Home > American Water Heater > Gas Heater > American Water Heater 40 Gallon 38000 BTU Direct Vent Natural Gas Water Heater DVG6240S38NOV user manual

American Water Heater 40 Gallon 38000 BTU Direct Vent Natural Gas Water Heater DVG6240S38NOV user manual

    Download as PDF Print this page Share this page

    Have a look at the manual American Water Heater 40 Gallon 38000 BTU Direct Vent Natural Gas Water Heater DVG6240S38NOV user manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							   www.  
     
    americanwaterheater  
     
    .com 21
    CERTIFIED GAS 
    SUPPLY FLEX PIPE 
    (PROPERLY SIZED 
    FOR THE HEATER 
    INPUT RATE)
    SEDIMENT 
    TRAPGAS 
    CONTROL 
    VA LV E GROUND 
    JOINT 
    UNION 
    (OPTIONAL)
    CAP
    3” 
    MIN.
    Figure 13 
    BLACK PIPE
    SEDIMENT 
    TRAPGAS 
    CONTROL 
    VA LV E GROUND 
    JOINT 
    UNION 
    (OPTIONAL)
    CAP
      3”  MIN.
    Figure 14 
     SEDIMENT  TRAP
    • Contaminants in gas lines can 
    cause fire or explosion.
    • Clean all gas piping before 
    installation.
    • Install sediment trap in accor-
    dance with NFPA54.Fire and Explosion Hazard
    WARNING
     
    A sediment trap should be installed as close to the inlet of 
    the water heater as practical at the time of water heater 
    installation. The sediment trap should be either a tee fi tting 
    with a capped nipple in the bottom outlet or other device 
    recognized as an effective sediment trap. If a tee fi tting is 
    used, it should be installed in conformance with one of the 
    methods of installation shown in Figure 13 & Figure 14.
    Contaminants in the gas lines may cause improper 
    operation of the gas control valve/thermostat that may 
    result in fi re or explosion. Before attaching the gas line be 
    sure that all gas pipe is clean on the inside. To trap any 
    dirt or foreign material in the gas supply line, a sediment 
    trap (sometimes called a dirt leg) must be incorporated in 
    the piping. The sediment trap must be readily accessible. 
    Install in accordance with the “Gas Piping” section. Refer 
    to the current edition of the  
    “National Fuel Gas Code” 
    (ANSI Z223.1/NFPA 54) .
     HIGH  ALTITUDE  INSTALLATIONS
    Installations above  7,700’ . require replacement of the 
    burner orifi ce in accordance with the current edition of 
    the  
    “National Fuel Gas Code” (ANSI Z223.1/NFPA 54). 
    Failure to replace the orifi ce could result in improper and 
    ineffi cient operation of the appliance, producing carbon 
    monoxide gas in excess of safe limits, which could result 
    in serious personal injury or death. Contact your gas 
    supplier for any specifi c changes which may be required 
    in your area.
    Breathing carbon monoxide can cause brain damage or death.
    Always read and understand instruction manual.
    • High altitude orifice must be 
    installed for operation above 
    7,700 ft.
    • Contact a qualified installer or 
    service agency.
    Breathing Hazard - Carbon Monoxide Gas
    WARNING
        
    						
    							22 www.  
     
    americanwaterheater  
     
    .com  
     
     VENTING
    This direct vent water heater uses a sealed venting 
    system to supply fresh combustion air to the heater and 
    to exhaust the products of combustion (fl ue gases) to the 
    outdoors. The venting is a “pipe in a pipe” system. The 
    inner (3”) piping carries out the exhaust fl ue gases while 
    the outer (6”) piping carries in fresh combustion air. The 
    corrugated end of the vent piping connects to the top of 
    the water heater and the opposite end connects to the vent 
    termination hood which will be mounted on the exterior wall 
    (see Figure 16). Figure 16 shows the hot exhaust gas exit 
    and the location of the combustion air intake.
    Figure 19 thru Figure 26 show how to assemble and 
    connect the venting system.
    Figure 28 thru Figure 30 show various installation options.
    DO NOT STORE OR USE GASOLINE OR OTHER 
    FLAMMABLE VAPO RS AND LIQUIDS IN THE VICINITY 
    OF THE VENT TERMINATION HOOD.
    NEVER OPERATE THE WATER HEATER UNLESS IT IS 
    VENTED TO THE  OUTDOORS AND  HAS ADEQUATE AIR 
    SUPPLY TO AVOID RISKS OF IMPROPER OPERATION, 
    FIRE, EXPLOSION OR ASPHYXIATION.
    DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND 
    VENTILATING AIR. ADEQUATE AIR  FOR  COMBUSTION 
    AND VENTILATION MUST BE PROVIDED FOR SAFE 
    OPERATION.
     
