Home > American Water Heater > Gas Heater > American Water Heater 40 Gallon 38000 BTU Direct Vent Natural Gas Water Heater DVG6240S38NOV user manual

American Water Heater 40 Gallon 38000 BTU Direct Vent Natural Gas Water Heater DVG6240S38NOV user manual

    Download as PDF Print this page Share this page

    Have a look at the manual American Water Heater 40 Gallon 38000 BTU Direct Vent Natural Gas Water Heater DVG6240S38NOV user manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							   www.  
     
    americanwaterheater  
     
    .com 31
     STRANGE  SOUNDS
    Possible noises due to expansion and contraction of some 
    metal parts during periods of heat-up and cool-down do 
    not necessarily represent harmful or dangerous conditions.
    Condensation causes sizzling and popping within the 
    burner area during heating and cooling periods and should 
    be considered normal. See “Condensate” in this section.
    Sediment collecting over time in the bottom of the tank 
    can result in “rumbling” or “percolating” sounds. Follow 
    the directions given in “Draining, Refi lling And Flushing”.
       OPERATIONAL  CONDITIONS
     Smelly  Water
    In each water heater there is installed at least one anode 
    rod (see Figure 1, item 22) for corrosion protection of the 
    tank. Some models will have an additional anode which 
    is connected to the hot water outlet nipple (see Figure 1, 
    item 23). Certain water conditions will cause a reaction 
    between the anode rod and the water. The most common 
    complaint associated with the anode rod is one of a “rotten 
    egg smell” in the hot water. The smell is a result of four 
    factors which must all be present for the odo r to develop:
    1.  A concentration of sulfate in the supply water.
    2.  Little or no dissolved oxygen in the water.
    3.  A sulfate reducing bacteria which has accumulated 
    within the water heater (this harmless bacteria is 
    nontoxic to humans).
    4.  An excess of active hydrogen in the tank. This is 
    caused by the corrosion protective action of the anode.
    For certain water conditions, setting the gas control valve/
    thermostat at  140°F  can reduce the smell generated in 
    the water heater.
    Note: Under these conditions install a mixing valve to limit 
    the temperature of the water delivered to the system (see 
    “Water Piping” section).
    Smelly water may be eliminated or reduced in some water 
    heater models by replacing the anode(s) with one of less 
    active material, and then chlorinating the water heater tank 
    and all water lines. Contact the local water heater supplier 
    or service agency for further information concerning an 
    Anode Replacement Kit and this chlorination treatment.
    If the smelly water persists after the anode replacement 
    and chlorination treatment, we can only suggest that 
    chlorination or aeration of the water supply be considered 
    to eliminate the water problem.
    Do not remove the anode leaving the tank unprotected. By 
    doing so, all warranty on the water heater tank is voided. “Air” In Hot Water Faucets
    HYDROGEN GAS: Hydrogen gas can be produced in 
    a hot water system that has not been used for a long 
    period of time (generally two weeks or more). Hydrogen 
    gas is extremely fl ammable and explosive. To prevent the 
    possibility of injury under these conditions, we recommend 
    the hot water faucet, located farthest away, be opened for 
    several minutes before any electrical appliances which 
    are connected to the hot water system are used (such 
    as a dishwasher or washing machine). If hydrogen gas is 
    present, there will probably be an unusual sound similar 
    to air escaping through the pipe as the hot water faucet 
    is opened. There must be no smoking or open fl ame near 
    the faucet at the time it is open.
     High Water Temperature Shut Off System
    This water heater is equipped with an automatic gas 
    shut-off system. This system works when high water 
    temperatures are present. Turn “OFF” the entire gas supply 
    to the water heater. The high temperature shut-off is built 
    into the gas control valve. It is non-resettable. If the high 
    temperature shut-off activates, the gas control valve must 
    be replaced. Contact your gas supplier or service agency.  
    						
    							32 www.  
     
    americanwaterheater  
     
    .com  
    MAINTENANCE
    FOR YOUR SAFETY AND SATISFACTORY OPERATION, 
    IT IS RECOMMENDED THAT THIS HEATER BE 
    CHECKED ONCE A YEAR BY A COMPETENT SERVICE 
    PERSON.
    USERS OF THIS WATER HEATER SHOULD BE AWARE 
    THAT GAS COMPONENTS WEAR OUT OVER A PERIOD 
    OF TIME. THE GAS CARRYING COMPONENTS OF 
    THIS WATER HEATER SHOULD BE INSPECTED FOR 
    PROPER OPERATION PERIODICALLY BY A QUALIFIED 
    SERVICE TECHNICIAN.
     HOUSEKEEPING
    • Do not obstruct combustion air 
    openings at the vent termination 
    hood.
    • Do not use or store flammable 
    vapor products such as gasoline, 
    solvents or adhesives in the same 
    room or area near water heater, 
    the vent termination hood, or other 
    appliance.
    • Can cause serious injury or death.Fire and Explosion Hazard
    DANGER
     
