Home > American Water Heater > Gas Heater > American Water Heater 74 Gallon 80 Thermal Efficiency UltraLow NOx Heavy Duty Commercial Gas Water Heater User Manual

American Water Heater 74 Gallon 80 Thermal Efficiency UltraLow NOx Heavy Duty Commercial Gas Water Heater User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual American Water Heater 74 Gallon 80 Thermal Efficiency UltraLow NOx Heavy Duty Commercial Gas Water Heater User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							1
    PRINTED IN U.S.A. 1212 PART NO. 325370-000
    MODELS BBCN375T754NV 
    PLACE THESE INSTRUCTIONS ADJACENT TO HEATER
    AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.
    COMMERCIAL ULTRA LOW NOx GAS WATER HEATER
    Glass-Lined Tank-type Water Heater 
    •  INSTALLATION   •   OPERATION   •   SERVICE   •   MAINTENANCE  •  LIMITED WARRANTY
      CAUTION
    TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION 
    RELATIVE TO YOUR SAFETY.  PLEASE READ THOROUGHLY 
    BEFORE  INSTALLING AND  USING THIS APPLIANCE.
    Series 100
    www .americanwaterheate r.co m
    American Wa ter Heater
    Johnson Cit y, TN 37605 
    						
    							2
    FOREWORD
    The design of model BBCN375T754NV complies with the current edition 
    of ANSI Z21.10.3/CSA 4.3 as automatic storage or automatic circulating 
    tank type water heaters.
    Installation diagrams are found in this manual.  These diagrams will serve 
    to provide the installer with a reference for the materials and method of 
    piping necessary.  It is highly essential that all water and gas piping be 
    installed as shown on the diagrams.
    In addition to these instructions, the equipment shall be installed in 
    accordance with those installation regulations in force in the local area 
    where the installation is to be made.  These shall be carefully followed 
    in all cases.  Authorities having jurisdiction should be consulted before 
    installations are made.
    ROUGH-IN DIMENSIONS
    FIGURE 1.
    The installation must conform to these instructions and the local code 
    authority having jurisdiction.  
    In the absence of local codes, the installation must comply with the following:
    In the United States:Current edition of the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 
    and the National Electrical Code, NFPA 70;
    In Canada:Current edition of the Installation Code CAN/CSA-B149.1 and the 
    Canadian Electrical Code CSA C22.1.
    These are available from Canadian Standards Association, 8501 East 
    Pleasant Valley Road, Cleveland, OH 44131 or National Fire Protection 
    Association, 1 Batterymarch Park, Quincy, MA 02269.
    *INSTALL IN ACCORDANCE WITH LOCAL CODES
    TOP VIEW
    TABLE 3, GAS AND ELECTRICAL CHARACTERISTICS
    All Models: Maximum supply pressure = 14.0 in. W.C. (3.48 kPa)
      Minimum supply pressure, Natural gas = 6 in. W.C. (1.49 kPa). 
      Minimum pressures must be maintained under both load and no load (stati\
    c and dynamic) conditions.
    Recovery ratings are based on 80% thermal efficiency. 
    TABLE 1, DIMENSIONS
    Units
    AB CDEFGHJK L M
    Inches CM 66 5/8
    169.22 58 3/4
    134.23 30 15/16
    78.58 27 3/4
    70.5 15 1/4
    38.6 4
    10.2 15 3/4
    40.0 16
    40.6 1 1/4
    3.2 1 1/4
    NPT 1/2
    NPT 12 1/4
    31.1
    TABLE 2, RECOVERY RATINGS
    Manifold Pressure Electrical Characteristics
    Type of gas Inches W.C.kPaVoltz/Hz Amperes
    Natural Gas 4.01.12 120/160 
    						