    **Minimum 12 in.
    Minimum 12 in.
    above grade or
    anticipated snow
    level
    Minimum 12 in.
    under veranda, porch,
    deck or balcony
    (see footnote 1)
    Minimum
    3 ft.
    above if within
    10 ft.
    horizontally to
    a mechanical air
    supply inlet
    Minimum 9 in. to a non mechanical air supply inlet
    into building or combustion air inlet to another appliance Minimum 12 in.
    from soffit *Minimum 9 in. to
     a window or door
     that may be opened
    **Minimum
    18 in.
    from outside
    corner
    1. Permitted only if veranda, porch, deck or balcony is fully opened on a minimum of two sides beneath the floor.
    2. A vent shall not terminate above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings. AREA WHERE TERMINAL IS NOT PERMITTED VENT TERMINAL AIR SUPPLY INLETMinimum
    3 ft.
    clearance to a 
    service regulator
    vent outlet** Or as required by local authorities.
    Figure 15 
    Breathing carbon monoxide can cause brain damage or death.
    Always read and understand instruction manual.
    • Install vent system In accordance with codes.
    • Do not operate water heater if flood damaged.
    • Install water heater in accordance with the 
    instruction manual.
    • Do not operate if soot buildup is present.
    • Do not obstruct water heater air intake.
    • Do not place chemical vapor emitting products near 
    water heater or vent terminal hood.
    • Gas and carbon monoxide detectors are available.
    • Never operate the heater unless it is vented to the 
    outdoors and has adequate air supply to avoid risks 
    of improper operation, fire, explosion or asphyxia-
    tion.
    • Analyze the entire vent system to make sure that 
    condensate will not become trapped in a section of 
    vent pipe and therefore reduce the open cross 
    sectional area of the vent.
    • Chemical corrosion of flue and vent system can 
    cause serious injury or death.
    Breathing Hazard - Carbon Monoxide Gas
    WARNING
     VENT TERMINAL CLEARANCES
    The vent system must terminate so that proper clearances 
    are maintained as cited in local codes or the current edition 
    of the  
    “National Fuel Gas Code”, ANSI Z223.1/NFPA 
    54 as follows: 
    						
    							   www.  
     
    americanwaterheater  
     
    .com 23
    FRESH 
    COMBUSTION 
    AIR IN
    HOT 
    EXHAUST 
    GAS OUT
    SCREW
    Figure 16 
    Be sure venting is properly connected to prevent escape 
    of dangerous flue gases which could cause deadly 
    asphyxiation.
     DV TERMINATION SAFETY COVER
    When the heater is in operation the vent termination hood 
    will be hot (see Figure 16).
    A Safety cover (see Figure 17) is available to prevent 
    accidental contact with the vent terminal. Contact your 
    Customer Service Department for ordering information.
    Figure 17 
    Alternatively, a wire mesh or louvered fencing guard can 
    be built around the termination as shown in Figure 18.
    Figure 18 
     VENT  CONNECTIONS
    After the location for the vent terminal has been selected 
    as outlined in Figure 6 & Figure 15, use the following 
    illustrations for installation:
     LOCATING CLEARANCE HOLE FOR VENT
    Cut a clearance hole, approximately  7”  in diameter, through 
    the exterior wall for the vent assembly. The recommended 
    height is  64”  for  40 gal.  models,  73”  for  50 gal.  models 
    and  74”  for  50 gal.  Hi-Input models, as measured from 
    the hole center to bottom of water heater. Where the 
    wall is combustible and the wall thickness is over  14” ,  1”  
    clearance to combustible surfaces around the vent terminal 
    is needed. The fi rst  14”  is zero clearance (see Figure 21).
     STANDARD  VENT  ARRANGEMENT
    * If the horizontal length of the venting is less than  30”  
    the restricter plate must be installed (see Figure 22, Figure 
    28 thru Figure 30).
    • Do not use the restricter plate in an offset installation 
    (see Figure 26).
    • Do not use the restricter plate the horizontal length of 
    the venting is greater than  30” .
    Note: The length of “unstretched” corrugated tube could 
    cause the length of the vent run to exceed the minimum. In 
    this case cut off a piece of the corrugated tube to achieve 
    the  17”  minimum vent length.    
    						