    INSTALLED IN SUITABLE AREA:
    To ensure sufficient ventilation and combustion air 
    supply, proper clearances from the water heater must 
    be maintained. See “Locating The New Water Heater” 
    section. Combustible materials such as clothing, cleaning 
    materials, or fl ammable liquids, etc. must not be placed 
    against or adjacent to the water heater which can cause 
    a fi re.
     FLOOD  DAMAGE
    Flood damage to a water heater may not be readily visible 
    or immediately detectable. However, over a period of time 
    a fl ooded water heater will create dangerous conditions 
    which can cause DEATH, SERIOUS BODILY INJURY, 
    OR PROPERTY DAMAGE. Contact a qualifi ed installer or 
    service agency to replace a fl ooded water heater. Do not 
    attempt to repair the unit! It must be replaced!
     VENTING SYSTEM INSPECTION
    At least once a year a visual inspection should be made 
    of the venting system. You should look for:
    1.  Obstructions which could cause improper venting. 
    The combustion and ventilation air fl ow must not be 
    obstructed.
    2.  Damage or deterioration which could cause improper 
    venting or leakage of combustion products.
    Be sure the vent piping is properly connected to prevent 
    escape of dangerous fl ue gasses which could cause 
    deadly asphyxiation.
    Obstructions and deteriorated vent systems may present 
    serious health risk or asphyxiation.
    Chemical vapo r corrosion of the fl ue and vent system 
    may occur if air for combustion contains certain chemical 
    vapo rs. Spray can propellants, cleaning solvents, 
    refrigerator and air conditioner refrigerants, swimming pool 
    chemicals, calcium and sodium chloride, waxes, bleach 
    and process chemicals are typical compounds which are 
    potentially corrosive.
    If after inspection of the vent system you found sooting or 
    deterioration, something is wrong. Call the local gas utility 
    to correct the problem and clean or replace the fl ue  and 
    venting before resuming operation of the water heater.
    Breathing carbon monoxide can cause brain damage or death. 
    Always read and understand instruction manual.
    • Flue gases may escape if vent pipe is not 
    connected.
    • Be alert for obstructed, sooted or deteriorated 
    vent system to avoid serious injury or death.
    • Do not store corrosive chemicals in vicinity of 
    the water heater or the vent termination hood.
    • Chemical corrosion of flue and vent system 
    can cause serious injury or death.
    Breathing Hazard - Carbon Monoxide Gas
    WARNING
     PILOT AND MAIN BURNER
    At least once a year a visual inspection should be made 
    of the main burner and the pilot assembly for proper fl ame 
    characteristics. This can be done by removing the Outer 
    Door and viewing the main burner operation through the 
    Viewport on the Inner Door (see Figure 38). The main 
    burner should provide complete combustion of gas, ignite 
    rapidly, give reasonably quiet operation, and cause no 
    excessive fl ame lifting from the burner ports. If the proper 
    fl ame characteristics are not evident (see Figure 32), 
    make sure that the fl ow of combustion and ventilation 
    air is not blocked in the venting system. You should also 
    check for sooting. Soot is not normal and will impair proper 
    combustion.
    Soot build-up indicates a problem that requires correction 
    before further use. Turn “OFF” gas to water heater and 
    leave off until repairs are made, because failure to correct 
    the cause of the sooting can result in a fi re causing death, 
    serious injury, or property damage.
    If proper fl ame characteristics are not evident, call your 
    service agency to remove and clean the burner and correct 
    any operational problem. 
    						
    							   www.  
     