    							3
    GENERAL SAFETY INFORMATION
    PRECAUTIONS
    DO NOT USE THIS WATER HEATER IF ANY PART HAS BEEN UNDER 
    WATER.  Immediately  call  a  qualified  service  technician  to  inspect  the 
    appliance and to replace any part of the control system and any gas 
    control which has been under water.
    IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO NOT OPERATE 
    HEATER UNTIL ALL CORRECTIVE STEPS HAVE BEEN MADE BY A 
    QUALIFIED SERVICEMAN.
    1.  EXTERNAL FIRE.
    2. DAMAGE.
    3.  FIRING WITHOUT WATER.
    4. SOOTING.
    Heater must be protected from freezing downdrafts during shutdown periods.
    GROUNDING INSTRUCTIONS
    This water heater must be grounded in accordance with the National 
    Electrical Code and/or local codes. These must be followed in all cases.
    This water heater must be connected to a grounded metal, permanent 
    wiring system; or an equipment grounding conductor must be run with 
    the circuit conductors and connected to the equipment grounding terminal 
    or lead on the water heater, see Figure 5.
    TABLE OF CONTENTS
                                                                            \
                                             Page
    ROUGH-IN DIMENSIONS .............................................................  2
    FOREWORD  ........................................................................\
    .........  2
    GENERAL SAFETY INFORMATION .............................................  2-4 
    Precautions ........................................................................\
    ............  3
      Grounding Instructions ...............................................................  3
      Chemical Vapor Corrosion  .........................................................  3
      Extended Non-use Periods  ........................................................  3
      Insulation Blankets .....................................................................  4
      High Altitude  Installations ...........................................................  4
      Circulating Pump  .......................................................................  4
    INSTALLATION INSTRUCTIONS  ................................................. 4-9 
    Required Ability ........................................................................\
    ......  4
      Locating The Heater ..................................................................  4
     Clearances ........................................................................\
    .........  5
      Hard Water ........................................................................\
    ........  5
      Air Requirements  .......................................................................  5 
     Venting  ........................................................................\
    ...............  6
      Thermometers (Not Supplied)  ...................................................  7
      Combination Water (Potable) Heating and Space Heating  ....... 7
      Relief Valve ........................................................................\
    ........  7
      Gas Piping  ........................................................................\
    .........  7
      Heater Wiring  ........................................................................\
    .....  8
      Wiring Diagram  ........................................................................\
    ..  8 
     Purging  ........................................................................\
    ..............  9
      Gas Pressure Regulation ..........................................................  9
    OPERATION ........................................................................\
    .........  9 
    To Operate The Heater .............................................................  9
      Lighting Instructions  ..................................................................  10
      Temperature Regulation  ...........................................................  11
      Checking Venting  ......................................................................  11
      High Temperature Limit Switch  .................................................  11
    SERVICE INFORMATION ............................................................  12-13
      Main Burner and Igniter  ............................................................  12
      Checking Gas Input  ..................................................................  12
      Vent System ........................................................................\
    ......  12
      Blower Maintenance  .................................................................  13
      Relief Valve ........................................................................\
    .......  13
      Hot Water Odor  ........................................................................\
    .  13
      Winter Protection  ......................................................................  13
      Replacement Parts  ...................................................................  13
    PREVENTIVE MAINTENANCE  ....................................................  13-14
      Procedure for Periodic Removal Of Lime Deposits  .................. 13
      Deliming Solvents  .....................................................................  13
      Tank Cleanout Procedure  .........................................................  14
    CHECKLIST  ........................................................................\
    .........  15-16
     Condensation ........................................................................\
    ....  15
     Anode  ........................................................................\
    ...............  15
      Service & Repair  .......................................................................  16
    TROUBLESHOOTING .................................................................  17-20
    NOTES ........................................................................\
    .................  21-22
    LIMITED WARRANTY  ...................................................................  23
    CHEMICAL VAPOR CORROSION
     WARNINGCORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF 
    AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS.  SUCH  
    CORROSION MAY RESULT IN FAILURE AND RISK OF ASPHYXIATION.
    Spray can propellants, cleaning solvents, refrigerator and air condition\
    ing 
    refrigerants, swimming pool chemicals, calcium and sodium chloride (wat\
    er 
    softener salt), waxes, and process chemicals are typical compounds whic\
    h 
    are potentially corrosive.  Do not store products of this sort near the heater.  
    Also, air which is brought in contact with the heater should not contain\
     
    any of these chemicals.  If necessary, uncontaminated air should be 
    obtained from remote or outside sources.  The limited warranty is voided 
    when failure of water heater is due to a corrosive atmosphere.  (Refer to 
    the limited warranty for complete terms and conditions.)
    EXTENDED NON-USE PERIODS
     WARNINGHYDROGEN GAS CAN BE PRODUCED IN A HOT WATER SYSTEM 
    SERVED BY THIS HEATER THAT HAS NOT BEEN USED FOR A LONG 
    PERIOD OF TIME (GENERALLY TWO WEEKS OR MORE). HYDROGEN 
    GAS IS EXTREMELY FLAMMABLE. To reduce the risk of injury under 
    these conditions, it is recommended that the hot water faucet be opened 
    for several minutes at the kitchen sink before using any electrical appliance 
    connected to the hot water system. If hydrogen is present, there will 
    probably be an unusual sound such as air escaping through the pipe as 
    the water begins to flow. THERE SHOULD BE NO SMOKING OR OPEN 
    FLAME NEAR THE FAUCET AT THE TIME IT IS OPEN.
     Page 
    						
