Home
>
American Water Heater
>
Gas Heater
>
American Water Heater 74 Gallon 80 Thermal Efficiency UltraLow NOx Heavy Duty Commercial Gas Water Heater User Manual
American Water Heater 74 Gallon 80 Thermal Efficiency UltraLow NOx Heavy Duty Commercial Gas Water Heater User Manual
Have a look at the manual American Water Heater 74 Gallon 80 Thermal Efficiency UltraLow NOx Heavy Duty Commercial Gas Water Heater User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
1 PRINTED IN U.S.A. 1212 PART NO. 325370-000 MODELS BBCN375T754NV PLACE THESE INSTRUCTIONS ADJACENT TO HEATER AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE. COMMERCIAL ULTRA LOW NOx GAS WATER HEATER Glass-Lined Tank-type Water Heater • INSTALLATION • OPERATION • SERVICE • MAINTENANCE • LIMITED WARRANTY CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY. PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE. Series 100 www .americanwaterheate r.co m American Wa ter Heater Johnson Cit y, TN 37605
2 FOREWORD The design of model BBCN375T754NV complies with the current edition of ANSI Z21.10.3/CSA 4.3 as automatic storage or automatic circulating tank type water heaters. Installation diagrams are found in this manual. These diagrams will serve to provide the installer with a reference for the materials and method of piping necessary. It is highly essential that all water and gas piping be installed as shown on the diagrams. In addition to these instructions, the equipment shall be installed in accordance with those installation regulations in force in the local area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made. ROUGH-IN DIMENSIONS FIGURE 1. The installation must conform to these instructions and the local code authority having jurisdiction. In the absence of local codes, the installation must comply with the following: In the United States:Current edition of the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 and the National Electrical Code, NFPA 70; In Canada:Current edition of the Installation Code CAN/CSA-B149.1 and the Canadian Electrical Code CSA C22.1. These are available from Canadian Standards Association, 8501 East Pleasant Valley Road, Cleveland, OH 44131 or National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269. *INSTALL IN ACCORDANCE WITH LOCAL CODES TOP VIEW TABLE 3, GAS AND ELECTRICAL CHARACTERISTICS All Models: Maximum supply pressure = 14.0 in. W.C. (3.48 kPa) Minimum supply pressure, Natural gas = 6 in. W.C. (1.49 kPa). Minimum pressures must be maintained under both load and no load (stati\ c and dynamic) conditions. Recovery ratings are based on 80% thermal efficiency. TABLE 1, DIMENSIONS Units AB CDEFGHJK L M Inches CM 66 5/8 169.22 58 3/4 134.23 30 15/16 78.58 27 3/4 70.5 15 1/4 38.6 4 10.2 15 3/4 40.0 16 40.6 1 1/4 3.2 1 1/4 NPT 1/2 NPT 12 1/4 31.1 TABLE 2, RECOVERY RATINGS Manifold Pressure Electrical Characteristics Type of gas Inches W.C.kPaVoltz/Hz Amperes Natural Gas 4.01.12 120/160
3 GENERAL SAFETY INFORMATION PRECAUTIONS DO NOT USE THIS WATER HEATER IF ANY PART HAS BEEN UNDER WATER. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water. IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO NOT OPERATE HEATER UNTIL ALL CORRECTIVE STEPS HAVE BEEN MADE BY A QUALIFIED SERVICEMAN. 1. EXTERNAL FIRE. 2. DAMAGE. 3. FIRING WITHOUT WATER. 4. SOOTING. Heater must be protected from freezing downdrafts during shutdown periods. GROUNDING INSTRUCTIONS This water heater must be grounded in accordance with the National Electrical Code and/or local codes. These must be followed in all cases. This water heater must be connected to a grounded metal, permanent wiring system; or an equipment grounding conductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead on the water heater, see Figure 5. TABLE OF CONTENTS \ Page ROUGH-IN DIMENSIONS ............................................................. 2 FOREWORD ........................................................................\ ......... 2 GENERAL SAFETY INFORMATION ............................................. 2-4 Precautions ........................................................................\ ............ 3 Grounding Instructions ............................................................... 3 Chemical Vapor Corrosion ......................................................... 3 Extended Non-use Periods ........................................................ 3 Insulation Blankets ..................................................................... 4 High Altitude Installations ........................................................... 4 Circulating Pump ....................................................................... 4 INSTALLATION INSTRUCTIONS ................................................. 4-9 Required Ability ........................................................................\ ...... 