Page 11
11 FIGURE 6. WIRING DIAGRAM AND SCHEMATIC HEATER WIRING All electrical work must be installed in the United States in accordance with the current edition of the National Electrical Code ANSI/NFPA No. 70, in Canada, must conform to all local code authority having jurisdiction. AN ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION. If any of the original wire as supplied with the appliance must be replaced, use only type 105°C thermoplastic or equivalent, 250°C...
Page 12
125. Wait fi ve (5) minutes to clear out any gas. If you then smell gas, STOP! Follow B in the safety information above on this label. If you dont smell gas, go to next step. 6. Turn on all electrical power to the appliance. 7. Set thermostat to desired setting by fi rst pressing the COOLER and HOTTER buttons together and holding for 1 second. Then press the HOTTER button. 8. If the appliance will not operate, follow the instructions TO TURN...
Page 13
13. SETTING THE WATER HEATER TEMPERATURE AT 120°F (49°C) (APPROX. MARK ON FACE OF THE TEMPERATURE ADJUSTING DIAL) WILL REDUCE THE RISK OF SCALDS. Some States or Provinces require settings at specifi c lower temperatures. Figure 6 shows the approximate water temperatures produced at various thermostat settings. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 20°F (11°C). If...
Page 14
14 Type of Gas BTU Per Cu. Ft.Time Required To Consume 1 Cu. Ft. of Gas Natural 1050 50.3 Seconds CHECKING VENTING The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation. 1. Seal any unused openings in the venting system. 2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54...
Page 15
15 • To check UN•LIME for continued use or reuse, place some lime scale or white chalk into a glass with a small amount of solution. If the material is vigorously dissolved by the solution, the UN•LIME can be reused. If not, the UN•LIME has been weakened and should be replaced. 8. When deliming has been completed, the heater should be fl ushed for 3 to 5 minutes with fresh water. • Remove the deliming equipment, install the drain valve, open the cold water inlet line and allow water to fl ow...
Page 16
16 CHECKLIST Before contacting your dealer, check the water heater to see if the apparent malfunction is caused by some external fault. Consulting this checklist may eliminate the need for a repair call and restore hot water service. NOT ENOUGH OR NO HOT WATER 1. Look for leaking or open hot water faucets. Check for excessive usage. 2. Your gas company can check the gas input to the heater to see that it is correct. An underfi red heater will not produce hot water at its normal recovery rate. 3....
Page 17
17 Restart the water heater as directed under Operating Your Water Heater. See the repair parts illustration for anode rod location. Figure 9 SERVICE AND REPAIR The water heater requires no special care other than the normal maintenance as noted above. If you are having a problem with your water heater, before calling for service please refer to the following TROUBLESHOOTING sections. If service becomes necessary, contact your dealer, installer or an authorized service agent. Do...
Page 18
18 TROUBLESHOOTING For your safety, water heater service should be performed only by a qualifi ed service technician. Read the GENERAL SAFETY INFORMATION section fi rst. PROBLEMPOSSILBE MALFUNCTIONSERVICE TO BE PERFORMED NOT ENOUGH OR NO HOT WATER1) Blower will not run. A) ON/OFF control switch turned off. Turn switch to the on position. B) Blower unplugged. Plug blower back into 115 vac. outlet. C) No power at outlet. Repair service to outlet. D) ON/OFF switch defective. Replace switch. E) Control...
Page 19
19 WARNING: DO NOT BY-PASS ANY CONTROLS TO MAKE HEATER OPERATE. OPERATE ONLY AS WIRED FROM FACTORY. TROUBLE SHOOTING Please check guidelines below. For your safety, water heater service should be performed only by a qualifi ed service technician. Read the GENERAL SAFETY INFORMATION section fi rst. # LED STATUS PROBLEM SOLUTION 1 The gas control valve/thermostat has sensed inadequate or no earth ground.1 Ensure the wall outlet (power supply) is properly grounded. 2 Ensure all ground...
Page 20
20 # LED STATUS PROBLEM SOLUTION 7 8 9 Self diagnostic check has detected a problem with the gas valve driver circuit, internal microprocessor, or other internal circuits.1 Turn the power off for 10-20 seconds then on again to clear these error codes. 2 If any of these error codes persist or cannot be cleared - replace the gas control valve/thermostat. 10 The gas control valve/thermostat has sensed main burner fl ame out of proper sequence.1 Turn the power off for 10-20 seconds then on again to...