    							4
    INSULATION BLANKETS
    Insulation blankets available to the general public for external use 
    on gas water heaters are not required for use on your water heater. 
    The purpose of an insulation blanket is to reduce the standby heat 
    loss encountered with storage tank water heaters. Your  water 
    heater meets or exceeds the current edition of ASHR AE/IES 90.1 
    standards with respect to insulation and standby loss requirement 
    making an insulation blanket unnecessary.
      WARNING
    Should you choose to apply an insulation blanket to this heater, you 
    should follow these instructions.  Failure to follow these instructions 
    can result in fire, asphyxiation , serious personal injury or death.
    • Do not apply insulation to the top of the water heater, as this will 
    interfere with safe operation.
    •  Do not cover the outer door, thermostat or temperature & pressure 
    relief valve.
    •  Do not allow insulation to come within 2" (5cm) of the floor to prevent 
    blockage of combustion air flow to the burner.
    •  Do not  cover the instruction manual.  Keep it on the side of the water 
    heater or nearby for future reference.
    •  Do obtain new warning and instruction labels from the manufacturer 
    for placement on the blanket directly over the existing labels.
    •  Do inspect the insulation blanket frequently to make certain it does 
    not sag, thereby obstructing combustion air flow.
    HIGH ALTITUDE INSTALLATIONS
    Water heaters covered in this manual have been tested and 
    approved for installation at elevations up to 7,700 feet (2,347 
    m) above sea level. For installation above 7,700 feet (2,347 m), 
    the water heater’s Btu input should be reduced at the rate of 4 
    percent for each 1,000 feet (305 m) above sea level which requires 
    replacement of the burner orifice in accordance with the National 
    Fuel Gas Code ANSI Z223.1/ NFPA 54. Contact your local gas 
    supplier for further information.
    Failure to replace the standard orifice with the proper high altitude 
    orifice when installed at elevations above 7,700 feet (2,347 m) 
    could result in improper and inefficient operation of the water 
    heater, producing carbon monoxide gas in excess of the safe 
    limits. This could result in serious injury or death. Contact your 
    local gas supplier for any specific changes that may be required 
    in your area. 
    Upon completion of derating of the heater, adjustment to the 
    gas pressure regulator may be required.  See CHECKING THE 
    INPUT section in this manual for inlet and manifold pressure 
    requirements.
    Also due to the input rating reduction required at high altitudes, 
    the output rating of the appliance is also reduced and should be 
    compensated for in the sizing of the equipment for application.
    CIRCULATING PUMP
    A circulating pump is used when a system requires a circulating 
    loop or there is a storage tank used in conjunction with the heater.  
    Refer to the piping diagrams at rear of manual for electrical hookup 
    information and install in accordance with the current edition of the 
    National Electrical Code ANSI/NFPA No. 70. In Canada refer to 
    Canadian Electrical Code CSA C22.1.
    Only all bronze circulating pumps are used with commercial 
    water heaters. Although circulators are oiled and operated by 
    the manufacturer some circulators must be oiled again before 
    operating.  Please refer to manufacturer’s instructions. 
    INSTALLATION INSTRUCTIONS
    REQUIRED ABILITY
    INSTALLATION OR SERVICE OF THIS WATER HEATER 
    REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED 
    TR ADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR 
    SUPPLY, VENTING, ELECTRICAL AND GAS SUPPLY WORK 
    ARE REQUIRED.
    L O C AT I N G  T H E  H E AT E R
      WARNING
    THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH 
    AS GAS WATER HEATERS IN ROOMS, GAR AGES OR OTHER 
    AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR 
    ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED, 
    OPER ATED OR REPAIRED.  FLAMMABLE VAPORS ARE HEAV Y 
    AND TR AVEL ALONG THE FLOOR AND MAY BE IGNITED BY THE 
    HEATER’S PILOT OR MAIN BURNER FLAMES CAUSING FIRE 
    OR EXPLOSION.  SOME LOCAL CODES PERMIT OPER ATION 
    OF GAS APPLIANCES IF INSTALLED 18 INCHES (45.7 CM) OR 
    MORE ABOVE THE FLOOR. THIS MAY REDUCE THE RISK IF 
    LOCATION IN SUCH AN AREA CANNOT BE AVOIDED.
    DO NOT INSTALL THIS WATER HEATER DIRECTLY ON A CARPETED 
    FLOOR.  A FIRE HAZARD MAY RESULT.  Instead the water heater must 
    be placed on a metal or wood panel extending beyond the full width 
    and depth by at least 3 inches (7.6 CM) in any direction.  If the heater is  
    						