    americanwaterheater  
     
    .com 33
     BURNER  FLAMES
    Inspect the burner flames through the viewport and 
    compare them to the drawings in Figure 32. A properly 
    operating burner should produce a soft blue fl ame.  Blue 
    tips with yellow inner cones are satisfactory. The tips of the 
    fl  ame may have a slight yellow tint. The fl  ame should not be 
    all yellow or have a sharp blue-orange colo r. Contaminated 
    air may cause an orange colo red fl  ame. Contact a qualifi ed 
    service technician if the fl ame is not satisfactory
    CORRECT FLAME 
    SOFT BLUE
    INCORRECT 
    FLAME LAZY 
    YELLOW
    TIPS MAY HAVE 
    A YELLOW TINT
    YELLOW INNER 
    CONES ARE 
    SATISFACTORY
    Figure 32 
     SERVICING THE WATER HEATER
    Servicing this water heater shall be done by qualifi ed 
    service personnel only.
    1.  Before performing any maintenance, it is important 
    to turn “OFF” the gas supply to the water heater at 
    the manual gas shut-off valve. This valve is typically 
    located beside the water heater. Note the position of 
    the shut-off valve in the open/on position, then proceed 
    to turn it “OFF” (see Figure 1).
    2.  With the water heater shut-off, allow suffi cient time for 
    the it to cool off before performing any service.
       REMOVING AND REPLACING THE GAS CONTROL 
    VALVE/THERMOSTAT
     Removing The Gas Control Valve/Thermostat:
    1.  Turn the gas control/temperature knob to the “OFF” 
    position (see Figure 31 and Figure 33).
    2.  Turn “OFF” the gas at the manual gas shut-off valve 
    (see Figure 1).
    3.  Drain the water heater. Refer to the “Draining, Refi lling 
    And Flushing” section and follow the procedure.
    4.  Disconnect the igniter wire from the igniter lead wire. 
    Use needle nose pliers to disconnect the thermopile 
    connector. Disconnect the pilot tube (7/16” wrench) 
    and manifold tube (3/4” wrench) at the gas control 
    valve/thermostat (see Figure 33).
    Note: Propane (LP) Gas systems use reverse (left-hand) 
    threads on the manifold tube.
    5.  Refer to “Gas Piping” and disconnect the ground joint 
    union in the gas piping (see Figure 13 & Figure 14). 
    Disconnect the remaining pipe from the gas control 
    valve/thermostat.
    6.  To remove the gas control valve/thermostat, thread a 
      4”  section of gas pipe into the inlet and use it to turn 
    the gas control valve/thermostat (counterclockwise). 
    Do not use a pipe wrench or equivalent to grip body. 
    Damage may result, causing leaks. Do not insert 
    any sharp objects into the inlet or outlet connections. 
    Damage to the gas control valve/thermostat may 
    result.
       Replacing The Gas Control Valve/Thermostat:
    To replace the gas control valve/thermostat, reassemble 
    in reverse order. When replacing the gas control valve/
    thermostat, thread a  4”  section of gas pipe into the inlet and 
    use it to turn the gas control valve/thermostat (clockwise). 
    DO NOT OVER TIGHTEN; damage may result.
    • Be sure to use approved Tefl on® tape or pipe joint 
    compound on the gas piping connections and fi tting 
    on the back of the gas control valve that screws into 
    the tank.
    • Be sure to remove the pilot ferrule nut from the new gas 
    control valve/thermostat. Reconnect the manifold tube, 
    pilot tube, igniter wire and the thermopile connections.
    • Turn the main gas supply “ON” and check the gas 
    supply connections for leaks. Correct any leak found.
    • Light the pilot and main burner, then check the manifold 
    tube and pilot tube connections for leaks. Use an 
    approved noncorrosive leak detection solution. If such 
    a solution is not available, use a mixture of hand dish 
    washing soap and water (one part soap to 15 parts 
    water) or childrens’ soap bubble solution. Bubbles 
    forming indicate a leak. Correct any leak found.
    • Be sure tank is completely fi lled with water before 
    lighting and activating the water heater. Follow the 
    lighting instructions on the label or see “Lighting 
    Instructions” to restart the water heater.
    If additional information is required, reference the number 
    on the cover of this manual for service information.
    TEFLON® is a registered trademark of E.I. Du Pont De Nemours and 
    Company
       REMOVING THE MANIFOLD/BURNER ASSEMBLY
    1.  Turn the gas control/temperature knob to the “OFF” 
    position (see Figure 31 and Figure 33).
    2.  Turn “OFF” the gas at the manual gas shut-off valve 
    (see Figure 1).
    IGNITER
    WIRERED WIRE PILOT
    TUBE
    MANIFOLD TUBE IGNITER
    BUTTON
    IGNITER
    LEAD
    WIREWHITE
    WIRE GAS CONTROL/
    TEMPERATURE 
    KNOB
    THERMOPILE 
    CONNECTOR
    Figure 33 
    3.  Remove the outer door.
    4.  Disconnect the following from the gas control valve/
    thermostat: pilot tube (7/16” wrench), igniter wire (from 
    the igniter lead wire), and manifold tube (3/4” wrench) 
    (see Figure 33).
    Note: Propane (LP) Gas systems use reverse (left-hand) 
    threads on the manifold tube.
    5.  Use needle nose pliers to disconnect the thermopile 
    connector from the gas control valve/thermostat (see 
    Figure 33).
    6.  Grasp the manifold tube and push down slightly to   
    						
    							34 www.  
     
