Home
>
American Water Heater
>
Water Heater
>
American Water Heater Common Vent Kit for HCG3 Series User Manual
American Water Heater Common Vent Kit for HCG3 Series User Manual
Have a look at the manual American Water Heater Common Vent Kit for HCG3 Series User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
PRINTED 1015 332199-001 CONTENTS 1. Introduction 2. PVC Common Vent Kit Instructions (See Page 3) 3. Polypropylene Common Vent Kit Instructions(See Page 9) COMMON VENT KIT (PVC AND DURAVENT) Kit Instructions SERVICING SHOULD ONLY BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN 0036004800550059004C0046004C0051004A00030056004B00520058004F0047000300520051004F005C000300450048000300530048005500490052005500500048004700030045005C000300440003003400580044004F004C00BF0048004700030036004800550059004C004600480003
2 INTRODUCTION These instructions cover how to use the above kits to install two of any combination of the following 150 to 250 models or 300 to 500 models of water heaters in a common horizontal direct vent configuration. You may not combine water heaters from the two groups: 150 to 250 Models, Series 200/201; A. O. SMITH MODELS: BTH 150(A), BTH 199(A) & BTH 250(A) AMERICAN MODELS: (A)HCG3100T 150, (A)HCG3100T 199 & (A)HCG3100T 250 STATE MODELS: SUF 150(N,P)E(A), SUF 199(N,P)E(A) & SUF 250(N,P)E(A) RELIANCE MODELS: RUF 150(N,P)E(A), RUF 199(N,P)E(A) & RUF 250(N,P)E(A) Serie\ s 200,201 JOHN WOOD MODELS: (A)JWSH100150(N,P), (A)JWSH100199(N,P) & (A)JWSH100250(N,P) 300 to 500 Models, Series 200/201: A. O. SMITH MODELS: BTH 300(A,Y,Z), BTH 338(A), BTH 400(A) & BTH 500(A) AMERICAN MODELS: (A)HCG3119T 300 & (A)HCG3130T 400 STATE MODELS: SUF 300150(N,P)E(A), SUF 400150(N,P)E(A) & SUF 500150(N,P)E(\ A) RELIANCE MODELS: RUF 300150(N,P)E(A), RUF 400150(N,P)E(A) & RUF 500150(N,P)E(A\ ) JOHN WOOD MODELS: (A)JWSH119300(N,P) & (A)JWSH119400(N,P) NOTE: These instructions are included with a kit that connects one water heater to a common vent system. Study this instruction to determine how many kits you may need for your instal\ lation. Servicing should only be performed by a 4ualified Service Technician
3 PVC COMMON VENT KIT 9009152005 OR 9009227005 INSTRUCTIONS ADDITIONAL INFORMATION This kit instruction is a supplement to the Instruction Manual that is supplied with the water heater. The multiple heater installation must satisfy all the requirements of the Instruction Manual as well as the requirements of this kit instruction. The installer may also consult with installation instructions from the vent manufacturer. In the event of any conflict between the documents, these instructions take precedence. Installations must comply with applicable national, state, and local codes. For Canadian installation, Polypropylene vent must be listed as a ULC-S636 approved system. If Polypropylene vent is not required by your local code, you may use either PVC or CPVC pipes for your water heater that allows non-metallic venting material installations. The kit is meant to accommodate heaters that maintain the recommended 24” clearance between the water heaters. NOTE: The use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel® (polyphenolsulfone) in non- metallic venting system is prohibited. Covering non-metallic vent pipe and fittings with thermal insulation is prohibited. PVC PARTS LIST Each kit contains the adapters needed to connect the vent and air intake system to one heater. Additional parts are needed to create the connectors, common sections and vent terminations. A list of additional parts is included below for your convenience. For example, to common vent 2 heaters requires 2 of the kits in Table 1A, the additional parts in Table 2, and PVC parts selected to fit the installation. 12 ITEM NO. KIT #DESCRIPTIONKIT SUPPLIED 1VENT ADAPTER,OUTLET,6,PP,DURAVENT1 2 9009152005 VENT ADAPTER,PP/PVC,STAINLESS,DURAVENT1 3 INSTRUCTION,COMMON VENT KIT,BTH 150-250 (NOT SHOWN)1 TABLE 1A. PVC COMMON VENT KIT (150 TO 250 MODELS) (ONE KIT NEEDED FOR EACH HEATER) NO. KIT #DESCRIPTIONKIT SUPPLIED 1 1 2BACKFLOW PREVENTER, BTH 300-500, DURAVENT 1VENT ADAPTER, BTH 300-500, SS, DURAVENT9009227005 ITEM NO. TABLE 1B. PVC COMMON VENT KIT (300 TO 500 MODELS) (ONE KIT NEEDED FOR EACH HEATER) Servicing should only be performed by a 4ualified Service Technician