4 Locating The Heater .................................................................. 4 Clearances ........................................................................\ ......... 5 Hard Water ........................................................................\ ........ 5 Air Requirements ....................................................................... 5 Venting ........................................................................\ ............... 6 Thermometers (Not Supplied) ................................................... 7 Combination Water (Potable) Heating and Space Heating ....... 7 Relief Valve ........................................................................\ ........ 7 Gas Piping ........................................................................\ ......... 7 Heater Wiring ........................................................................\ ..... 8 Wiring Diagram ........................................................................\ .. 8 Purging ........................................................................\ .............. 9 Gas Pressure Regulation .......................................................... 9 OPERATION ........................................................................\ ......... 9 To Operate The Heater ............................................................. 9 Lighting Instructions .................................................................. 10 Temperature Regulation ........................................................... 11 Checking Venting ...................................................................... 11 High Temperature Limit Switch ................................................. 11 SERVICE INFORMATION ............................................................ 12-13 Main Burner and Igniter ............................................................ 12 Checking Gas Input .................................................................. 12 Vent System ........................................................................\ ...... 12 Blower Maintenance ................................................................. 13 Relief Valve ........................................................................\ ....... 13 Hot Water Odor ........................................................................\ . 13 Winter Protection ...................................................................... 13 Replacement Parts ................................................................... 13 PREVENTIVE MAINTENANCE .................................................... 13-14 Procedure for Periodic Removal Of Lime Deposits .................. 13 Deliming Solvents ..................................................................... 13 Tank Cleanout Procedure ......................................................... 14 CHECKLIST ........................................................................\ ......... 15-16 Condensation ........................................................................\ .... 15 Anode ........................................................................\ ............... 15 Service & Repair ....................................................................... 16 TROUBLESHOOTING ................................................................. 17-20 NOTES ........................................................................\ ................. 21-22 LIMITED WARRANTY ................................................................... 23 CHEMICAL VAPOR CORROSION WARNINGCORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS. SUCH CORROSION MAY RESULT IN FAILURE AND RISK OF ASPHYXIATION. Spray can propellants, cleaning solvents, refrigerator and air condition\ ing refrigerants, swimming pool chemicals, calcium and sodium chloride (wat\ er softener salt), waxes, and process chemicals are typical compounds whic\ h are potentially corrosive. Do not store products of this sort near the heater. Also, air which is brought in contact with the heater should not contain\ any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outside sources. The limited warranty is voided when failure of water heater is due to a corrosive atmosphere. (Refer to the limited warranty for complete terms and conditions.) EXTENDED NON-USE PERIODS WARNINGHYDROGEN GAS CAN BE PRODUCED IN A HOT WATER SYSTEM SERVED BY THIS HEATER THAT HAS NOT BEEN USED FOR A LONG PERIOD OF TIME (GENERALLY TWO WEEKS OR MORE). HYDROGEN GAS IS EXTREMELY FLAMMABLE. To reduce the risk of injury under these conditions, it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance connected to the hot water system. If hydrogen is present, there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow. THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR THE FAUCET AT THE TIME IT IS OPEN. Page