    							5
    installed in a carpeted alcove or closet, the entire floor shall be covered 
    by the panel.  Also, see the drain requirements.
    THIS HEATER SHALL BE LOCATED OR PROTECTED SO IT IS 
    NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE.
      WARNING
    FLAMMABLE ITEMS
    , PRESSURIZED CONTAINERS OR ANY 
    OTHER POTENTIAL FIRE HA ZARDOUS ARTICLES MUST 
    NEVER BE PLACED ON OR ADJACENT TO THE HEATER.  OPEN 
    CONTAINERS OF FLAMMABLE MATERIAL SHOULD NOT BE 
    STORED OR USED IN THE SAME ROOM WITH THE HEATER.
    When installing the heater, consideration must be given to proper 
    location.  Location selected should be as close to the stack or 
    chimney as practicable, with adequate air supply and as centralized 
    with the piping system as possible.
    THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE IT 
    WILL BE SUBJECT TO FREEZING.
    THE HEATER SHOULD BE LOCATED IN AN AREA WHERE 
    LEAK AGE FROM THE HEATER OR CONNECTIONS WILL NOT 
    RESULT IN DAMAGE TO THE ADJACENT AREA OR TO LOWER 
    FLOORS OF THE STRUCTURE.
    WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE 
    DR AIN PAN SHOULD BE INSTALLED UNDER THE HEATER.  Such 
    pans should be fabricated with sides at least 2" (5cm) deep, with 
    length and width at least 2" (5cm) greater than the diameter of the 
    heater and must be piped to an adequate drain.  The pan must not 
    restrict combustion air flow.
    Drain pans suitable for these heaters are available from from the 
    manufacturer, authorized service agencies or distributors. 
    CLEARANCES
    These heaters are approved  for installation on combustible flooring 
    in a closet having a ceiling 12" (30.5cm) above top cover and with 
    clearances to combustible construction of 6" (15.2cm) from flue or 
    vent connector, 0" (0cm) at the sides and rear and 5" (10.2cm) to 
    front to prevent a possible fire hazard condition.  A minimum of 4" 
    (10.2cm) shall be allowed for installation of serviceable parts.
    HARD WATER
    Where hard water conditions exist, water softening or the threshold   
    type of water treatment is recommended. This will protect   
    the dishwashers, coffee urns, water heaters, water piping and   
    other equipment.
    See MAINTENANCE section for details of tank cleanout procedure.
    AIR REQUIREMENTS
    REFER TO CURRENT EDITION OF THE "NATIONAL FUEL GAS 
    CODE ANSI Z223.1/NFPA 54. FOR CANADA CONSULT CAN/
    C SA - B149.1.
    KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE 
    MATERIALS, GASOLINE AND OTHER FLAMMABLES, VAPORS 
    AND LIQUIDS.
    DO NOT OBSTRUCT THE FLOW OF THE COMBUSTION OR 
    VENTILATING AIR.
     WARNINGATTIC AND/OR EXHAUST FANS OPERATING ON THE PREMISES 
    WITH A WATER HEATER CAN RESULT IN CARBON MONOXIDE 
    POISONING AND  DEATH.
    OPERATION OF THESE FANS CAN PRODUCE A NEGATIVE DRAFT IN 
    THE AREA OF THE WATER HEATER PREVENTING THE PRODUCTS 
    OF COMBUSTION FROM EXHAUSTING THROUGH THE CHIMNEY 
    OR VENT PIPE.
    The venting of the water heater should be inspected by a qualified service 
    technician at the time of installation and periodically thereafter to ensure 
    a down-draft condition does not exist.
     WARNING
    FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR COMBUSTION 
    AND VENTILATION. AN INSUFFICIENT SUPPLY OF AIR WILL CAUSE 
    RECIRCULATION OF COMBUSTION PRODUCTS RESULTING IN 
    AIR CONTAMINATION THAT MAY BE HAZARDOUS TO LIFE. SUCH 
    A CONDITION OFTEN WILL RESULT IN A YELLOW, LUMINOUS 
    BURNER FLAME, CAUSING CARBONING OR SOOTING OF THE 
    COMBUSTION CHAMBER, BURNERS AND FLUE TUBES AND 
    CREATES A  RISK  OF ASPHYXIATION.
    Where an exhaust fan is supplied in the same room with a heater, 
    sufficient openings for air must be provided in the walls.   UNDERSIZED 
    OPENINGS WILL CAUSE AIR TO BE DRAWN INTO THE ROOM 
    THROUGH THE CHIMNEY, CAUSING POOR COMBUSTION. 
    SOOTING MAY RESULT IN SERIOUS DAMAGE TO THE HEATER 
    AND RISK OF FIRE OR EXPLOSION.
    DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATING 
    AIR.  ADEQUATE AIR FOR COMBUSTION AND VENTILATION MUST 
    BE PROVIDED FOR SAFE OPERATION.
    UNCONFINED SPACE
    In buildings of conventional frame, brick, or stone construction, 
    unconfined spaces may provide adequate air for combustion, ventilation 
    and draft hood dilution.
    If the unconfined space is within a building of tight construction (buildings  
    using the following construction: weather stripping, heavy insulation, 
    caulking, vapor barrier, etc.), air for combustion, ventilation and draft hood 
    dilution must be obtained from outdoors.  The installation instructions 
    for confined spaces in tightly constructed buildings must be followed to 
    ensure adequate air supply.
    CONFINED SPACE
    When drawing combustion and dilution air from inside a conventionally 
    constructed building to a confined space, such a space shall be provided 
    with two permanent openings, ONE IN OR WITHIN 12 INCHES (30.5cm) 
    OF THE ENCLOSURE TOP AND ONE IN OR WITHIN 12 INCHES 
    (30.5cm) OF THE ENCLOSURE BOTTOM.  Each opening shall have 
    a free area of at least one square inch per 1000 Btuh (2,225mm
    2/Kw) of 
    the total input of all appliances in the enclosure, but not less than 100 
    square inches (645 square cm).
    If  the  confined  space  is  within  a  building  of  tight  construction,  air  for 
    combustion, ventilation, and draft hood dilution must be obtained 
    from outdoors.  When directly communicating with the outdoors or 
    communicating with the outdoors through vertical ducts, two permanent 
    openings, located in the above manner, shall be provided.  Each opening 
    shall have a free area of not less than one square inch per 4000 Btuh 
    (8,900mm
    2/Kw) of the total input of all appliances in the enclosure.  If 
    horizontal ducts are used, each opening shall have a free area of not 
    less than one square inch per 2000 Btuh (4,450mm
    2/Kw) of the total input 
    of all appliances in the enclosure.  For Canadian installations consult 
    CAN/CSA-B149.1.  
    						