    americanwaterheater  
     
    .com  
    free the manifold tube and pilot tube.
    7.  Remove the screws (1/4” nut driver) securing the 
    manifold/burner assembly to the combustion chamber 
    (Figure 34).
    8.  Carefully remove the manifold/burner assembly 
    from the combustion chamber. BE SURE NOT TO 
    DAMAGE ANY INTERNAL PARTS.
    VIEWPORTPILOT TUBE
    MANIFOLD 
    DOOR
    MANIFOLD COMPONENT 
    BLOCKMANIFOLD 
    TUBE
    OUTER DOOR 
    NOT SHOWNMANIFOLD
    SCREW (2) GAS CONTROL 
    VALVE/THERMOSTATTHERMOPILE
    WIRE
    CONNECTIONS GAS CONTROL/
    TEMPERATURE 
    KNOB
    PIEZO IGNITER 
    BUTTON
    Figure 34 
     REMOVING THE BURNER FROM THE MANIFOLD/
    BURNER ASSEMBLY
     Natural Gas (Low Nox) & Propane (LP) Gas Burner
    1.  Take off the burner by removing the two (2) screws 
    located underneath the burner.
    2.  Check the burner to see if it is dirty or clogged. The 
    burner may be cleaned with soap and hot water (see 
    Figure 35).
    Important: DO NOT remove the orifi ce.
    SCREWS
    BURNER 
    (BOTTOM VIEW)PILOT 
    ASSEMBLY 
    (BOTTOM VIEW)
    KEEP DRAIN 
    HOLE IN THIS 
    POSITION
    Figure 35 
    3.  When replacing the burner, ensure the drain hole is 
    in the position shown in Figure 35.
     REPLACING THE PILOT/THERMOPILE ASSEMBLY
    1.  Remove the manifold door assembly as described in 
    “Removing The Manifold/Burner Assembly” section.
    2.  Remove the burner to access the pilot/thermopile 
    assembly. Remove and keep the screws securing the 
    burner to the manifold (see Figure 35).
    Important: DO NOT remove the orifi ce.
    3.  Remove the screw securing the pilot/thermopile 
    assembly to the pilot bracket and keep for reuse later 
    (see Figure 36 & Figure 39).
    4.  Lift the retainer clip straight up from the back of 
    the manifold component block (using a fl at-blade 
    screwdriver), then remove the manifold component 
    block from the manifold door (see Figure 36).
    Important: Be careful not to bend or alter the position of 
    the pilot tube. It will be used as a bending template for the 
    new pilot assembly. Note the placement/order of the wires 
    in the manifold component block.
    BURNER AND 
    OTHER FITTINGS 
    NOT SHOW FOR 
    CLARITY.
    PILOT/THERMOPILE 
    ASSEMBLY SCREW THERMOPILE 
    CONNECTORPILOT 
    TUBE
    IGNITER 
    WIRE
    MANIFOLD 
    COMPONENT 
    BLOCKRETAINER 
    CLIP
    MANIFOLD 
    DOOR PILOT/THERMOPILE 
    ASSEMBLY
    GASKET
    TA B
    BRACKETSLOT
    VIEWPORT
    Figure 36 
    5.  Lift the pilot/thermopile assembly (including the igniter 
    wire) from the manifold assembly (see Figure 37).
    6.  Read this step carefully before proceeding. Using the 
    old pilot/pilot tube assembly as a guide, bend the new 
    pilot tube to match the old one. Make only the bends 
    closest to the pilot before going to the next step.
    THERMOPILE 
    WIRES
    THERMOPILE 
    CONNECTOR
    PILOT TUBE NOT 
    SHOWN FOR CLARITY IGNITER 
    CONNECTOR
    PILOT/
    THERMOPILE 
    ASSEMBLY THERMOPILE
    PILOT
    Figure 37 
    7.  Route the new pilot tube, igniter wire and thermopile 
    wires through the opening in the manifold door (see 
    Figure 36).    
    						
    							   www.  
     