    							24 www.  
     
    americanwaterheater  
     
    .com  
     VENT  ASSEMBLY
    The vent piping and the vent termination hood are to be 
    connected as shown in Figure 20.
    Maintain vent clearances to combustibles as shown in 
    Figure 21.
    Depending on your access to where the vent termination 
    passes through the wall, you may wish to connect the 
    piping and vent termination hood together fi rst.
    Inside the vent piping there are springs that hold the two 
    corrugated pipes in position. When the pipes are stretched 
    to the required length, the springs will remain properly 
    spaced.
    To connect the vent piping to the vent termination hood, 
    fi rst slide the inner (3”) corrugated pipe over the inner vent 
    termination pipe. Continue this action until the locking 
    clip on the corrugated pipe snaps into position in the 
    corresponding groove (see Figure 19). Secure corrugated 
    pipe with screw (supplied) inserted through hole opposite 
    the locking clip.
    Repeat this process with the outer (6”) corrugated pipe and 
    lock it into position on the outer pipe on the vent termination 
    (see Figure 19). Secure corrugated pipe with screw 
    (supplied) inserted through hole opposite the locking clip.
    Note: To reduce the friction between the corrugated pipe 
    and the O-rings, it is recommended to dampen the O-rings 
    with water.
    The completed connection is shown in Figure 20.
    INNER 
    CORRUGATED PIPEINNER VENT 
    TERMINATION PIPEOUTER VENT 
    TERMINATION PIPE
    O-RING OUTER 
    CORRUGATED 
    PIPE
    LOCKING CLIP 
    GROOVE LOCKING 
    CLIP
    Figure 19 
    SCREW
    Figure 20 
     SECURING VENT TERMINATION ASSEMBLY TO 
    THE EXTERIOR WALL
    Some models are supplied with trim plates which may 
    be used to cover the holes in the wall (see Figure 1 and 
    Figure 21). Slide one trim plate (if supplied) over the outer 
    corrugated tube, then insert the outer corrugated tube 
    through the clearance hole from exterior wall. Secure 
    the trim plate to the exterior wall, then secure the vent 
    terminal to the exterior wall with 4 screw anchors (included) 
    appropriate for the type of wall construction. Caulk the 
    junction of the vent terminal base plate and the exterior 
    wall with exterior type sealant (not included). Slide the trim 
    plate (inside) over the outer corrugated tube and fasten the 
    trim plate to the interior wall. Caulk the junction of the outer 
    corrugated tube and the trim plate (inside) with suitable 
    sealant. The vent termination hood attaches to the vent 
    piping as shown in Figure 20.
    TRIM PLATE 
    (INSIDE)TRIM PLATE 
    (OUTSIDE)
    APPLY 
    SEALANT SPRING
    CUTAWAY TO 
    SHOW SPRING 
    PLACEMENT
    APPLY 
    SEALANT
      14”  ZERO 
    CLEARANCE  1”  
    CLEARANCE
    Figure 21 
     VENT RESTRICTER PLATE
    The vent restricter plate (see Figure 22) is required for 
    short horizontal runs on low vent installations (see Figure 
    29) and high vent installations (see Figure 30).
    For short horizontal vent runs (see Figure 29) place the 
    restricter plate over the fl  ue tube reducer before connecting 
    the inner corrugated tube to the fl ue tube reducer. DO 
    NOT use the restricter plate if the horizontal run is greater 
    than  30” .
    For high vertical runs use the restricter plate only when 
    the vertical run of the venting above the heater is greater 
    than  48”  (see Figure 30).
    UPPER AIR 
    INLET BOX FLUE TUBE 
    REDUCER
    RESTRICTER 
    PLATE
    Figure 22 
     UNCOMPRESSING THE CORRUGATED TUBING
    1.  Pull the inner corrugated tube towards the water heater 
    and leave some length over the water heater’s center 
    for bending (see Figure 23).
    2.  Pull the outer corrugated tube toward the water heater 
    and leave it  2”  shorter than the inner corrugated tube.
    3.  Make sure there are two springs evenly spaced at the 
    bend in the tube.
    4.  Use metal hangers to keep venting level or with a 
    slope upward from the heater to terminal.     
    						
    							   www.  
     