4 INSULATION BLANKETS Insulation blankets available to the general public for external use on gas water heaters are not required for use on your water heater. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank water heaters. Your water heater meets or exceeds the current edition of ASHR AE/IES 90.1 standards with respect to insulation and standby loss requirement making an insulation blanket unnecessary. WARNING Should you choose to apply an insulation blanket to this heater, you should follow these instructions. Failure to follow these instructions can result in fire, asphyxiation , serious personal injury or death. • Do not apply insulation to the top of the water heater, as this will interfere with safe operation. • Do not cover the outer door, thermostat or temperature & pressure relief valve. • Do not allow insulation to come within 2" (5cm) of the floor to prevent blockage of combustion air flow to the burner. • Do not cover the instruction manual. Keep it on the side of the water heater or nearby for future reference. • Do obtain new warning and instruction labels from the manufacturer for placement on the blanket directly over the existing labels. • Do inspect the insulation blanket frequently to make certain it does not sag, thereby obstructing combustion air flow. HIGH ALTITUDE INSTALLATIONS Water heaters covered in this manual have been tested and approved for installation at elevations up to 7,700 feet (2,347 m) above sea level. For installation above 7,700 feet (2,347 m), the water heater’s Btu input should be reduced at the rate of 4 percent for each 1,000 feet (305 m) above sea level which requires replacement of the burner orifice in accordance with the National Fuel Gas Code ANSI Z223.1/ NFPA 54. Contact your local gas supplier for further information. Failure to replace the standard orifice with the proper high altitude orifice when installed at elevations above 7,700 feet (2,347 m) could result in improper and inefficient operation of the water heater, producing carbon monoxide gas in excess of the safe limits. This could result in serious injury or death. Contact your local gas supplier for any specific changes that may be required in your area. Upon completion of derating of the heater, adjustment to the gas pressure regulator may be required. See CHECKING THE INPUT section in this manual for inlet and manifold pressure requirements. Also due to the input rating reduction required at high altitudes, the output rating of the appliance is also reduced and should be compensated for in the sizing of the equipment for application. CIRCULATING PUMP A circulating pump is used when a system requires a circulating loop or there is a storage tank used in conjunction with the heater. Refer to the piping diagrams at rear of manual for electrical hookup information and install in accordance with the current edition of the National Electrical Code ANSI/NFPA No. 70. In Canada refer to Canadian Electrical Code CSA C22.1. Only all bronze circulating pumps are used with commercial water heaters. Although circulators are oiled and operated by the manufacturer some circulators must be oiled again before operating. Please refer to manufacturer’s instructions. INSTALLATION INSTRUCTIONS REQUIRED ABILITY INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TR ADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING, ELECTRICAL AND GAS SUPPLY WORK ARE REQUIRED. L O C AT I N G T H E H E AT E R WARNING THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH AS GAS WATER HEATERS IN ROOMS, GAR AGES OR OTHER AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED, OPER ATED OR REPAIRED. FLAMMABLE VAPORS ARE HEAV Y AND TR AVEL ALONG THE FLOOR AND MAY BE IGNITED BY THE HEATER’S PILOT OR MAIN BURNER FLAMES CAUSING FIRE OR EXPLOSION. SOME LOCAL CODES PERMIT OPER ATION OF GAS APPLIANCES IF INSTALLED 18 INCHES (45.7 CM) OR MORE ABOVE THE FLOOR. THIS MAY REDUCE THE RISK IF LOCATION IN SUCH AN AREA CANNOT BE AVOIDED. DO NOT INSTALL THIS WATER HEATER DIRECTLY ON A CARPETED FLOOR. A FIRE HAZARD MAY RESULT. Instead the water heater must be placed on a metal or wood panel extending beyond the full width and depth by at least 3 inches (7.6 CM) in any direction. If the heater is
