUXQWHFKQLFLHQGHVHUYLFHTXDOL¿p NOTES
13/ HQWUHWLHQQHGHYUDLWrWUHHIIHFWXpTXHSDUXQWHFKQLFLHQGHVHUYLFHTXDOL¿p CÔTÉ ENTRÉE D’AIR $GDSWDWHXU j HQWUpH