    							6
    CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACK-FLOW
    PREVENTER, CHECK VALVE OR WATER METER WITH CHECK 
    VALVE, PROVISIONS FOR THERMAL EXPANSION OF WATER IN 
    THE HOT WATER SYSTEM MUST BE PROVIDED.
    FIGURE 3.
    CIRCULATING RETURN LINE CONNECTIONS
    TEMPERED WATER LOOP, IF USED, CONNECT TO POINT "A".  
    STORED TEMPERATURE WATER LOOP, IF USED, CONNECT TO 
    COLD WATER INLETWARNING
    TEMPERATURE SETTING SHOULD NOT EXCEED SAFE 
    USE TEMPERATURE AT FIXTURES.  SEE TEMPERATURE 
    REGULATION ON PAGE 11.  IF HIGHER PREHEAT 
    TEMPERATURES ARE NECESSARY TO OBTAIN 
    ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD 
    VALVE FOR HOT WATER SUPPLIED TO FIXTURES.
    SINGLE TEMPERATURE
    VENTING
     WARNING
    THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE 
    FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION 
    OF FLUE GASES.  SUCH CONDITIONS CAUSE SOOTING OR RISKS 
    OF  FIRE AND ASPHYXIATION.
    This water heater must be protected from freezing downdrafts.
    Remove all soot or other obstructions from the chimney that will retard 
    a free draft.
    Type B venting is recommended with these water heaters. 
    This water heater must be vented in compliance with all local codes, the 
    current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, 
    and with the Category I Venting Tables.
    In Canada, venting shall conform to the requirements of the current 
    edition of the CAN/CSA B149.1-00 installation code.
    If any part of the vent system are exposed to ambient temperatures below\
     
    35 degrees F (2 degrees C) it must be insulated to prevent condensation.
    • 
    Do not connect the heater to a common vent or chimney with solid 
    fuel burning equipment.  This practice is prohibited by many local  
    building codes as is the practice of venting gas fired equipment to 
    the duct work of ventilation systems.
    •  Where  a  separate  vent  connection  is  not  available  and  the  vent 
    pipe from the heater must be connected to a common vent with an 
    oil burning furnace, the vent pipe should enter the smaller common 
    vent or chimney at a point above the large vent pipe.
    FIGURE 2.
    VENT CONNECTION
    Vent connections must be made to an adequate stack or chimney. Size 
    and install proper size vent pipe.  Do not reduce pipe size to less than 
    that of the blower outlet.
    Horizontal runs of vent pipe must have a minimum upward slope toward 
    the chimney of 1/4 inch per foot (2cm per meter).  Dampers or other 
    obstructions must not be installed in between the heater and the blower.  
    Be sure that the vent pipe does not extend beyond the inside wall of 
    the chimney.
    Where a continuous or intermittent back draft is found to exist, the 
    cause must be determined and corrected.  A special vent cap may be 
    required.  If the back draft cannot be corrected by the normal methods or 
    if a suitable draft cannot be obtained, a blower type flue gas exhauster 
    must be employed to assure proper venting and correct combustion.
    MIXING VALVE APPLICATION FOR TWO TEMPERATURE WATER
    VACUUM RELIEF
           VA LV E
    *INSTALL PER 
    LOCAL CODES. 
    						
    							7
    THERMOMETERS (Not Supplied)
    Thermometers should be obtained and field installed as shown in 
    Figure 3.
    Thermometers are installed in the system as a means of detecting the 
    temperature of the outlet water supply.
    COMBINATION WATER (POTABLE) HEATING AND SPACE HEATING
    1. All piping components connected to this unit for space heating 
    applications shall be suitable for use with potable water.
    2.  Toxic chemicals, such as those used for boiler treatment, shall 
    NEVER be introduced into this system.
    3. This unit may NEVER be connected to any existing heating system 
    or component(s) previously used with a non-potable water heating 
    appliance.
    4.  When the system requires water for space heating at temperatures 
    higher than required for domestic water purposes, a tempering 
    valve must be installed.  Please refer to installation diagram on 
    page 6 of  this manual for suggested piping arrangements.
    5.  These water heaters cannot be used in space heating applications 
    o n l y.
     CAUTION
    A closed system will exist if a check valve (without bypass), pressure 
    reducing valve (without bypass), or a water meter (without bypass) 
    is installed in the cold water line between the water heater and street 
    main (or well).
    Excessive pressure may develop in such closed systems, causing 
    premature tank failure or intermittent relief valve operation.   This is not a 
    warranty failure.  An expansion tank or a similar device may be required 
    in the inlet supply line between the appliance and the meter or valve to 
    compensate for the thermal expansion of the water.
    SYSTEM CONNECTIONS
    The system installation must conform to these instructions and to the 
    local code authority having jurisdiction.  Good practice requires that all 
    heavy piping be supported.
    RELIEF VALVE
    This water heater is equipped with a combination temperature-pressure 
    relief valve that complies with the standard for relief valves for hot w\
    ater 
    supply systems Z21.22-CSA 4.4. FOR SAFE OPERATION OF THE 
    WATER HEATER, THE RELIEF VALVE(S) MUST NOT BE REMOVED 
    OR PLUGGED.
    ASME ratings cover pressure relief capacities. ANSI ratings cover release 
    rate with temperature actuation.
    In addition to the appliance relief valve, each remote storage tank 
    which may be used in conjunction with this appliance shall also be 
    installed with a properly sized, rated and approved combination 
    temperature (ANSI) and pressure (ASME) relief valve(s). This valve\
     