5 installed in a carpeted alcove or closet, the entire floor shall be covered by the panel. Also, see the drain requirements. THIS HEATER SHALL BE LOCATED OR PROTECTED SO IT IS NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE. WARNING FLAMMABLE ITEMS , PRESSURIZED CONTAINERS OR ANY OTHER POTENTIAL FIRE HA ZARDOUS ARTICLES MUST NEVER BE PLACED ON OR ADJACENT TO THE HEATER. OPEN CONTAINERS OF FLAMMABLE MATERIAL SHOULD NOT BE STORED OR USED IN THE SAME ROOM WITH THE HEATER. When installing the heater, consideration must be given to proper location. Location selected should be as close to the stack or chimney as practicable, with adequate air supply and as centralized with the piping system as possible. THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE IT WILL BE SUBJECT TO FREEZING. THE HEATER SHOULD BE LOCATED IN AN AREA WHERE LEAK AGE FROM THE HEATER OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE ADJACENT AREA OR TO LOWER FLOORS OF THE STRUCTURE. WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE DR AIN PAN SHOULD BE INSTALLED UNDER THE HEATER. Such pans should be fabricated with sides at least 2" (5cm) deep, with length and width at least 2" (5cm) greater than the diameter of the heater and must be piped to an adequate drain. The pan must not restrict combustion air flow. Drain pans suitable for these heaters are available from from the manufacturer, authorized service agencies or distributors. CLEARANCES These heaters are approved for installation on combustible flooring in a closet having a ceiling 12" (30.5cm) above top cover and with clearances to combustible construction of 6" (15.2cm) from flue or vent connector, 0" (0cm) at the sides and rear and 5" (10.2cm) to front to prevent a possible fire hazard condition. A minimum of 4" (10.2cm) shall be allowed for installation of serviceable parts. HARD WATER Where hard water conditions exist, water softening or the threshold type of water treatment is recommended. This will protect the dishwashers, coffee urns, water heaters, water piping and other equipment. See MAINTENANCE section for details of tank cleanout procedure. AIR REQUIREMENTS REFER TO CURRENT EDITION OF THE "NATIONAL FUEL GAS CODE ANSI Z223.1/NFPA 54. FOR CANADA CONSULT CAN/ C SA - B149.1. KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLES, VAPORS AND LIQUIDS. DO NOT OBSTRUCT THE FLOW OF THE COMBUSTION OR VENTILATING AIR. WARNINGATTIC AND/OR EXHAUST FANS OPERATING ON THE PREMISES WITH A WATER HEATER CAN RESULT IN CARBON MONOXIDE POISONING AND DEATH. OPERATION OF THESE FANS CAN PRODUCE A NEGATIVE DRAFT IN THE AREA OF THE WATER HEATER PREVENTING THE PRODUCTS OF COMBUSTION FROM EXHAUSTING THROUGH THE CHIMNEY OR VENT PIPE. The venting of the water heater should be inspected by a qualified service technician at the time of installation and periodically thereafter to ensure a down-draft condition does not exist. WARNING FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR COMBUSTION AND VENTILATION. AN INSUFFICIENT SUPPLY OF AIR WILL CAUSE RECIRCULATION OF COMBUSTION PRODUCTS RESULTING IN AIR CONTAMINATION THAT MAY BE HAZARDOUS TO LIFE. SUCH A CONDITION OFTEN WILL RESULT IN A YELLOW, LUMINOUS BURNER FLAME, CAUSING CARBONING OR SOOTING OF THE COMBUSTION CHAMBER, BURNERS AND FLUE TUBES AND CREATES A RISK OF ASPHYXIATION. Where an exhaust fan is supplied in the same room with a heater, sufficient openings for air must be provided in the walls. UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN INTO THE ROOM THROUGH THE CHIMNEY, CAUSING POOR COMBUSTION. SOOTING MAY RESULT IN SERIOUS DAMAGE TO THE HEATER AND RISK OF FIRE OR EXPLOSION. DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATING AIR. ADEQUATE AIR FOR COMBUSTION AND VENTILATION MUST BE PROVIDED FOR SAFE OPERATION. UNCONFINED SPACE In buildings of conventional frame, brick, or stone construction, unconfined spaces may provide adequate air for combustion, ventilation and draft hood dilution. If the unconfined space is within a building of tight construction (buildings using the following construction: weather stripping, heavy insulation, caulking, vapor barrier, etc.), air for combustion, ventilation and draft hood dilution must be obtained from outdoors. The installation instructions for confined spaces in tightly constructed buildings must be followed to ensure adequate air supply. CONFINED SPACE When drawing combustion and dilution air from inside a conventionally constructed building to a confined space, such a space shall be provided with two permanent openings, ONE IN OR WITHIN 12 INCHES (30.5cm) OF THE ENCLOSURE TOP AND ONE IN OR WITHIN 12 INCHES (30.5cm) OF THE ENCLOSURE BOTTOM. Each opening shall have a free area of at least one square inch per 1000 Btuh (2,225mm 2/Kw) of the total input of all appliances in the enclosure, but not less than 100 square inches (645 square cm). If the confined space is within a building of tight construction, air for combustion, ventilation, and draft hood dilution must be obtained from outdoors. When directly communicating with the outdoors or communicating with the outdoors through vertical ducts, two permanent openings, located in the above manner, shall be provided. Each opening shall have a free area of not less than one square inch per 4000 Btuh (8,900mm 2/Kw) of the total input of all appliances in the enclosure. If horizontal ducts are used, each opening shall have a free area of not less than one square inch per 2000 Btuh (4,450mm 2/Kw) of the total input of all appliances in the enclosure. For Canadian installations consult CAN/CSA-B149.1.
