Home
>
American Water Heater
>
Gas Heater
>
American Water Heater 80 Thermal Efficiency UltraLow NOx Heavy Duty Commercial Gas Water Heater BCL3 User Manual
American Water Heater 80 Thermal Efficiency UltraLow NOx Heavy Duty Commercial Gas Water Heater BCL3 User Manual
Have a look at the manual American Water Heater 80 Thermal Efficiency UltraLow NOx Heavy Duty Commercial Gas Water Heater BCL3 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
21 WATER HEATER INSTALLATION T&P VALVE DISCHARGE PIPE Explosion Hazard Temperature-Pressure Relief Valve must comply with ANSI Z21.22- CSA 4.4 and ASME code. Properly sized temperature- pressure relief valve must be installed in opening provided. Can result in overheating and excessive tank pressure . Can cause serious injury or death. This water heater is provided with a properly rated/sized and certified combination temperature - pressure (T&P) relief valve by the manufacturer. See Temperature-Pressure Relief Valve on pages 13-14 for information on replacement and other requirements. Water Damage Hazard Temperature-Pressure Relief V alve discharge pipe must terminate at adequate drain. CAUTION Install a discharge pipe between the T&P valve discharge opening and a suitable floor drain. Do not connect discharge piping directly to the drain unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in adequate quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage. T&P Valve Discharge Pipe Requirements: • Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions. • Shall not be plugged or blocked. • Shall not be exposed to freezing temperatures. • Shall be of material listed for hot water distribution. • Shall be installed so as to allow complete drainage of both the Temperature-Pressure Relief Valve and the discharge pipe. • Must terminate a maximum of six inches above a floor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building. • Shall not have any valve or other obstruction between the relief valve and the drain. WATER LINE CONNECTIONS The water piping installation must conform to these instructions and to all local code authority having jurisdiction. Good practice requires that all heavy piping be supported. Read and observe all requirements in the following sections before installation of the water piping begins: 1. Water Temperature Control and Mixing Valves on page 12. 2. Dishwashing Machines on page 13. 3. Temperature-Pressure Relief Valve on page 13. 4. Closed Systems and Thermal Expansion on page 13. 5. For multiple water heater installations see Water Piping Diagrams beginning on page 35. Water (potable) Heating And Space Heating 1. All piping components connected to this unit for space heating applications shall be suitable for use with potable water. 2. Toxic chemicals, such as those used for boiler treatment, shall NEVER be introduced into this system. 3. This unit may NEVER be connected to any existing heating system or component(s) previously used with a non-potable water heating appliance. 4. When the system requires water for space heating at temperatures higher than required for domestic water purposes, a tempering valve must be installed. Please refer to Water Piping Diagrams beginning on page 35 of this manual for suggested piping arrangements. 5. These water heaters cannot be used in space heating applications only Thermometers (not Supplied) Thermometers should be obtained and field installed as shown in the installation diagrams. Thermometers are installed in the system as a means of detecting the temperature of the outlet water supply. Water Piping Diagrams This manual provides detailed water piping diagrams for typical methods of application for the water heaters, see Water Piping Diagrams beginning on page 35. The water heater may be installed by itself, or with a separate storage tank. When used with a separate storage tank, the circulation may be either by gravity or by means of circulating pump. Adjust flow by throttling a full port ball valve installed in the circulating line on the outlet side of the pump. Never throttle flow on the suction side of a pump. See the Water Piping Diagrams beginning on page 35. NOTE: In addition to the factory installed Temperature-Pressure Relief Valve (T&P valve) on the water heater, each remote storage tank that may be installed and piped to a water heating appliance must also have its own properly sized, rated and approved Temperature-Pressure Relief Valve installed. Call the toll free technical support phone number listed on the back cover of this manual for further assistance in sizing a T&P valve for remote storage tanks.