4 12 3 ITEM NO. PART NUMBERDESCRIPTIONADDITIONALREQUIRED 19005376205PLATE,WALL COVER,0.052,GALV,STEEL4 2 332647-000VENT SCREEN COUPLING ASSEMBLY,62 3 321764-000AIR INTAKE TERMINAL2 TABLE 2. ADDITIONAL REQUIRED PARTS - PVC Supports - You will need enough supports so that you can install one every 3 feet of horizontal run and every 5 feet of vertical run for both the inlet and vent pipe. Supports may be field supplied metal strapping or equivalent. Condensate Drain - Each water heater must have a separate condensate drain line running to an open drain. Follow the directions in the water heater’s Instruction Manual. Do not use a common condensate drain line for multiple heaters. INSTRUCTIONS Physical Layout - General This kit may be used as part of a common vent installation of two of any combination of the models in the 150 to 250 group or the 300 to 500 group listed on Page 2 of this manual in a horizontal direct vent configuration. You may not mix water heaters from the different groups. NOTE: Do not use these parts to combine these water heaters with any oth\ er heater or gas appliance. This kit is meant to common vent water heaters that are physically close to each other and facing the same direction. The limits of this kit are: • Two (2) heaters only, • Both heaters on the same floor, • Through the wall vent and air inlet terminations, • Both heaters in the same room (pressure zone), • No change to the system layout, as shown in Figure 1 or Figure 4, except as explained in the section following and • The adapters shown in Table 1A and Table 3A must not be modified. The system layout must be planned to minimize the linear length and number of fittings in the system. The kit is meant to accommodate heaters that maintain the recommended 24” clearance between the water heaters, (52” on center for the 120 to 250 models and 57” on center for the 300 to 500 models). Consult the water heater’s installation instructions for proper clearances for service. Consult the water heater’s Instruction Manual and see Figure 2 for requirements for locating the air intake and vent terminals. The common vent is the section of the vent and air inlet piping where the gases from both heaters flow together, See Figure 1. The maximum equivalent length straight pipe and elbows of the common sections is 50 feet. The minimum equivalent length of the common sections is 3 feet. Each 90° elbow is equal to 5 feet and a 45° elbow is equal to 2½ feet. The maximum number of elbows is three. The air intake terminal (90° elbow) is not included in the equivalent length. Maximum Equivalent Lengths - The normal maximum equivalent lengths of the system are: Common section: 50 feet, Connector height: 110” and Heater spacing: 24” clearance (see above). If it is necessary to modify the connectors or heater spacing, the equivalent length of additional vent connector, heater spacing or elbows must be deducted from the 50 equivalent feet of the common vent or common air intake sections. Servicing should only be performed by a 4ualified Service Technician
5 The individual vent connectors attach the heaters to the common vent. The exhaust vent connectors are attached to the water heater with the parts in the kit. The air inlet connectors are attached with PVC reducing fittings to the heater’s PVC coupling. As shown in Figure 1, the individual vent connectors consist of vertical and horizontal sections that connect the heater outlets to the common vent. Using different lengths of pipes, the height of the horizontal sections may be adjusted to be from 80” to 110” from the bottom of the heater to the centerline of the horizontal section. The combustion air and exhaust vent sides of the system may be different heights, but each must meet the 80” to 110” height requirement. Support: DO NOT SUPPORT WEIGHT OF VENT SYSTEM ON THE HEATER. Supports must be installed every 3 feet of horizontal run and 5 feet of vertical run for both the inlet and vent pipe. Supports may be made of field supplied metal strapping or equivalent. The common vent outlet piping must be sloped upwards toward the vent terminal at least 1/4” per foot. Terminations: See Figure 2 for location requirements of horizontal vent and intake terminations. You must use the terminations found in the additional required parts list. The air inlet terminal is a 90° elbow pointing down and the vent outlet is the end of a straight pipe section, facing horizontally. COMMON VENTING AIR INTAKE TERMINAL (FIELD SUPPLIED PARTS, SEE TABLE 2) 6Ø VENT SCREEN COUPLING ASSEMBLY (FIELD SUPPLIED PARTS, SEE TABLE 2) VENT ADAPTER PP/PVC, STAINLESS DURAVENT (KIT SUPPLIED PARTS) (REFER TO TABLES 1A & 1B FOR RESPECTIVE MODELS AND KITS) VENT ADAPTER, OUTLET 6, PP, DURAVENT (KIT SUPPLIED PARTS) (SEE TABLES 1A & 1B FOR RESPECTIVE MODELS AND KITS) INDIVIDUAL VENTCONNECTOR FIGURE 1. DEFINITION OF SYSTEM SECTIONS - PVC Servicing should only be performed by a 4ualified Service Technician