6 CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACK-FLOW PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE, PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED. FIGURE 3. CIRCULATING RETURN LINE CONNECTIONS TEMPERED WATER LOOP, IF USED, CONNECT TO POINT "A". STORED TEMPERATURE WATER LOOP, IF USED, CONNECT TO COLD WATER INLETWARNING TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES. SEE TEMPERATURE REGULATION ON PAGE 11. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES. SINGLE TEMPERATURE VENTING WARNING THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION. This water heater must be protected from freezing downdrafts. Remove all soot or other obstructions from the chimney that will retard a free draft. Type B venting is recommended with these water heaters. This water heater must be vented in compliance with all local codes, the current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, and with the Category I Venting Tables. In Canada, venting shall conform to the requirements of the current edition of the CAN/CSA B149.1-00 installation code. If any part of the vent system are exposed to ambient temperatures below\ 35 degrees F (2 degrees C) it must be insulated to prevent condensation. • Do not connect the heater to a common vent or chimney with solid fuel burning equipment. This practice is prohibited by many local building codes as is the practice of venting gas fired equipment to the duct work of ventilation systems. • Where a separate vent connection is not available and the vent pipe from the heater must be connected to a common vent with an oil burning furnace, the vent pipe should enter the smaller common vent or chimney at a point above the large vent pipe. FIGURE 2. VENT CONNECTION Vent connections must be made to an adequate stack or chimney. Size and install proper size vent pipe. Do not reduce pipe size to less than that of the blower outlet. Horizontal runs of vent pipe must have a minimum upward slope toward the chimney of 1/4 inch per foot (2cm per meter). Dampers or other obstructions must not be installed in between the heater and the blower. Be sure that the vent pipe does not extend beyond the inside wall of the chimney. Where a continuous or intermittent back draft is found to exist, the cause must be determined and corrected. A special vent cap may be required. If the back draft cannot be corrected by the normal methods or if a suitable draft cannot be obtained, a blower type flue gas exhauster must be employed to assure proper venting and correct combustion. MIXING VALVE APPLICATION FOR TWO TEMPERATURE WATER VACUUM RELIEF VA LV E *INSTALL PER LOCAL CODES.