22 INSTALLATION DIAGRAMS - TOP INLET/OUTLET USAGE Use of the top inlet water connection requires an inlet dip tube (refer to figure 19). The tube is supplied in the heater. Follow caution labels if applying heat to this fitting. Do not allow pipe dope to contact the plastic tube during installation.TUBE INLET INSTALLATION FIGURE 19.
23 HEATER WIRING ELECTRICAL WIRING All electrical work must be installed in accordance with the National Electrical Code, ANSI/NFPA 70 or the Canadian Electrical Code, CSA C22.1 and local requirements. When installed, the water heater must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70 or the Canadian Electrical Code, CSA C22.1. If any of the original wire as supplied with the water heater must be replaced, it must be replaced with 105°C rated wiring or its equivalent, except in the burner housing. In this case 200°C rated wire must be used. The controls of this water heater are polarity sensitive. Be certain to properly wire the hot and neutral connections. 24V 24V(GND)GNDPVMV/PVMV SPARK 4 2 BK BKR R R R LOWER PROBEUPPER PROBE THERMOSTAT BLOWER PRESSURE SWITCH 1a1b1 120 VAC HOT120 VAC NUETRAL EARTH GROUND PILOT IGNITION MODULE GAS VALVE BLOWER FACTORY INSTALLE DBY INSTALLER POWER RELAY IF ANY OF THE ORIGINAL WIRE AS SUPPLIED MUST BE REPLACED US ONLY 18 AWG \ 105C 600V UL AWM STYLE #1015 WIRE EXCEPT GAS VALVE CABLE WHICH MUST USE 2 CONDUCTOR 18 AWG 80C 300V UL CATEGORY QPTZ POWER LIMITED CIRCUIT CABL E327382-000 REV. 00 R R R BLK W WBLK W LEGEND:R= REDW= WHITEBLK= BLACKY= YELLOWY MP BLUE BLK LOW GASPRESSURESWITCH(SELECT MODELS) FIGURE 20. WIRING DIAGRAM
24 GAS PIPING Contact your local gas service company to ensure that adequate gas service is available and to review applicable installation codes for your area. Size the main gas line in accordance with Table 7. The figures shown are for straight lengths of pipe at 0.5 in. W.C. pressure drop, which is considered normal for low pressure systems. Note: Fittings such as elbows, tees and line regulators will add to the pipe pressure drop. Also refer to the current edition of the National Fuel Gas Code. Schedule 40 Steel or Wrought Iron Pipe is the preferred material for the gas line of this water heater. It is imperative to follow the sizing recommendations in the current edition of the National Fuel Gas Code if Corrugated Stainless Steel Tubing (CSST) is used as the gas line for this water heater. The heater is not intended for operation at higher than 14.0" W.C.- natural gas, (1/2 pound per square inch gage) supply gas pressure. Exposure to higher supply pressure may cause damage to the gas control valve which could result in fire or explosion. If overpressure has occurred such as through improper testing of gas lines or emergency malfunction of the supply system, the gas control valve must be checked for safe operation. Make sure that the outside vents on the supply regulators and the safety vent valves are protected against blockage. These are parts of the gas supply system, not the heater. Vent blockage may occur during ice storms. TABLE 7 - GAS SUPPLY PIPE LENGTHS (IN FEET) Maximum Equivalent Pipe Length - Natural Gas Only Input rate (BTU/HR) Schedule 40 Steel or Wrought Iron Pipe 1/2" 3/4" 1"1 1/4" 1 1/2" 120,000 2070200 200200 154,000 1040150 200200 180,000 -30 100 200200 199,000 -30 90200 200 250,000 -20 60200 200 275,000 -10 50200 200 310,000 -10 40150 200 366,000 --30 100 200 390,000 --20 100 200 Fitting Type* Equivalent length in feet 45°Ell 0.71.01.21.61.9 90°Ell 1.62.12.63.54.0 Te e 3.14.15.26.98.0 Natural Gas 0.60 Specific Gravity, 0.50" W.C. Pressure Drop *Screwed Fittings It is important to guard against gas control valve fouling from contaminants in the gas ways. Such fouling may cause improper operation, fire or explosion. If copper supply lines are used they must be internally tinned and certified for gas service. Before attaching the gas line, be sure that all gas pipe is clean on the inside. To trap any dirt or foreign material in the gas supply line, a sediment trap must be incorporated in the piping (see Figure 21). The sediment trap must be readily accessible and not subject to freezing conditions. Install in accordance with recommendations of serving gas suppliers. Refer to the current edition of the National Fuel Gas