6 ASSEMBLY: All joints that are PVC to PVC should be attached using approved solvent glue. See the water heater’s Instruction Manual for additional details. Start the assembly at the wall termination and proceed towards the middle of the common system. Next, start assembly at the appliances. This will allow small adjustments near the tees over the heaters. Wall Penetration - The general instructions for penetrating the side wall are found in the Side Wall Terminations sections of the water heater’s Instruction Manual. The common vent system may not be used with the concentric or low profile vent terminals as described in the Instruction Manual supplied with the water heater. For each penetration, cut a 7” diameter hole through the structure. First, attach the final terminations for the ex- haust outlet and air intake to their final, straight pipes. Outside the building, insert the last straight pipe sections through the wall plates and then, through the penetration. Run a bead of field-supplied silicone sealant around the wall plate and press it in place. Inside the building, place a second wall plate over each of the pipes and seal the plates to the wall with silicone sealant. After the vent system is completely set up, finish the penetrations by sealing the gap between the pipe and wall plates with a bead of silicone\ sealant. FIGURE 2. WALL TERMINATIONS Servicing should only be performed by a 4ualified Service Technician
7 VENT The exhaust vent is connected to the heater by two adapters. The vent outlet adapter/ backflow preventer is connected to the aluminum exhaust vent elbow by inserting the male end of the vent outlet adapter into the outlet and securing it with the rubber boot and hose clamps (supplied with the water heater as shown in Figure 3). Then, insert the backflow preventer into the adapter. Next, the Polypropylene/ PVC adapter is inserted into the outlet of the backflow preventer and secured with the attached locking ring. After that, the remainder of the exhaust vent side of the common system is composed of Schedule 40 PVC pipe and fittings. Straight pipe to tee - Use field-supplied straight pipe sections to reach the horizontal part of the system that runs above the heaters. The total height from the bottom of the heater to the centerline of the horizontal must be from 80” to 110”. LOCKING RING FIGURE 3. OUTLET VENT ADAPTER & ADAPTER TO PVC 150 - 250 MODELS300 to 500 MODELS Servicing should only be performed by a 4ualified Service Technician
8 INLET AIR SIDE Adapter to inlet - The water heater’s air inlet is either a 3” or 4” PVC coupling. For the 150 to 250 models, attach a 3” to 4” reducing adapter and then, a 4” to 6” reducing adapter to begin the 6” vent connector. The 300 to 500 models require only a 4” to 6” reducing adapter. A 90° elbow is then attached to turn the connector vertical, towards the remainder of the system. Straight pipe to tee - A straight pipe section is used to run from the elbow to the bottom of the tee. The length may be adjusted so that the height to the center line of the horizontal run is 80” to 110” from the base of the heater. In certain cases, it is desirable to provide a means to drain water from the weather out of the air inlet. The drain should be a 6” diameter fitting with a J-trapped drain, such as detailed in the water heater’s Instruction Manual. The drain should be placed just before the tee that joins the common section with the connectors (away from the heaters). Common Sections The common sections are the pipes that carry the vent gas or intake air to and from the outside. Each pipe\ must extend from the tee over the heaters to the outside/ outdoors etc. It is preferred to run the air and vent sections next to each