7 THERMOMETERS (Not Supplied) Thermometers should be obtained and field installed as shown in Figure 3. Thermometers are installed in the system as a means of detecting the temperature of the outlet water supply. COMBINATION WATER (POTABLE) HEATING AND SPACE HEATING 1. All piping components connected to this unit for space heating applications shall be suitable for use with potable water. 2. Toxic chemicals, such as those used for boiler treatment, shall NEVER be introduced into this system. 3. This unit may NEVER be connected to any existing heating system or component(s) previously used with a non-potable water heating appliance. 4. When the system requires water for space heating at temperatures higher than required for domestic water purposes, a tempering valve must be installed. Please refer to installation diagram on page 6 of this manual for suggested piping arrangements. 5. These water heaters cannot be used in space heating applications o n l y. CAUTION A closed system will exist if a check valve (without bypass), pressure reducing valve (without bypass), or a water meter (without bypass) is installed in the cold water line between the water heater and street main (or well). Excessive pressure may develop in such closed systems, causing premature tank failure or intermittent relief valve operation. This is not a warranty failure. An expansion tank or a similar device may be required in the inlet supply line between the appliance and the meter or valve to compensate for the thermal expansion of the water. SYSTEM CONNECTIONS The system installation must conform to these instructions and to the local code authority having jurisdiction. Good practice requires that all heavy piping be supported. RELIEF VALVE This water heater is equipped with a combination temperature-pressure relief valve that complies with the standard for relief valves for hot w\ ater supply systems Z21.22-CSA 4.4. FOR SAFE OPERATION OF THE WATER HEATER, THE RELIEF VALVE(S) MUST NOT BE REMOVED OR PLUGGED. ASME ratings cover pressure relief capacities. ANSI ratings cover release rate with temperature actuation. In addition to the appliance relief valve, each remote storage tank which may be used in conjunction with this appliance shall also be installed with a properly sized, rated and approved combination temperature (ANSI) and pressure (ASME) relief valve(s). This valve\ shall comply with the standard for relief valves for hot water supply systems Z21.22-CSA 4.4. WARNING THE PURPOSE OF RELIEF VALVE IS TO AVOID EXCESSIVE PRESSURE OR TEMPERATURE INTO THE STEAM RANGE, WHICH MAY CAUSE SCALDING AT FIXTURES, TANK EXPLOSION, SYSTEM OR HEATER DAMAGE. NO VALVE IS TO BE PLACED BETWEEN THE RELIEF VALVE AND TANK. Your local code authority may have other specific relief valve requirements. A DRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO DIRECT DISCHARGE TO A SAFE LOCATION TO AVOID SCALDING OR WATER DAMAGE. THIS LINE MUST NOT BE REDUCED FROM THE SIZE OF THE VALVE OUTLET AND MUST NOT CONTAIN VALVES, RESTRICTIONS NOR SHOULD IT BE LOCATED IN FREEZING AREAS. DO NOT THREAD OR CAP THE END OF THIS LINE. RESTRICTED OR BLOCKED DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE AND IS UNSAFE. DISCHARGE LINE SHALL BE INSTALLED TO ALLOW COMPLETE DRAINAGE OF BOTH THE VALVE AND LINE. See SERVICE INFORMATION section for procedure and precautions. The type, size and location of the relief valves must be in accordance with local codes. The location of the relief valve is shown in Figure 1. The heater has a factory installed high temperature limit switch. GAS PIPING Contact your local gas service company to ensure that adequate gas service is available and to review applicable installation codes for your area. Size the main gas line in accordance with Table 4. The figures shown are for straight lengths of pipe at 0.5 in. W.C. pressure drop, which is considered normal for low pressure systems. Note: Fittings such as elbows, tees and line regulators will add to the pipe pressure drop. Also refer to the current edition of the National Fuel Gas Code. For Canadian installations consult Canadian Installation Code CAN/CSA-B149.1. WARNING The minimum gas supply pressure for input adjustment is 6.0" kPa W.C. for natural gas (11.0" kPa W.C. for propane). THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER THAN 14" kPa WATER COLUMN SUPPLY PRESSURE. EXPOSURE TO HIGHER GAS SUPPLY PRESSURE MAY CAUSE DAMAGE TO THE CONTROL WHICH COULD RESULT IN FIRE OF EXPLOSION. If overpressure has occurred such as through improper testing of gas lines or emergency malfunction of the supply system, the control must be checked for safe operation. Make sure that the outside vents on the supply regulators and the safety vent valves are protected against blockage. These are parts of the gas supply system not the heater. Vent blockage may occur during ice storms. IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM CONTAMINANTS IN THE GAS WAYS. SUCH FOULING MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION. IF COPPER SUPPLY LINES ARE USED THEY MUST BE INTERNALLY TINNED AND CERTIFIED FOR GAS SERVICE. BEFORE ATTACHING THE GAS LINE, BE SURE THAT ALL GAS PIPE IS CLEAN ON THE INSIDE. TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED SEDIMENT TRAP OR DRIP LEG) MUST BE INCORPORATED IN THE PIPING (SEE FIG. 5). THE DIRT LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING CONDITIONS. INSTALL IN ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS. REFER TO THE CURRENT EDITION OF THE NATIONAL FUEL GAS CODE. For Canadian installations consult Canadian Installation Code CAN/ CSA-B149.1. To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to gas valve inlet. Apply joint compounds (pipe dope) sparingly and only to the male threa\ ds of pipe joints. Do not apply compounds to the first two threads. Use compounds resistant to the action of liquefied petroleum gases.