    americanwaterheater  
     
    .com 35
    8.  Using the pilot screw removed earlier, attach the new 
    pilot/thermopile assembly. Reattach the burner to the 
    manifold using the screws removed earlier.
    9.  Reinstall the manifold component block in the 
    manifold door. Ensure that the pilot tube and wires 
    are positioned as shown in Figure 38.
    MANIFOLD
    COMPONENT
    BLOCK
    PILOT TUBE PASSES 
    THROUGH TOP 
    HOLE OF MANIFOLD 
    COMPONENT BLOCK 
    (LARGEST HOLE)IGNITER WIRE 
    PASSES THROUGH 
    CENTER OF MANIFOLD 
    COMPONENT BLOCK 
    (SMALLEST HOLE) THERMOPILE WIRES 
    PASS THROUGH 
    BOTTOM HOLE 
    OF MANIFOLD 
    COMPONENT BLOCK
    VIEWPORT
    Figure 38 
    10.  Carefully bend the new pilot tube to match the bend 
    of the manifold tube.
    Note: When bending, DO NOT crimp or crease the pilot 
    tube.
    11.  Before you proceed to the next step, install the new 
    brass ferrule nut in the gas control valve/thermostat’s 
    pilot tube opening, HAND TIGHT ONLY.
    12. Install the manifold/burner assembly. Refer to the 
    “Replacing The Manifold/Burner Assembly” section 
    for instructions.
       REPLACING THE MANIFOLD/BURNER ASSEMBLY
    1.  Check the door gasket for damage or imbedded debris 
    prior to installation (see Figure 36).
    2.  Inspect the viewport for damage and replace as 
    required (see Figure 36).
    3.  Insert the new manifold/burner assembly into the 
    burner compartment, making sure that the tab of the 
    manifold tube engages the slot of the bracket inside 
    the combustion chamber (see Figure 36).
    4.  Inspect the door gasket and make sure there is no 
    fi berglass insulation between the gasket and the 
    combustion chamber (see Figure 36).
    5.  Tighten the two screws that secure the manifold/burner 
    assembly to the combustion chamber. (Use a 1/4” nut 
    driver.) There should be no space between the gasket 
    part of the manifold door and combustion chamber.Important: Do not operate the water heater if the door 
    gasket does not create a seal between the manifold door 
    and the combustion chamber.
    6.  Reconnect the manifold tube (3/4” wrench) and pilot 
    tube (7/16” wrench) to the gas control valve/thermostat 
    (see Figure 33). Do not cross-thread or apply any 
    thread sealant to the fi ttings.
    Important: If you were supplied with a new ferrule nut in 
    a parts kit, follow these steps to connect the pilot tube:
    1.)  Install the ferrule nut into the gas valve at the pilot 
    tube location, hand tight only.
    2.)  Insert the pilot tube into the ferrule nut until the 
    tube bottoms out, then tighten the nut with a 7/16” 
    wrench until the crimp connection seals to the 
    pilot tube.
    3.)  Continue to tighten until the nut is tight in the gas 
    valve.
    Note: Propane (LP) Gas systems use reverse (left-hand) 
    threads on the manifold tube.
    7.  Connect thermopile connector to the gas control valve/
    thermostat (see Figure 33).
    8.  Reconnect the igniter wire (see Figure 33).
    9.  Turn “ON” the gas supply to the water heater at the 
    manual gas shut-off valve (see Figure 1).
    10. Follow the lighting instructions on the label or see 
    “Lighting Instructions” to restart the water heater. With 
    the main burner lit, check for leaks at the manifold 
    and pilot connections by brushing on an approved 
    noncorrosive leak detection solution. If such a solution 
    is not available, use a mixture of hand dish washing 
    soap and water (one part soap to 15 parts water) 
    or childrens’ soap bubble solution. Bubbles forming 
    indicate a leak. Correct any leak found.
    11.  Verify proper operation, then replace the outer door.
    Explosion Hazard
    Tighten both manifold door screws securely.
    Remove any fiberglass between gasket and
    combustion chamber.
    Replace viewport if glass is missing
    or damaged.
    Replace manifold component block if miss-
    ing or removed.
    Replace door gasket if damaged.
    Failure to do so can result in death,
    explosion, or fire.
    WARNING  
    						
    							36 www.  
     
    americanwaterheater  
     
    .com  
     PIEZOELECTRIC IGNITER SYSTEM
    The piezoelectric igniter system consists of the igniter 
    button, electrode, and wire. The pilot is ignited by an 
    electric spark generated when the igniter button is pressed 
    (see Figure 39).
    PILOT/
    THERMOPILE
    BRACKET
    ELECTRODETHERMOPILE
    PILOT
    IGNITER BUTTONWIRE TO ELECTRODE
    Figure 39 
     TESTING THE IGNITER SYSTEM
    Turn “OFF” the gas to the water heater at the manual gas 
    shut-off valve. Watch the electrode tip while activating the 
    igniter. A visible spark should jump from the electrode. To 
    avoid shock, do not touch the burner or any metal part 
    on the pilot or pilot assembly. If no spark is visible, check 
    the wire connections and make sure the electrode is not 
    broken. Replace the igniter if defective. Dirt and rust on the 
    pilot or electrode tip can prevent the igniter spark. Wipe 
    clean with a damp cloth and dry completely. Rust can be 
    removed from the electrode tip and metal surfaces by 
    lightly sanding with an emery cloth or fi ne grit sandpaper.
     TEMPERATURE-PRESSURE RELIEF VALVE TEST
    It is recommended that the temperature-pressure relief 
    valve be checked to ensure it is in operating condition at 
    least once a year.
    When checking the temperature-pressure relief valve 
    operation, make sure that (1) no one is in front of or around 
    the outlet of the T&P valve discharge line, and (2) that 
    water discharge will not cause any property damage, as 
    water may be extremely hot. Use care when operating 
    valve as the valve may be hot.
    To check the relief valve, lift lever at the end of valve 
    several times (see Figure 40). The valve should seat 
    properly and operate freely.
    If after manually operating the valve, it fails to completely 
    reset and continues to release water, immediately close 
    the cold water inlet to the water heater and drain the 
    water heater, see “Draining, Refilling And Flushing” 
    section. Replace the T&P valve with a properly rated/
    sized new one, see “Temperature-Pressure Relief Valve” 
    for instructions on replacement.
    Figure 40 
    If the Temperature-Pressure Relief Valve on the water 
    heater weeps or discharges periodically, it may be due to 
    thermal expansion.
    Note: Excessive water pressure is the most common 
    cause of temperature-pressure relief valve leakage. 
    Excessive water system pressure is most often caused 
    by “thermal expansion” in a “closed system.” See “Closed 
    Water Systems” and “Thermal Expansion” sections of this 
    manual. The T&P valve is not intended for the constant 
    relief of thermal expansion.
    • Burn hazard.
    • Hot water discharge.
    • Keep clear of 
    temperature-pressure 
    relief valve discharge.
    BURN
    HOT
    HOT
    DANGER
       DRAINING, REFILLING AND FLUSHING
    Periodic draining and cleaning of sediment from the tank 
    maybe necessary. It is recommended that the tank be 
    drained and fl ushed every 6 months to remove sediment 
    which may build up during operation. The water heater 
    should be drained if being shut down during freezing 
    temperatures or for an extended period of time. See 
    “Typical Installation” section (Figure 1) in this manual for 
    location of the water heater components described below.
     To Drain The Water Heater Storage Tank
    1.  Turn the gas control/temperature knob to the “OFF” 
    position (see Figure 31 and Figure 33).
    2.  Turn “OFF” the gas supply at the manual gas shut-off 
    valve.
    3.  Close the cold water inlet valve to the water heater.
    4.  Open a nearby hot water faucet and leave open to 
    allow for draining.
    5.  Connect a hose to the drain valve and terminate to 
    an adequate drain.
    Note: If the water heater is going to be shut down and 
    drained for an extended period, the drain valve should be 
    left open with hose connected allowing water to terminate 
    to an adequate drain.
    6.  Open the water heater drain valve.
    7.  Close the water heater drain valve when all water in 
    the storage tank has drained.  
    						