Code. To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to gas control valve inlet. Apply joint compounds (pipe dope) sparingly and only to the male threads of pipe joints. Do not apply compounds to the first two threads. Use compounds resistant to the action of liquefied petroleum gases. Gas Meter Size – Natural Gases Only Be sure the gas meter has sufficient capacity to supply the full rated gas input of the water heater as well as the requirements of all other gas fired equipment supplied by the meter. If gas meter is too small, ask the gas company to install a larger meter having adequate capacity. GAS PIPING AND SEDIMENT TRAP INSTALLATION FIGURE 21. GAS LINE LEAK TESTING Fire and Explosion Hazard Leak test before placing the water heater in operation. Disconnect gas piping and main gas shutof f valve before leak testing. Install sediment trap in accordance with NFP A 54. Use joint compound or Teflon tape compatible with propane gas. Any time work is done on the gas supply system perform a leak test to avoid the possibility of fire or explosion. 1. For test pressures exceeding 1/2 psi (3.45 kPa) disconnect the water heater and its Main Gas Shutoff Valve from the gas supply piping system during testing, see Figure 21. The gas supply line must be capped when disconnected from the water heater. 2. For test pressures of 1/2 psi (3.45 kpa) or less, the water heater need not be disconnected, but must be isolated from the supply gas line by closing the Main Gas Shutoff Valve during testing. 3. Coat all supply gas line joints and connections upstream of the water heater with a non-corrosive soap and water solution to test for leaks. Bubbles indicate a gas leak. Do not use matches, candles, flame or other sources of ignition for this purpose. 4. Repair any leaks before placing the water heater in operation. PURGING Gas line purging is required with new piping or systems in which air has entered. Purging should be performed per the current edition of NFPA 54 the National Fuel Gas Code.
25 PRIOR TO START UP Installation and start up of this water heater requires abilities and skills equivalent to that of a licensed tradesman in the field involved, see Qualifications on page 6. Do not place the water heater in operation if any part has been under water. Immediately call a qualified service technician to inspect the water heater and to replace any part of the control system and any gas control which has been under water. Light the water heater in accordance with the Lighting and Operation Instruction label on the water heater and in this manual on page 27. The water heaters covered by this manual are equipped with an electronic control system that automatically sequences the Blower, the Igniter, the 24 VAC Gas Valve, Burner ignition, and flame sensing. The control system will lock out after three unsuccessful ignition attempts. Before attempting start up, thoroughly study and familiarize yourself with the exact Sequence Of Operation, see the written Sequence Of Operation on page 27 and the Sequence Of Operation Flow Chart on page 28. Be certain that the water heater is full of water, that air is purged from the gas and water lines and that there are no leaks in the gas and water lines. Ensure all inlet water valves are open. Filling The Water Heater Follow these steps to fill the water heater prior to start up. 1. Close the heater drain valve. 2. Open a nearby hot water faucet to permit the air in the system to escape. 3. Fully open the cold water inlet valve allowing the piping and water heater to fill with water. 4. Close the hot water faucet opened in Step 2 as water starts to flow. Supply Gas Line Purging Fire or Explosion Hazar d Read instruction manual before installing, using or servicing water heate r. To avoid risk of fire or explosion purge discharge must not enter into confined areas or spaces where ignition can occur . The area must be well ventilated and all sources of ignition must be deactivated or removed. Gas line purging is required with new piping or systems in which air has entered. Use only the gas shown on the water heater rating label. Keep ignition sources away from faucets after extended periods of non-use. 1. Close the Main Gas Shutoff Valve, see Figure 21 on page 24. 2. Purge all air from the supply gas line up to the water heater’s Main Gas Shutoff Valve. 