    americanwaterheater  
     
    .com 25
    INNER 
    CORRUGATED 
    PIPEOUTER 
    CORRUGATED PIPE
    RESTRICTER 
    PLATEFLUE TUBE 
    REDUCER
    APPLY 
    SILICONE
    Figure 23 
     VENT CONNECTION TO THE WATER HEATER
    Bend both the corrugated pipes toward the fl ue connection 
    on the water heater. Pull and connect the inner corrugated 
    pipe to the water heater’s fl ue tube reducer with hi-temp 
    red silicone (included) and gear clamp. Make sure this 
    connection is tight and leak proof (see Figure 24).
    *The sealant between the inner corrugated pipe and water 
    heater’s fl ue tube reducer must be hi-temp red silicone 
    or other material suitable for  600°F  continuous service.
    Note: If you are using the vent restricter plate, the inner 
    vent pipe is to go over the side legs and down the stops.
    SMOOTH, 
    EASY CURVE
    GEAR 
    CLAMP
    CUTAWAY TO 
    SHOW DETAILS
    RESTRICTER 
    PLATE STOP
    Figure 24 
    Apply hi-temp red silicone (included) around the collar on 
    air manifold box. Pull the outer corrugated pipe all the way 
    on to collar and secure with the gear clamp. Pull the free 
    end of the corrugated pipe past the gear clamp and secure 
    with one sheet metal screw (see Figure 25).
    GEAR 
    CLAMP
    APPLY 
    SILICONE 
    TO AIRBOX 
    BEFORE 
    ATTACHING 
    PIPING
    SECURE 
    WITH A 
    SHEET METAL 
    SCREW
    SMOOTH, 
    EASY CURVE
    Figure 25 
     OFFSET  VENT  ARRANGEMENT
    Where a straight vent arrangement is impossible, a 
    horizontal 90° maximum bend can be made. Use the 
    water heater casing outer diameter as a template to form 
    the corrugated tube.
    SMOOTH, 
    EASY CURVE
    90° 
    MAXIMUM 
    BEND
    Figure 26 
    Figure 27 
    Note: To ensure good exhaust gas fl ow, bend vent piping 
    using a smooth, easy curve as shown in Figure 24 thru 
    Figure 26. Do not use reverse or compound curves as 
    shown in Figure 27.       
    						
    							26 www.  
     
    americanwaterheater  
     
    .com  
    ABOVE 
    ANTICIPATED 
    SNOW 
    LEVEL OR 
      12”  ABOVE 
    GRADE
    A
    B
    Low Vent installation
    7
    6
    8
    1
    C
    519
    Figure 28 
    DIM. 4038 5040 5047
    A 80”  MAX.
    B 9”  MIN.
    C 
    (RECOMMENDED)  63.63”  73.00”  74.00” 
    C 
    (MINIMUM)  60.75  69.50  70.50 
    D 14.25”  MIN.
    NOTE: Dimension “C” is the height above to fl oor to the center of the 
    termination hole through the exterior wall.
    D
    4
    Minimum Vent installation
    C
    ABOVE 
    ANTICIPATED 
    SNOW 
    LEVEL OR 
      12”  ABOVE 
    GRADE3
      9” 
    Figure 29 
     
    12”  MIN. 
    BELOW 
    SOFFIT
      72”  
    MAX.
    6
    2
    High Vent installation
    51
    1
      17”  
    MIN.
    Figure 30 
    NOTES: (applies to Figure 28 thru Figure 30)
    1.  In any installation the total of dimension “A” plus 
    dimension “B” must not exceed  89” .
    2.  This heater can be installed with  0”  clearance to a wall.
    3.  Minimum vent pipe clearance to combustibles is  1”  
    (see Figure 21).
    4.  Minimum distance from center of heater to wall is 
      14.25” .
    5.  Dimension “A” includes wall thickness.
    6.  Hole diameter in wall is  7” .
    7.  Venting must slope up away from the heater a 
    minimum of  0.25” per foot  of length to prevent 
    condensation from collecting and to provide 
    suffi cient draft.
    8.  Distance above horizontal at full extension is  2” .
    9.  Use support stays to hold the venting to avoid sags 
    or valleys.    
    						
    							   www.  
     