    							   www.  
     
    americanwaterheater  
     
    .com 37
     To  Refi ll The Water Heater Storage Tank
    1.  Close the water heater drain valve.
    2.  Remove the drain hose.
    3.  Open a nearby hot water faucet and leave open to 
    allow air to escape.
    4.  Open the cold water inlet valve to the water heater.
    5.  To purge the lines of any excess air, keep the hot 
    water faucet open for 3 minutes after a constant fl ow 
    of water is obtained.
    6.  Turn “ON” the gas supply at the manual gas shut-off 
    valve.
    7.  Follow the lighting instructions on the label or see 
    “Lighting Instructions” to restart the water heater.
     To Flush The Water Heater Storage Tank
    1.  Turn “OFF” the gas at the manual gas shut-off valve 
    (see Figure 1).
    2.  Ensure the cold water inlet valve is open.
    3.  Connect a hose to the drain valve and terminate it to 
    an adequate drain.
    4.  Ensure the drain hose is secured before and during the 
    entire fl ushing procedure. Flushing is performed with 
    system water pressure applied to the water heater.
    5.  Open the water heater drain valve to fl ush the storage 
    tank. Caution: Water will be hot.
    6.  Flush the water heater storage tank to remove 
    sediment and allow the water to fl ow until it runs clean.
    7.  Close the water heater drain valve when fl ushing  is 
    completed.
    8.  Remove the drain hose.
    9.  Ensure the heater is full of water.
    10.  Turn “ON” the gas supply at the manual gas shut-off 
    valve.
    11.  Follow the lighting instructions on the label or see 
    “Lighting Instructions” to restart the water heater.
    12. Allow the water heater to complete several heating 
    cycles to ensure it is operating properly.
    Caution: Do not turn on the gas to the water heater 
    unless the tank is full. Open a hot water faucet and allow 
    the water to run until the air is purged and the water fl ows 
    uninterrupted from the faucet.
    Important: When operating a cold tank, condensation can 
    occur and drip on the burner. This should not be confused 
    with a tank leak.
     DRAIN VALVE WASHER REPLACEMENT
    1.  Turn “OFF” the gas at the manual gas shut-off valve 
    (see Figure 1).
    2.  Follow “Draining” instructions in the “Draining, Refi lling 
    And Flushing” section.
    3.  Turning counterclockwise (
    ), remove the hex cap 
    below the screw handle.
    4.  Remove the washer and put the new one in place.
    5.  Screw the handle and cap assembly back into the 
    drain valve and retighten using a wrench. DO NOT 
    OVER TIGHTEN.
    6. Follow “Refi lling” instructions in the “Draining, Refi lling 
    And Flushing” section.
    7.  Check for leaks. Repair as needed.
    8.  Follow the lighting instructions on the label or see 
    “Lighting Instructions” to restart the water heater.
    HANDLE AND 
    CAP ASSEMBLY ALTERNATIVE 
    STEM HANDLE
    WASHER
    Figure 41 
     ANODE ROD MAINTENANCE
    Each water heater contains at least one anode rod, 
    which will slowly deplete (due to electrolysis) prolonging 
    the life of the water heater by protecting the glass-lined 
    tank from corrosion. Adverse water quality, hotter water 
    temperatures, high hot water usage, hydronic heating 
    devices, and water softening methods can increase 
    the rate of anode rod depletion. Once the anode rod 
    is depleted, the tank will start to corrode, eventually 
    developing a leak.
    Certain water conditions will cause a reaction between the 
    anode rod and the water. The most common complaint 
    associated with the anode rod is a “rotten egg smell” 
    produced from the presence of hydrogen sulfi de  gas 
    dissolved in the water. See “Operational Conditions”.
    Important: Do not remove this rod permanently as it will 
    void any warranties. A special anode rod may be available 
    if water odo r or discolo ration occurs.
    CAP
    ANODE ROD *
    * THE ANODE ROD IS COVERED 
    BY URETHANE FOAM LOCATED 
    UNDER THE CAP. CHIP AWAY 
    THE FOAM TO EXPOSE THE 
    TOP OF THE ANODE ROD 
    Figure 42      
    						