8 FIGURE 4. WIRING DIAGRAM AND SCHEMATIC HEATER WIRING All electrical work must be installed in the United States in accordance with the current edition of the National Electrical Code ANSI/NFPA No. 70, in Canada, with the current edition of Canadian Electrical Code CSA C22.1, must conform to all local code authority having jurisdiction. AN ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION. If any of the original wire as supplied with the appliance must be replaced, use only type 105°C thermoplastic or equivalent, 250°C type F must be used for the flame sensor leads and the spark ignition cable must be high voltage 250°C. CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER SERVICING.
9 TABLE 4. GAS SUPPLY LINE SIZES (IN INCHES)* MAXIMUM CAPACITY OF PIPE IN CUBIC FEET PER HOUR BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR GAS LEAKAGE. Use soap and water solution or other material acceptable for the purpose in locating the leaks. DO NOT USE MATCHES, CANDLES, FLAME OR OTHER SOURCES OF IGNITION FOR THIS PURPOSE. FIGURE 5. GAS PIPING AND SEDIMENT TRAP INSTALLATION DISCONNECT THE HEATER AND ITS MANUAL GAS SHUTOFF VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY SUPPLY PRESSURE TESTING EXCEEDING 1/2 PSIG (3.45 kPa). GAS SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED FROM THE HEATER FOR TEST PRESSURES OF 1/2 PSIG (3.45 kPa) OR LESS. THE APPLIANCE NEED NOT BE DISCONNECTED, BUT MUST BE ISOLATED FROM THE SUPPLY PRESSURE TEST BY CLOSING THE MANUAL GAS SHUTOFF VALVE. PURGING Gas line purging is required with new piping or systems in which air has entered. CAUTIONPURGING SHOULD BE PERFORMED BY PERSONS EXPERIENCED IN THIS TYPE GAS SERVICE. TO AVOID RISK OF FIRE OR EXPLOSION, PURGE DISCHARGE MUST NOT ENTER CONFINED AREAS OR SPACES WHERE IGNITION CAN OCCUR. THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION MUST BE INACTIVATED OR REMOVED. GAS METER SIZE — NATURAL GASES ONLY Be sure the gas meter has sufficient capacity to supply the full rated gas input of the water heater as well as the requirements of all other gas fired equipment supplied by the meter. If gas meter is too small, ask the gas company to install a larger meter having adequate capacity. GAS PRESSURE REGULATOR The gas pressure regulator is built into the gas valve and is equipped to operate on the gas specified on model and rating plate. The regulator is factory adjusted to deliver gas to burner at correct water column pressure allowing for a nominal pressure drop through the controls. The minimum gas supply pressure for input adjustment must not be less than 6" w.c. (1.49 kPa) for natural gas and 11" w.c. (2.73 kPa). Do not subject the combination gas valve to inlet gas pressures of more than 14.0" w.c. (3.48 kPa) - natural gas. A service regulator is necessary if higher gas pressures are encountered. Gas pressure specified in Table 5, refer to flow pressure taken at pressure tap of automatic gas valve while heater is operating. TABLE 5. Type ofGas InputManifold Pressure Natural 75,100 Btu/hr 22 KW/hr 4.0 in. W.C. 1.12 kPa OPERATION It is recommended that a qualified person perform the initial firing of the heater. At this time the user should not hesitate to ask the individual any questions which he may have in regard to the operation and maintenance of the unit. TO OPERATE THE HEATER 1. Close the heater drain valve (Figure 1) by turning handle clockwise . 2. Open a nearby hot water faucet to permit the air in the system to escape. 3. Fully open the cold water inlet pipe valve (Figure 1) allowing the heater and piping to be filled. 