3. When all air has been purged from the supply gas line, tighten all supply gas line connections. 4. Check for gas leaks, see Gas Line Leak Testing on page 24 and repair any leaks found. START UP INITIAL START UP Required Test Equipment U-tube manometer, pressure gauge, or digital manometer. Recommended range: 20” W.C. (5 kPa). NOTE: All test equipment must be acclimated to ambient temperature before calibration and use. Preparation 1. Adjust the thermostat to the lowest temperature setting. 2. Turn the water heater’s on/off switch to the “off” position. 3. Close the Main Gas Shut Off Valve, see Figure 21 on page 24. 4. Wait five (5) minutes for any residual gas to clear. 5. Open the Supply Gas Pressure Port on the gas control valve by turning the center screw counter-clockwise. Connect the manometer to the supply gas pressure test port, see Figure 22. 6. Open the Main Gas Shutoff Valve. 7. Measure and record the supply gas pressure, this is a “static” supply gas pressure reading; while the water heater is not firing. FIGURE 22. – TOP VIEW Lighting The Water Heater 1. Turn the water heater’s on/off switch to the “on” position. 2. Adjust the thermostat to the desired water temperature. 3. Record the supply gas pressure when the 24 VAC Gas Valve is energized and the Burner is operating. This is a “dynamic” gas pressure reading; while the water heater is firing. 4. Compare the actual supply gas pressure reading recorded above to the required minimum/maximum values given in Table 3 on page 8. Adjust supply gas pressure as necessary, see the instructions that follow. 5. After the supply gas pressure adjustments are complete, turn off the water heater and close the Main Gas Supply Shut Off Valve. Disconnect the manometer from the Supply Gas Pressure Port and turn the center screw clockwise until the port is closed. Supply Gas Pressure Adjustment Fire and Explosion Hazar d Turn of f gas lines during installation. Contact a qualified installer or servic e technician for installation and service. Excessive gas pressure to gas valve ca n cause serious injury or death. Do not use water heater with any gas other than the gas shown on the rating label.
26 7. If improper venting is observed during any of the above tests, the venting system must be corrected. FAILURE TO CORRECT BACK DR AFTS MAY CAUSE AIR CONTAMINATION AND UNSAFE CONDITIONS. • If the back draft cannot be corrected by the normal method or if a suitable draft cannot be obtained, a blower type flue gas exhauster must be employed to ass ure proper venting and correct combustion. CHECKING THE INPUT Follow these instructions to determine the firing rate of the water heater. 1. Follow the procedure described in the "Initial Start Up" section on page 25 to measure the static and dynamic supply gas pressures. Verify that the static and dynamic supply gas pressures conform to the values listed in Table 3 on page 8. 2. Use this formula to “clock” the meter. Be sure that other gas consuming appliances are not operating during this interval. (3600/T) x H = Btuh T = Time in seconds to burn one cubic foot of gas. H = Btu’s per cubic foot of gas. Btuh = Actual heater input. Example: (BCL3100T1996NOX) T = 18.1 seconds H = 1000 BTU/Cu.Ft. Btuh = (3,600/18.1) x 1,000 = 199,000 (Compare with BCL3100T1996NOX model and rating.) UNDER NO CIRCUMSTANCES SHOULD THE GAS INPUT EXCEED THE INPUT SHOWN ON THE HEATER'S R ATING PLATE. WATER TEMPERATURE ADJUSTMENT Wa ter temperature over 125°F (52°C) can cause severe burns instantly resulting in severe injury or death. Children, the elderly and the physically or mentally disabled are at highest risk for scald injury . Feel water before bathing or showering. Te mperature limiting devices such as mixing valves must be installed when required by codes and to ensure safe temperatures at fixtures. The water temperature is controlled by a thermostat, Fig. 3, which has two sensing elements. One sensor is located near the top of the tank and the other is near the center. The thermostat is set in the lowest position before the heater leaves the factory. The thermostat temperature dial, Fig. 3, is accessible by removing the control cover. The dial is adjustable and may be set for 120°F (49°C) to 180°F (82°C) water temperature, but 120°F (49°C) is the recommended starting point. It is suggested the