other, over a similar path as shown in Figure 1. However, differences may be needed in the field. The requirements for both the air intake and vent common sections are: • The equivalent length straight pipe and elbows of each common section will be limited\ to between 3 feet and 50 feet. Each (3) 90° elbow is equivalent to 5 feet pipe and a 45° elbow is equivalent to 2½ feet of pipe. The maximum number of elbows is three. The terminal elbows are not considered in calculating maximum or minimum equivalent lengths; • Each common section may include vertical sections, but the final terminations must be horizontal through the wall. Vertical section lengths must be included in the total equivalent length.\ • The horizontal vent section must be sloped upward at least 1/4” per f\ oot towards the vent terminal and • Each section must be supported as detailed in the above procedure. Terminations The placement of the vent and air terminals must follow the guidelines for terminal location found in the water heater’s Instruction Manual. All required clearances to building features are the same as found in the water heater’s Instruction Manual. The combustion vent terminal is a coupling with a screen that finishes the end of the pipe. The air inlet terminal must use the 90° elbow pointed down as shown in Figure 2. Clearances to the ground and to anticipated snow level must be as shown in Figure 2. The ends of both terminals must be protected with the bird screens supplied with the terminations. Servicing should only be performed by a 4ualified Service Technician
9 POLYPROPYLENE COMMON VENT KIT 9009132005 OR 9009226005 INSTRUCTIONS This kit instruction is a supplement to the Instruction Manual that is supplied with the water heater. The multiple heater installation must satisfy all the requirements of the Instruction Manual as well as the requirements of this kit instruction. The installer may also consult with installation instructions from the vent manufacturer. In the event of any conflict between the documents, these instructions take precedence. The kit is meant to accommodate heaters that are 52” apart, on center. The heaters listed previously may also be common vented using a Polyprop\ ylene system manufactured by M&G Duravent. This is a system listed to UL 1738 and ULC S636 and may be required in some localities. POLYPROPYLENE PARTS LIST Each kit contains the adapters needed to connect the vent and air intake system to one heater. Additional parts are needed to create the connectors, common sections and vent terminations. A list of additional parts is included below for your convenience. For example, to common vent 2 heaters requires 2 of the kits in Table 3A plus the additional parts in Table 4. This is enough to create the system in Figure 4. Additional Polypropylene parts may be needed to extend the pipe systems between the heaters and the terminations. 2 1 3 ITEM NO. KIT # NUMBERDESCRIPTIONKIT SUPPLIED 1VENT ADAPTER,OUTLET,6,PP,DURAVENT1 2 9009132005VENT ADAPTER,INLET,6,PP,DURAVENT1 3 VENT ADAPTER CONNECTOR,DURAVENT1 TABLE 3A. POLYPROPYLENE COMMON VENT KIT (150 - 250 MODELS) (ONE KIT NEEDED FOR EAC\ H HEATER) ITEM NO. KIT # NUMBERDESCRIPTIONKIT SUPPLIED 1 APPLIANCE-INCREASER, BTH 300-500, DURAVENT 1 29009226005BACKFLOW PREVENTER, BTH 300-500, DURAVENT1 TABLE 3B. POLYPROPYLENE COMMON VENT KIT (300 - 500 MODELS) (ONE KIT NEEDED FOR EAC\ H HEATER) Servicing should only be performed by a 4ualified Service Technician
10 1 24 5 7 3 UV RESISTANT(BLACK) UV RESISTANT(BLACK) 8 NOTES:ITEMS 1 THRU 8 ARE FIELD SUPPLIED ONLY1.LOCKING RINGS ARE PREINSTALLED ON PIPES, TEES, AND ELBOWS2. ITEM NO.PART NUMBERDURAVENT STOCK NO.DESCRIPTION ADDITIONALREQUIRED FOR 2 HEATERS 1 N/A810009776VENT PIPE,6,72,PP,DURAVENT6 2 N/A810009774VENT PIPE,6,36,PP,UV,DURAVENT2 3 N/A810009772VENT PIPE,6,12,PP,DURAVENT4 4 N/A810009787VENT TEE W/CAP,90,6,PP,DURAVENT2 5 N/A810009783ELBOW,90,6,PP,UV,DURAVENT1 6 N/A810004276BIRD SCREEN,6,DURAVENT2 7 N/A810009782ELBOW,90,6,PP,DURAVENT4 89005376205N/APLATE,WALL COVER,0.052,GALV,STEEL4 6 TABLE 4. ADDITIONAL REQUIRED PARTS - POLYPROPYLENE 0036004800550059004C0046004C0051004A00030056004B00520058004F0047000300520051004F005C000300450048000300530048005500490052005500500048004700030045005C000300440003003400580044004F004C00BF0048004700030036004800550059004C004600480003