11SETTING THE WATER HEATER TEMPERATURE AT 120°F (49°C) (APPROX. " " MARK ON FACE OF THE TEMPERATURE ADJUSTING DIAL) WILL REDUCE THE RISK OF SCALDS. Some States or Provinces require settings at specific lower temperatures. Figure 6 shows the approximate water temperatures produced at various thermostat settings. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 20°F (11°C). If you experience this...
Page 12
121. Provide complete combustion of gas. 2. Cause rapid ignition and carryover of flame across entire burner. 3. Give reasonably quiet operation during ignition, burning and extinction. 4. Cause no excessive lifting of flames from burner ports. If preceding burner characteristics are not evident, check for accumulat\ ion of lint or other foreign material that restricts or blocks the air openi\ ngs to the heater or burner. WARNINGSOOT BUILD-UP INDICATES A PROBLEM THAT REQUIRES CORRECTION BEFORE...
Page 13
13 BLOWER MAINTENANCE For safety and satisfactory operation it is recommended that the blower be checked once a year by a competent service person. 1. MOTOR - The motor is factory oiled and sealed and requires no further maintenance. 2. WHEEL - Wheel must be clean of soot, ash or any other coating which inhibits either rotation or air flow. Remove all foreign material from vent system. 3. The pressure switch is inside the blower control box and is connected to the blower housing with a tube....
Page 14
14 TANK CLEANOUT PROCEDURE The following practices will ensure longer life and enable the unit to operate at its designed efficiency: 1. Once a month the heater should be flushed. Open the drain valve and allow two gallons of water to drain from the heater. Inlet water valve should remain open to maintain pressure in tank. 2. A cleanout opening is provided for periodic cleaning of the tank. Gas must be shut off and heater drained before opening cleanout. To clean heater through cleanout opening,...
Page 15
15 cold water inlet line and allow water to flow through heater and out drain valve. Don’t forget to plug vent and cap opening in Flo-Jug. 9. When flushing is completed: • Fill heater being certain to expel air from tank through a nearby hot water faucet or, if removed, the relief valve opening. • The heater relief valve can be washed in UN•LIME if it is limed. • Replace relief valve if removed for deliming. • Restore gas, oil or electrical supply to heater. • Check for water leakage. 10....
Page 16
16 NOTE: Anode must remain installed (except for inspection) to avoid shortening tank life. See LIMITED WARR ANTY. Replace as necessary. SERVICE AND REPAIR The water heater requires no special care other than the normal maintenance as noted above. If you are having a problem with your water heater, before calling for service please refer to the following TROUBLESHOOTING sections. If service becomes necessary, contact your dealer, installer or an authorized service agent. Do not attempt to...
Page 17
17 TROUBLESHOOTING For your safety, water heater service should be performed only by a qualified service technician. Read the GENERAL SAFETY INFORMATION section first. PROBLEM POSSILBE MALFUNCTION SERVICE TO BE PERFORMED NOT ENOUGH OR NO HOT WATER 1) Blower will not run. A) "ON/OFF" control switch turned off. Turn switch to the on position. B) Blower unplugged. Plug blower back into 115 vac. outlet. C) No power at outlet. Repair service to outlet. D) "ON/OFF" switch defective. Replace...
Page 18
18 TROUBLESHOOTING GUIDELINES TROUBLE SHOOTINGPlease check guidelines below. For your safety, water heater service should be performed only by a qualified service technician. Read the GENERAL SAFETY INFORMATION section first. INTELLI-VENT TROUBLESHOOTING CHART - USER CONTROL PROBLEM SOLUTION Inadequate or no earth ground 1. Ensure the wall outlet is properly grounded. 1 sensed by the Intelli-Vent™ control. 2. Ensure all ground connections/wires on the water heater are...
Page 19
19 TROUBLESHOOTING GUIDELINES TROUBLE SHOOTINGPlease check guidelines below. For your safety, water heater service should be performed only by a qualified service technician. Read the GENERAL SAFETY INFORMATION section first. INTELLI-VENT TROUBLESHOOTING CHART - USER CONTROL PROBLEMSOLUTION Ignition/ame failure. 6 The water heater has reached th e maximum number of retries and is currently lockedoutfor one hour . Cycle the power to the water heater of f and on to reset. Service Note: Ther esistance(...
Page 20
20 TROUBLESHOOTING GUIDELINES TROUBLE SHOOTINGPlease check guidelines below. For your safety, water heater service should be performed only by a qualified service technician. Read the GENERAL SAFETY INFORMATION section first. INTELLI-VENT TROUBLESHOOTING CHART - USER CONTROL PROBLEMSOLUTION 15 # LED ST ATUS B C D E F1. Turn off power to the water heater. 2. Unplug the ignitor assembly plug from the control. Check t he resistance of the black resistor wire between pins 3 & 4 with an...