dial be placed on the lowest setting which produces an acceptable hot water supply. This will always give the most energy efficient operation. The temperature control has a 4°F fixed differential. Supply gas pressure shall be measured while the water heater is not firing (static pressure) and while the water heater is firing at full capacity (dynamic pressure). If the supply gas pressure to the water heater is not between the required minimum and maximum values given in Table 3 on page 8 adjust the supply gas regulator as necessary. Adjust the supply gas regulator(s) per the regulator manufacturer’s instructions to achieve the required “static” and “dynamic” supply gas pressure. Multiple Water Heater Installations: In multiple water heater installations or in installations where the installed water heater(s) share a common gas supply main with other gas fired appliances; the supply gas pressures shall be measured at each water heater with all gas fired appliances connected to a common main firing at full capacity. On multiple water heater installations the supply gas line regulators shall be adjusted to provide gas pressure to each water heater within the minimum and maximum supply pressure requirements listed in Table 3 on page 8 with all gas fired appliances connected to a common gas main firing at full capacity. NOTE: A pressure drop of more than 1.5” W. C. (0.37 kPa) when the Main Burner ignites is an indication of an inadequate supply of gas and can lead to ignition failure, rough starts and/ or rough operation. If a drop of more than 1.5” W. C. (0.37 kPa) in supply gas pressure occurs when the Main Burner ignites, ensure the supply gas lines and regulator(s) are properly sized and installed. See the requirements for Supply Gas Regulator on page 12 and Gas Piping on page 24. Ensure all requirements and installation instructions are maintained. CHECKING VENTING The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation. 1. Seal any unused openings in the venting system. 2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1or the CAN/ CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition. 3. So far as is practical, close all building doors and windows and all doors between the space in which the water heater(s) connected to the venting system are located and other spaces of the building. Turn on all appliances not connected to the venting system. Turn on all exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Close fireplace dampers. 4. Follow the lighting instruction. Place the water heater being inspected in operation. Adjust thermostat so water heater shall operate continuously. 5. Inspect vent system for leakage after 5 minutes of main burner operation. 6. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.
27 8. If the Ignition Control does not sense the pilot flame during the ignition trial period, the Ignition Control shuts the Pilot Gas Valve and turns off the Spark Igniter. After 5 minute delay, a new trial for ignition is initiated. This sequence continues until the unit lights or “Call for Heat” is removed. 9. If the pilot flame is proved during the ignition trial period, the Ignition Control will energize the main gas control valve to start the heating cycle. If the flame signal is lost during the heating cycle, the Ignition Control closes the gas control valve and re- starts the ignition process at step 5. 10. Once the unit is satisfied, the Thermostat will turn off the 24vac power to the blower relay and the Ignition Control, and the unit will be in standby mode until another call for heat is initiated by the thermostat. See the flow chart on page 28 for more detailed information. SEQUENCE OF OPERATION The following information will describe the Sequence of Operation for this water heater. 1. Switch power on to unit. 2. Thermostat calls for heat. 3. Blower power relay is energized to start the blower. 4. The blower pressure switch is closed, 24VAC power is applied to the Ignition Control Module. 5. The Ignition Control performs diagnostic self check on system components. 6. After 30 seconds delay, the Ignition Control begins the trial for ignition by turning on the Spark Igniter and the Pilot Gas Valve. 7. The Ignition Control monitors the Flame Sensor during the ignition trial period. LIGHTING & OPERATING LABEL FIGURE 23.