    							38 www.  
     
    americanwaterheater  
     
    .com  
    Note: This rod may reduce but not eliminate water odo r 
    problems. The water supply system may require special 
    fi ltration equipment from a water conditioning company to 
    successfully eliminate all water odo r problems.
    Artifi  cially softened water is exceedingly corrosive because 
    the process substitutes sodium ions for magnesium and 
    calcium ions. The use of a water softener may decrease 
    the life of the water heater tank. The anode rod (see Figure 
    42) should be inspected after a maximum of three years 
    and annually thereafter until the condition of the anode 
    rod dictates its replacement (see Figure 43).
    EXPOSED 
    SUPPORT 
    WIRE
    PITTED ANODE  ROD EXPOSED 
    SUPPORT 
    WIRE
    Figure 43 
    Note: Artifi cially softened water requires the anode rod to 
    be inspected annually. The following are typical (but not 
    all) signs of a depleted anode rod:
    • The majority of the rods diameter is less than  3/8” .
    • Signifi cant sections of the support wire (approx. 1/3 or 
    more of the anode rod’s length) are visible.
    If the anode rod show signs of either or both it should be 
    replaced.
    Note: Whether re-installing or replacing the anode rod, 
    check for any leaks and immediately correct if found.
     To Remove The Anode Rod:
    1.  Turn the gas control/temperature knob to the “OFF” 
    position (see Figure 31 and Figure 33).
    2.  Turn “OFF” the gas at the manual gas shut-off valve 
    (see Figure 1).
    3.  Shut off the incoming water supply to the water heater 
    and open a nearby hot water faucet to depressurize 
    the water tank.
    4.  Connect a hose to the drain valve and terminate it to 
    adequate drain or to the exterior of the building. Open 
    the drain valve and drain approximately  5 gallons  of 
    water from tank. (Refer to “Draining, Refi lling  And 
    Flushing” for proper procedures). Close drain valve 
    and remove hose.
    5.  Remove and retain the anode cap on top of the heater 
    and remove and retain just enough insulation so you 
    can access to the anode head (see Figure 42). Keep 
    in a safe place for reinstallation later.
    6.  Remove the anode rod by using a ratchet and a 
    1-1/16” socket turning counter-clockwise (see Figure 
    42). To Install The Anode Rod:
    1. Use Tefl on
    ® tape or an approved pipe sealant on 
    threads of the new anode rod.
    2.  Place the anode rod in the spud (top of the tank) (see 
    Figure 42) and turn clockwise until the threads are 
    hand tight. Using a ratchet and 1-1/16” socket tighten 
    down water tight.
    3.  Open a nearby hot water faucet to purge air from 
    the water line. Fill water heater tank completely. 
    (Refer to “Draining, Refi lling And Flushing” for proper 
    procedures).
    Note: To assure the water heater tank is full, keep the hot 
    water faucet open for 3 minutes after a constant fl ow  of 
    water is obtained.
    4.  After turning closing the hot water faucet, check for 
    water leaks around anode rod and immediately correct 
    any if found.
    5.  Reinstall the insulation and anode cap which were 
    removed in step 5 of removal process.
    6.  Turn “ON” the manual gas shut-off valve (see Figure 
    1).
    7.  Turn the gas control/temperature knob to the “ON” 
    position (see Figure 31 and Figure 33).
    8.  Follow the lighting instructions on the label or see 
    “Lighting Instructions” to restart the water heater. 
    						
    							   www.  
     