4. Close the hot water faucet as water starts to flow. 5. The heater is ready to be operated. WARNING DO NOT ATTEMPT TO OPERATE WATER HEATER WITH COLD WATER INLET VALVE CLOSED. NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN IT IS FILLED WITH WATER AND A TEMPERATURE AND PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF THE HEATER. LENGTH IN FEET NORMAL IRON PIPE SIZES (INCHES) INPUT IN THOUSANDS BTU/HR 1/2" 3/4" 1"1 1/4" 1 1/2" 2"2 1/2" 3"4" 10 175360680 1400 21003960630011000 230000 20 120250485 950 146027504360 7700 15800 30 97200 375 770 118022003520 6250 12800 40 82170 320 660 9901900 3000 5300 10900 50 73151 285 580 9001680 2650 4750 9700 60 66138 260 530 8101520 2400 4300 8800 70 61125 240 490 7501400 2250 3900 8100 80 5711 8 220 460 6901300 2050 3700 7500 90 5311 0 205 430 6501220 1950 3450 7200 100 50103 195 400 6201150 1850 3250 6700 125 4493175 360 5501020 1650 2950 6000 150 4084160 325 5009501500 2650 5500 175 3777145 300 4608501370 2450 5000 200 3572135 280 4308001280 2280 4600 LENGTH IN METERS NORMAL IRON PIPE SIZES (INCHES) INPUT IN KW 1/2" 3/4" 1"1 1/4" 1 1/2" 2"2 1/2" 3"4" 3.0 51105199410 615 11601845 32216735 6.1 3573142278 428 8051277 22554626 9.1 285911 0225 346 6441031 18303748 12.2 245094193 290 556878 15523192 15.2 214483170 264 492776 13912840 18.3 194076155 237 445703 12592577 21.3 183770143 220 410659 11422372 24.4 173564165 202 381600 10832196 27.4 163260126 190 357571 10102108 30.5 15305711 7 182 337542 9521962 38.1 132751105 161 299483 8641757 45.7 12254795 146 278439 7761610 53.3 11234288 135 249401 7171464 61.0 10214082 126 234375 6881347
105. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow "B" in the safety information above on this label. If you don't smell gas, go to next step. 6. Turn on all electrical power to the appliance. 7. Set thermostat to desired setting by first pressing the COOLER and HOTTER buttons together and holding for 1 second. Then press the HOTTER button. 8. If the appliance will not operate, follow the instructions "TO TURN OFF GAS TO APPLIANCE" and call your technician or gas supplier. 9. WATER TEMPERATURE ADJUSTMENT is approximately 120°F (49°C). FOR YOUR SAFETY READ BEFORE OPERATING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. • If you cannot reach your gas supplier, call the fire department. C. Use only your hand to push in the control buttons. Never use tools. If the control buttons will not push in, don’t try to repair them, call a qualified service technician. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water. OPERATING INSTRUCTIONS A. Set thermostat to the lowest setting. B. Turn off all the electric power to the appliance if service is to be performed. TO TURN OFF GAS TO APPLIANCE BEFORE OPERATING: ENTIRE SYSTEM MUST BE FILLED WITH WATER AND AIR PURGED FROM ALL LINES. 1. STOP! Read the safety information above on this label. 2. Set the thermostat to the lowest setting by first pressing the COOLER and HOTTER buttons together and holding for 1 second. Then press the COOLER button until the WARM indicator light appears. 3. Turn the "ON/OFF" swich on the blower control to the "OFF" position. 4. This appliance is equipped with a device which automatically lights the burner. DO NOT TRY TO LIGHT THE BURNER BY HAND. A. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand. B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS: • Do not try to light any appliance. • Do not touch any electric switch; do not use any phone in your building. • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. CAUTION: Hotter water increases the risk of scald injury. Consult the instruction manual before changing temperatures. WARNING: TURN OFF ALL ELECTRIC POWER BEFORE SERVICING