28 SEQUENCE OF OPERATION FLOW CHART Description of this flow chart can be found in the “SEQUENCE OF OPERATION” section found on page 27. Thermostat calls f\uor heat Switch power on to\u unit \flower engages Prove\ur Switc h \bgnition Control mo\unitors flame signal Loss of flame sign\ual ? YE S YES NO NO \flower power relay is energ ized to st art blower \bgnion Contr ol provides power to Spa\urk \bgnite r and Pilot Gas V alve and monitor s Flame Sensor to de\ut ermine if \furner is\u lit 24V AC power to the \bgn\uion Cont rol and self check Tr ial for ignio n Spark O and Open \umain Gas V alve 5 minutes re try dela y Close pilot gas va lve and Spark o Flame Pro ved? Close Main valve and Pilot valve 30 Seconds P repur ge Thermos tat is sase d \flower – o; \flower\u Pr over – opens \bgnion Contr ol – o; Gas Valve – closes FIGURE 24.
29 VENTING SYSTEM Examine the venting system every six months for obstructions and/or deterioration of the vent piping. Check all vent system connections for leakage and repair or reseal as necessary. Remove all soot or other obstructions from chimney which will retard free draft. INTAKE AIR SCREEN The intake air screen is attached to the inlet end of the combustion blower. Inspect the intake air screen every six months. The intake air screen should be cleaned of any buildup of debris or foreign material. TEMPERATURE-PRESSURE RELIEF VALVE TEST Burn hazard. Hot water discharge . Keep clear of Temperature- Pressure Relief Valve discharge outlet . It is recommended that the Temperature-Pressure Relief Valve should be checked to ensure that it is in operating condition every 6 months. When checking the Temperature-Pressure Relief Valve operation, make sure that (1) no one is in front of or around the outlet of the Temperature-Pressure Relief Valve discharge line, and (2) that the water discharge will not cause any property damage, as the water may be extremely hot. Use care when operating valve as the valve may be hot. To check the relief valve, lift the lever at the end of the valve several times, see Figure 25. The valve should seat properly and operate freely. If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater and drain the water heater, see Draining and Flushing on page 30. Replace the Temperature- Pressure Relief Valve with a properly rated/sized new one, see Temperature-Pressure Relief Valve on pages 13-14 for instructions on replacement. FIGURE 25. If the Temperature-Pressure Relief Valve on the water heater weeps or discharges periodically, this may be due to thermal expansion. NOTE: Excessive water pressure is the most common cause of Temperature-Pressure Relief Valve leakage. Excessive water system pressure is most often caused by "thermal expansion" in a "closed system." See Closed Water Systems and Thermal Expansion on page 13. The Temperature-Pressure Relief Valve is not intended for the constant relief of thermal expansion. Temperature-Pressure Relief Valve leakage due to pressure build up in a closed system that does not have a thermal expansion tank installed is not covered under the limited warranty. Thermal expansion tanks must be installed on all closed water systems. DO NOT PLUG THE TEMPERATURE-PRESSURE RELIEF VALVE OPENING. THIS CAN CAUSE PROPERTY DAMAGE, SERIOUS INJURY OR DEATH. Explosion Hazar d Temperature-Pressure Relief Valve must comply with ANSI Z21.22- CSA 4.4 and ASME code. Properly sized temperature- pressure relief valve must be installed in opening provided. Can result in overheating and excessive tank pressure. Can cause serious injury or death. ANODE ROD INSPECTION The anode rod is used to protect the tank from corrosion. Most hot water tanks are equipped with an anode rod. The submerged rod sacrifices itself to protect the tank. Instead of corroding tank, water ions attack and eat away the anode rod. This does not affect water’s taste or color. The rod must be maintained to keep tank in operating condition. Anode deterioration depends on water conductivity, not necessarily water condition. A corroded or pitted anode rod indicates high water conductivity and should be checked and/or replaced more often than an anode rod that appears to be intact. Replacement of a depleted anode rod can extend the life of your water heater. Inspection should be conducted by a qualified technician, and at a minimum should be checked annually after the warranty period. Artificially softened water is exceedingly corrosive because the process substitutes sodium ions for magnesium and calcium ions. The use of a water softener may decrease the life of the water heater tank. The anode rod should be inspected after a maximum of three years and annually thereafter until the condition of the anode rod dictates its replacement. Anode rod replacement is not covered by warranty. NOTE: Artificially softened water requires the anode rod to be inspected annually. MAINTENANCE