    americanwaterheater  
     
    .com 39
    LEAKAGE CHECKPOINTS
     SERVICE
    If a condition persists or you are uncertain about the 
    operation of the water heater contact a service agency.
    Use this guide to check a “Leaking” water heater (see 
    Figure 44). Many suspected “Leakers” are not leaking 
    tanks. Often the source of the water can be found and 
    corrected.
    If you are not thoroughly familiar with gas codes, your 
    water heater, and safety practices, contact your gas 
    supplier or qualifi ed installer to check the water heater.
    Read this manual fi rst. Then before checking the water 
    heater make sure the gas supply has been turned “OFF”, 
    and never turn the gas “ON” before the tank is completely 
    full of water.
    Never use this water heater unless it is completely fi lled 
    with water. To prevent damage to the tank, the tank must 
    be fi lled with water. Water must fl ow from the hot water 
    faucet before turning “ON” gas to the water heater.
    D. Water at the vent assembly is water vapo r which has 
    condensed out of the combustion products. This is 
    caused by a problem in the vent. Contact the gas utility.
    E.  *Condensation may be seen on pipes in humid weather 
    or pipe connections may be leaking.
    F.  *The anode rod fi tting may be leaking (anode is located 
    under the plastic plug and insulation).
    G. Small amounts of water from temperature-pressure 
    relief valve may be due to thermal expansion or high 
    water pressure in your area.
    H.  *The temperature-pressure relief valve may be leaking 
    at the tank fi tting.
    I.  Water from a drain valve may be due to the valve being 
    slightly opened.
    J.  *The drain valve may be leaking at the tank fi tting.
    K.  Combustion products contain water vapo r which can 
    condense on the cooler surfaces of the tank. Droplets 
    form and drip onto the burner or run on the fl oor. This 
    is common at the time of start-up after installation and 
    when incoming water is cold.
    L.  Water in the water heater bottom or on the fl oor  may 
    be from condensation, loose connections, or the relief 
    valve. DO NOT replace the water heater until a full 
    inspection of all possible water sources is made and 
    necessary corrective steps taken.
    M. The combo heating system connections may be 
    leaking.
    Leakage from other appliances, water lines, or ground 
    seepage should also be checked.• * To check where threaded portion enters tank, insert 
    cotton swab between jacket opening and fi  tting. If cotton 
    is wet, follow the draining instructions in this manual, 
    and then remove fi tting. Put pipe dope or Tefl on
    ® tape 
    on the threads and replace. To refi ll the water heater 
    follow the instructions in “Draining, Refilling And 
    Flushing”.
    F
    G
    I
    H
    D
    E
    A
    BB
    C
    J
    Figure 44    
    						
    							40 www.  
     
    americanwaterheater  
     
    .com  
    REFERENCE PARTS LISTING
    Replacement parts may be ordered 
    through your plumber or the local 
    distributor. When ordering replacement 
    parts, always have the following 
    information ready:
    1.  Model, Serial and Product number
    2.  Type of gas
    3. Item number
    4. Parts description
    1 Vent Termination Hood
    2 Wall Plate
    3 ***Vent Pipe
    4 Cold Water Inlet Nipple/Diptube
    6 T&P Valve
    7 Gas Control Valve/Thermostat 
    (Honeywell)
    9 *Discharge Pipe
    10 Drain Valve
    11 Outer Gas Door
    12 Manifold Door Assembly (behind 
    outer door) (see Figure 3 & 
    Figure 4) (see also 
    Figure 47 & 
    Figure 48
    )
    13 *Floor Drain
    14 *Metal Drain Pan15 Flexible Manifold Tube (see 
    Figure 3 & Figure 4) (see also 
    Figure 47 & Figure 48)
    22 Anode (under cap)
    23 Hot Water Outlet Nipple (or Optional 
    Nipple/Anode)
    26 Air Inlet Snorkel
    27 Air Tower
    28 ***Airbox
    29 *Thermal Expansion Tank (required 
    for all closed systems)
    30 Sheet Metal Burner (see Figure 3 & 
    Figure 4) (see see also Figure 47 & 
    Figure 48)
    31 Gas Orifi ce (see Figure 3 & 
    Figure 4) (see also Figure 47 & 
    Figure 48)
    32 Gas Manifold (see Figure 3 & Figure 
    4) (see also Figure 47 & Figure 48)
    33 Manifold Door Gasket (see Figure 3 & 
    Figure 4) (see also 
    Figure 47 & Figure 48)
    34 Manifold Door (see Figure 3 & Figure 
    4) (see also Figure 47 & Figure 48)
    35 Two Piece Grommet With Clip (see 
    Figure 3 & Figure 4) (see also 
    Figure 47 & Figure 48)
    36 Viewport (see Figure 3 & Figure 4) 
    (see also 
    Figure 47 & Figure 48)
    37 Flexible Manifold Tube (see 
    Figure 3 & Figure 4) (see also 
    Figure 47 & Figure 48)
    38 Pilot (see Figure 3 & Figure 4) (see 
    also 
    Figure 47 & Figure 48)
    39 Thermopile (see Figure 3 & 
    Figure 4) (see also 
    Figure 47 & 
    Figure 48
    )
    40 Pilot Shield (see Figure 3 & 
    Figure 4) (see also 
    Figure 47 & 
    Figure 48
    )
    *  Items not supplied with the water 
    heater.
    ***  During operation the vent pipe and 
    airbox can get hot.
    23
    132
    6
    4
    9
    10
    13
    14
    15
    2
    1112
    4
    7
    22
    22
    Front View
    Figure 45  Figure 46
    26
    1
    27
    28
    Rear View   
    						
    All American Water Heater manuals Comments (0)

    Related Manuals for American Water Heater 40 Gallon 38000 BTU Direct Vent Natural Gas Water Heater DVG6240S38NOV user manual