    shall comply with the standard for relief valves for hot water supply 
    systems Z21.22-CSA 4.4.
     WARNING
    THE PURPOSE OF RELIEF VALVE IS TO AVOID EXCESSIVE PRESSURE 
    OR TEMPERATURE INTO THE STEAM RANGE, WHICH MAY CAUSE 
    SCALDING  AT FIXTURES, TANK EXPLOSION, SYSTEM OR HEATER 
    DAMAGE.  NO  VALVE IS TO BE PLACED BETWEEN THE 
    RELIEF 
    VALVE AND TANK.
    Your local code authority may have other specific relief valve 
    requirements.
    A DRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO 
    DIRECT DISCHARGE TO A SAFE LOCATION TO AVOID SCALDING OR 
    WATER DAMAGE.  THIS LINE MUST NOT BE REDUCED FROM THE 
    SIZE OF THE VALVE OUTLET AND MUST NOT CONTAIN VALVES, 
    RESTRICTIONS NOR SHOULD IT BE LOCATED IN FREEZING AREAS.  
    DO NOT THREAD OR CAP THE END OF THIS LINE.  RESTRICTED OR 
    BLOCKED DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE 
    AND IS UNSAFE.  DISCHARGE LINE SHALL BE INSTALLED TO ALLOW 
    COMPLETE DRAINAGE OF BOTH THE VALVE AND LINE.
    See SERVICE INFORMATION section for procedure and precautions.
    The type, size and location of the relief valves must be in accordance 
    with local codes.  The location of the relief valve is shown in Figure 1.  
    The heater has a factory installed high temperature limit switch.
    GAS PIPING
    Contact your local gas service company to ensure that adequate gas service 
    is available and to review applicable installation codes for your area.
    Size the main gas line in accordance with Table 4. The figures shown 
    are for straight lengths of pipe at 0.5 in. W.C. pressure drop, which is 
    considered normal for low pressure systems.  Note:  Fittings such as 
    elbows, tees and line regulators will add to the pipe pressure drop.  Also 
    refer to the current edition of the National Fuel Gas Code. For Canadian 
    installations consult Canadian Installation Code CAN/CSA-B149.1.
     WARNING
    The minimum gas supply pressure for input adjustment is 6.0" kPa W.C. 
    for natural gas (11.0" kPa W.C. for propane).
    THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER THAN 
    14" kPa WATER COLUMN SUPPLY PRESSURE. EXPOSURE TO HIGHER 
    GAS SUPPLY PRESSURE MAY CAUSE DAMAGE TO THE CONTROL 
    WHICH COULD RESULT IN FIRE OF EXPLOSION. If overpressure has 
    occurred such as through improper testing of gas lines or emergency 
    malfunction of the supply system, the control must be checked for safe 
    operation. Make sure that the outside vents on the supply regulators 
    and the safety vent valves are protected against blockage. These are 
    parts of the gas supply system not the heater. Vent blockage may occur 
    during ice storms.
    IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM 
    CONTAMINANTS IN THE GAS WAYS.  SUCH FOULING MAY CAUSE 
    IMPROPER OPERATION, FIRE OR EXPLOSION.
    IF COPPER SUPPLY LINES ARE USED THEY MUST BE INTERNALLY 
    TINNED AND CERTIFIED FOR GAS SERVICE. BEFORE ATTACHING THE 
    GAS LINE, BE SURE THAT ALL GAS PIPE IS CLEAN ON THE INSIDE.
    TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY 
    LINE, A DIRT LEG (SOMETIMES CALLED SEDIMENT TRAP OR DRIP 
    LEG) MUST BE INCORPORATED IN THE PIPING (SEE FIG. 5).  THE 
    DIRT LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT 
    TO FREEZING CONDITIONS. INSTALL IN ACCORDANCE WITH 
    RECOMMENDATIONS OF SERVING GAS SUPPLIERS.  REFER 
    TO THE CURRENT EDITION OF THE NATIONAL FUEL GAS CODE.  
    For Canadian installations consult Canadian Installation Code CAN/
    CSA-B149.1.
    To prevent damage, care must be taken not to apply too much torque 
    when attaching gas supply pipe to gas valve inlet.
    Apply joint compounds (pipe dope) sparingly and only to the male threa\
    ds 
    of  pipe  joints.    Do  not  apply  compounds  to  the  first  two  threads.    Use 
    compounds resistant to the action of liquefied petroleum gases. 
    						