30 DRAINING AND FLUSHING Burn harzard. Hot water discharge.Keep hands clear of drain valve discharge. It is recommended that the water heater storage tank be drained and flushed every 6 months to reduce sediment buildup. The water heater should be drained if being shut down during freezing temperatures. To Drain the Water Heater Storage Tank: 1. Turn off the electrical supply to the water heater. 2. Turn off the gas supply at the Main Gas Shutoff Valve if the water heater is going to be shut down for an extended period. 3. Ensure the cold water inlet valve is open. 4. Open a nearby hot water faucet and let the water run until the water is no longer hot. 5. Close the cold water inlet valve to the water heater. 6. Connect a hose to the water heater drain valve and terminate it to an adequate drain. 7. Open the water heater drain valve and allow all the water to drain from the storage tank. 8. Close the water heater drain valve when all water in the storage tank has drained. 9. Close the hot water faucet opened in Step 4. 10. If the water heater is going to be shut down for an extended period, the drain valve should be left open. To Flush the Water Heater Storage Tank: 1. Turn off the electrical supply to the water heater. 2. Ensure the cold water inlet valve is open. 3. Open a nearby hot water faucet and let the water run until the water is no longer hot. Then close the hot water faucet. 4. Connect a hose to the drain valve and terminate it to an adequate drain. 5. Ensure the drain hose is secured before and during the entire flushing procedure. Flushing is performed with system water pressure applied to the water heater. 6. Open the water heater drain valve to flush the storage tank. 7. Flush the water heater storage tank to remove sediment and allow the water to flow until it runs clean. 8. Close the water heater drain valve when flushing is completed. 9. Remove the drain hose. 10. Fill the water heater - see Filling The Water Heater in this manual. 11. Turn on the electrical supply to place the water heater back in operation. 12. Turn on the gas supply to the water heater at the Main Gas Shutoff Valve. 13. Allow the water heater to complete several heating cycles to ensure it is operating properly. PERIODIC REMOVAL OF LIME DEPOSITS FROM TANK TYPE COMMERCIAL WATER HEATERS The amount of calcium carbonate (lime) released from water is in direct proportion to water temperature and usage, see chart. The higher the water temperature or water usage, the more lime deposits are dropped out of the water. This is the lime scale which forms in pipes, heaters and on cooking utensils. Lime accumulation may affect the life of equipment, the efficiency of the heater, and fuel consumption characteristics. The usage of water softening equipment greatly reduces the hardness of the water. However, this equipment does not always remove all of the hardness (lime). For this reason it is recommended that a regular schedule for deliming be maintained. The time between cleaning will vary from weeks to years depending upon water conditions and usage. The depth of lime buildup should be measured periodically. Heaters equipped with cleanouts will have about 2" of lime buildup when the level of lime has reached the bottom of the cleanout opening. A schedule for deliming should then be set up based on the amount of time it would take for a 1" buildup of lime. It is recommended that the water heater initially be inspected after 6 months. Example 1: Initial inspection after 6 months shows 1/2" of lime accumulation. Therefore, the heater should be delimed once a year. Example 2: Initial inspection after 6 months shows 2" of lime accumulation. Therefore, the heater should be delimed every 3 months. FIGURE 26. DELIMING SOLVENTS UN•LIME is recommended for deliming. UN•LIME is a patented food grade acid which is safe to handle and does not create the harmful fumes which are associated with other products. UN•LIME may be obtained from your dealer, distributor or water heater manufacturer. Order Part Number 9005416105, 1 gallon, packed 4 gallons per case or Part Number 9005417105, 5 gallon container.