    							8
    FIGURE 4. WIRING DIAGRAM AND SCHEMATIC
    HEATER WIRING
    All electrical work must be installed in the United States in accordance with the current edition of the National Electrical Code
     ANSI/NFPA  No. 
    70, in Canada, with the current edition of Canadian Electrical Code CSA C22.1, must conform to all local code authority having jurisdiction.  AN 
    ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION.
    If any of the original wire as supplied with the appliance must be replaced, use only type 105°C thermoplastic or equivalent, 250°C type F must 
    be used for the flame sensor leads and the spark ignition cable must be high voltage 250°C.
     CAUTION
    LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS.  WIRING ERRORS CAN CAUSE IMPROPER AND 
    DANGEROUS OPERATION.  VERIFY PROPER OPERATION AFTER SERVICING. 
    						
    							9
    TABLE 4. GAS SUPPLY LINE SIZES (IN INCHES)*
    MAXIMUM CAPACITY OF PIPE IN CUBIC FEET PER HOUR
    BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR GAS 
    LEAKAGE. Use soap and water solution or other material acceptable for 
    the purpose in locating the leaks. DO NOT USE MATCHES, CANDLES, 
    FLAME OR OTHER SOURCES OF IGNITION FOR THIS PURPOSE.
    FIGURE 5. GAS PIPING AND  SEDIMENT TRAP INSTALLATION 
    DISCONNECT THE HEATER AND ITS MANUAL GAS SHUTOFF VALVE  
    FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY SUPPLY 
    PRESSURE TESTING EXCEEDING 1/2 PSIG (3.45 kPa). GAS SUPPLY LINE  
    MUST BE CAPPED WHEN DISCONNECTED FROM THE HEATER FOR TEST  
    PRESSURES OF 1/2 PSIG (3.45 kPa) OR LESS. THE APPLIANCE NEED  
    NOT BE DISCONNECTED, BUT MUST BE ISOLATED FROM THE SUPPLY  
    PRESSURE TEST BY CLOSING THE MANUAL GAS SHUTOFF VALVE.
    PURGING
    Gas line purging is required with new piping or systems in which air 
    has entered.
      CAUTIONPURGING SHOULD BE PERFORMED BY PERSONS EXPERIENCED 
    IN THIS TYPE GAS SERVICE. TO AVOID RISK OF FIRE OR 
    EXPLOSION, PURGE DISCHARGE MUST NOT ENTER CONFINED 
    AREAS OR SPACES WHERE IGNITION CAN OCCUR. THE AREA 
    MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION 
    MUST BE INACTIVATED OR REMOVED.
    GAS METER SIZE — NATURAL GASES ONLY
    Be sure the gas meter has sufficient capacity to supply the full rated gas 
    input of the water heater as well as the requirements of all other gas fired 
    equipment supplied by the meter.  If gas meter is too small, ask the gas 
    company to install a larger meter having adequate capacity.
    GAS PRESSURE REGULATOR
    The gas pressure regulator is built into the gas valve and is equipped to 
    operate on the gas specified on model and rating plate. The regulator is 
    factory adjusted to deliver gas to burner at correct water column pressure 
    allowing for a nominal pressure drop through the controls.
    The minimum gas supply pressure for input adjustment must not be less 
    than 6" w.c. (1.49 kPa) for natural gas and 11" w.c. (2.73 kPa).
    Do not subject the combination gas valve to inlet gas pressures of more 
    than 14.0" w.c. (3.48 kPa) - natural gas.  A service regulator is necessary 
    if higher gas pressures are encountered.
    Gas pressure specified in Table 5, refer to flow pressure taken at pressure 
    tap of automatic gas valve while heater is operating.
    TABLE 5.
    Type ofGas InputManifold 
    Pressure
    Natural 75,100 Btu/hr
    22 KW/hr 4.0 in. W.C.
    1.12 kPa
    OPERATION
    It is recommended that a qualified person perform the initial firing of the 
    heater. At this time the user should not hesitate to ask the individual any 
    questions which he may have in regard to the operation and maintenance 
    of the unit.
    TO OPERATE THE HEATER
    1.  Close the heater drain valve (Figure 1) by turning handle 
    clockwise 
    .
    2.  Open a nearby hot water faucet to permit the air in the system 
    to escape.
    3.  Fully open the cold water inlet pipe valve (Figure 1) allowing the 
    heater and piping to be filled.
    4.  Close the hot water faucet as water starts to flow.
    5.  The heater is ready to be operated.
      WARNING
    DO NOT ATTEMPT TO OPERATE WATER HEATER WITH COLD 
    WATER INLET VALVE CLOSED.
    NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN 
    IT IS FILLED WITH WATER AND A TEMPERATURE AND PRESSURE 
    RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF 
    THE HEATER. 
    LENGTH
    IN
    FEET NORMAL IRON PIPE SIZES (INCHES)
    INPUT IN THOUSANDS BTU/HR
    1/2" 3/4" 1"1 1/4" 1 1/2" 2"2 1/2" 3"4"
    10 175360680 1400 21003960630011000 230000
    20 120250485 950 146027504360 7700 15800
    30 97200 375 770 118022003520 6250 12800
    40 82170 320 660 9901900 3000 5300 10900
    50 73151 285 580 9001680 2650 4750 9700
    60 66138 260 530 8101520 2400 4300 8800
    70 61125 240 490 7501400 2250 3900 8100
    80 5711 8 220 460 6901300 2050 3700 7500
    90 5311 0 205 430 6501220 1950 3450 7200
    100 50103 195 400 6201150 1850 3250 6700
    125 4493175 360 5501020 1650 2950 6000
    150 4084160 325 5009501500 2650 5500
    175 3777145 300 4608501370 2450 5000
    200 3572135 280 4308001280 2280 4600
    LENGTH  IN 
    METERS NORMAL IRON PIPE SIZES (INCHES)
    INPUT IN KW
    1/2" 3/4" 1"1 1/4" 1 1/2" 2"2 1/2" 3"4"
    3.0 51105199410 615 11601845 32216735
    6.1 3573142278 428 8051277 22554626
    9.1 285911 0225 346 6441031 18303748
    12.2 245094193 290 556878 15523192
    15.2 214483170 264 492776 13912840
    18.3 194076155 237 445703 12592577
    21.3 183770143 220 410659 11422372
    24.4 173564165 202 381600 10832196
    27.4 163260126 190 357571 10102108
    30.5 15305711 7 182 337542 9521962
    38.1 132751105 161 299483 8641757
    45.7 12254795 146 278439 7761610
    53.3 11234288 135 249401 7171464
    61.0 10214082 126 234375 6881347 
    						
    							105. 
    Wait five (5) minutes                   to clear out any gas.  
    If you then smell gas,           STOP!  Follow "B" in 
    the safety information                above on this label.
      If you don't smell gas, go to next step.
    6.  Turn on all electrical power to the appliance.
    7.   Set thermostat to desired setting by first pressing the 
    COOLER 
      and HOTTER   buttons together and 
    holding for 1 second. Then press the HOTTER 
      
    button.
    8.   If the appliance will not operate, follow the 
    instructions "TO TURN OFF GAS TO APPLIANCE" 
    and call your technician or gas supplier.
    9.  WATER TEMPERATURE ADJUSTMENT
        is approximately 120°F (49°C).
        
       
     
    FOR YOUR SAFETY READ BEFORE OPERATING
    WARNING: If you do not follow these instructions exactly, a fire or explosion 
    may result causing property damage, personal injury or loss of life.
    •   If  you  cannot  reach  your  gas  supplier,  call  the  fire 
    department.
    C.  Use only your hand to push in the control buttons. 
    Never use tools. If the control buttons will not push 
    in,  don’t  try  to  repair  them,  call  a  qualified  service 
    technician. Force or attempted repair may result in a 
    fire or explosion.
    D.  Do not use this appliance if any part has been under 
    water. Immediately call a qualified service technician 
    to inspect the appliance and to replace any part of the 
    control system and any gas control which has been 
    under water.
    OPERATING INSTRUCTIONS
    A. Set thermostat to the lowest setting.
    B.  Turn off all the electric power to the appliance 
      if service is to be performed. 
    TO TURN OFF GAS TO APPLIANCE
    BEFORE OPERATING: ENTIRE SYSTEM MUST BE FILLED WITH WATER AND AIR PURGED FROM ALL LINES.
    1.    STOP!   Read the safety information above  
      on this label.
    2.   Set the thermostat to the lowest setting by first pressing 
    the COOLER 
     and HOTTER  buttons together 
    and holding for 1 second. Then press the COOLER 
      button until the WARM indicator light appears.  
    3.  Turn the "ON/OFF" swich on the blower control to the 
    "OFF" position.
    4.   This appliance is equipped with a device which 
    automatically lights the burner.
      DO NOT TRY TO LIGHT THE BURNER BY HAND.
    A. 
    This appliance does not have a pilot.  It is equipped with 
    an ignition device which automatically lights the burner.  
      Do not try to light the burner by hand.
    B.  BEFORE OPERATING smell all around the appliance 
    area for gas. Be sure to smell next to the floor because 
    some gas is heavier than air and will settle on the floor.
    WHAT TO DO IF YOU SMELL GAS:
    •  Do not try to light any appliance.
    •  Do not touch any electric switch;
      do not use any phone in your building.
    •  Immediately call your gas supplier from a neighbor’s 
    phone. Follow the gas supplier’s instructions.
    CAUTION:  Hotter water increases the risk 
    of scald injury.  Consult the instruction 
    manual before changing temperatures.
    WARNING:  TURN OFF ALL ELECTRIC
    POWER BEFORE SERVICING 
    						
    All American Water Heater manuals Comments (0)

    Related Manuals for American Water Heater 74 Gallon 80 Thermal Efficiency UltraLow NOx Heavy Duty Commercial Gas Water Heater User Manual