    americanwaterheater  
     
    .com 27
     INSTALLATION  CHECKLIST
    Note: Use and complete this checklist before lighting the 
    heater. Correct any conditions that do not meet these 
    instructions.
     Water Heater Location
      Centrally located with the water piping system. 
    Located as close to gas piping and vent pipe system 
    as possible.
      Located indoors and in a vertical position. Protected 
    from freezing temperatures.
      Proper clearances from combustible surfaces 
    maintained and not installed directly on a carpeted 
    floor.
      Provisions made to protect the area from water 
    damage. Metal drain pan installed and piped to an 
    adequate drain.
      Installation area free of corrosive elements, flammable 
    material and flammable vapo r emitting products.
      Sufficient room to service the water heater.
     Gas Supply and Piping
      Gas supply is the same type as listed on the water 
    heater data plate.
      Gas line equipped with shut-off valve, union and 
    sediment trap.
      Adequate pipe size and of approved material.
      Approved pipe joint compound or tape used.
      Chloride-free soap and water solution or other 
    approved means used to check all connections and 
    fittings for possible gas leaks.
     Vent Pipe System
      Evenly stretched out between water heater and vent 
    termination hood.
      Smooth bend with adequate support to prevent 
    sagging,  0.25” per foot .
      Inside pipe (3”) and outside pipe (6”) securely 
    fastened to vent termination hood.
      Vent restricter plate installed on heater flue outlet as 
    applicable.
      Inside pipe (3”) and outside pipe (6”) securely fastened 
    to water heater with silicone and gear clamps.
      Not obstructed in any way. Vent Termination Hood
      Securely fastened to exterior wall.
      Above anticipated snow level or  12”  above grade.
      Proper clearances from windows, doors, corners, 
    other vent openings etc.
      Area around vent termination hood clear and 
    unobstructed.
      No flammable vapo r emitting products stored nearby.
      Safety covers in place (when applicable).
     Water System Piping
      Temperature-Pressure relief valve properly installed 
    with a discharge line run to an open drain and 
    protected from freezing.
      All piping properly installed and free of leaks.
      Heater completely filled with water.
      Closed system pressure build-up precautions installed.
      Mixing valve installed (when applicable).
    After all actions on checklist are checked/
    completed, read the Lighting Instructions and 
    proceed with lighting the heater. 
    						
    							28 www.  
     
    americanwaterheater  
     
    .com  
     
    LIGHTING INSTRUCTIONS
    1.  Turn the gas control/temperature knob counterclockwise        to the OFF position. The status light will stop 
    blinking and stay on for a short time after the water heater is turned off. See Figure ‘A’.
    329352-000
    TO TURN OFF GAS TO APPLIANCE
    1.  STOP! It is imperative that you read all safety warnings before lighting the pilot.
    2.  Turn the gas control/temperature knob counterclockwise        to the OFF position.
    3.  Wait ten (10) minutes to clear out any gas. If you then smell gas,  STOP! Follow “ B” in the safety 
    information above on this label. If you do not smell gas, go to  the next step.
    4.  Turn the gas control/temperature knob clockwise        to “PILOT”. See Figure ‘B’.
    5.  Press the gas control/temperature knob all the way in and hold it in. The knob should travel in about 1/4 inch if 
    it is set to PILOT correctly. While holding the gas control/temperature knob in, click the igniter button 
    continuously (about once a second) for up to 90 seconds or until status light begins to blink. The pilot flame 
    should envelop the thermopile. See Figure ‘D’.
    6.  When the status light starts blinking, release the gas control/temperature knob. Set the gas 
    control/temperature knob to the desired setting. See Figure ‘C’.
      • If the status light does not start blinking within 90 seconds, repeat steps 2 through 5 up to THREE (3) times, 
    waiting 10 minutes between lighting attempts.
      • The circuitry in this advanced gas valve requires that you wait 10 minutes between lighting attempts.
      • If the status light turns a solid color, release the gas control/temperature knob and repeat steps 2 through 5 
    (waiting 10 minutes before attempting to relight the pilot). If the status light does not start blinking after 
    three lighting attempts, turn the gas control/temperature knob to the OFF position and call a qualified 
    service technician or your gas supplier.
    DANGER: Hotter water increases the risk of scald injury. Consult the instruction manual before 
    changing the temperature setting.
      Refer to the Lighting Instructions in the Installation Manual for more detailed troubleshooting information.
    DANGER:
    FIGURE  D
    Main Burner
    Thermopile Pilot FlameFIGURE  A
    OFF POSITIONFIGURE  B
    PILOT POSITIONFIGURE  C
    ON POSITION
    120°F
    Mark120°F
    Mark
    CONTROL KNOB
    120°F
    Mark
    GAS CONTROL
    Gas Control & 
    Temperature Knob
    Status
    Light
    Igniter
    Button
    LIGHTING INSTRUCTIONS
    A.  This appliance has a pilot which is lit by a piezoelectric spark gas ignition system. Do not open the inner door 
    of the appliance and try to light the pilot by hand.
    B.  BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because 
    some gas is heavier than air and will settle on the floor.
    WHAT TO DO IF YOU SMELL GAS
      • Do not try to light any appliance.
      • Do not touch any electric switch; do not use any phone in your building.
      • Immediately call your gas supplier from a neighbors phone. Follow the gas suppliers instructions.
      • If you cannot reach your gas supplier, call the fire department.
    C.  Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or 
    turn by hand, dont try to repair it, call a qualified service technician. Force or attempted repair may result in a 
    fire or explosion.
    D.  Do not use this appliance if any part has been under water. Immediately contact a qualified installer or service 
    agency to replace a flooded water heater. Do not attempt to repair the unit! It must be replaced!
    BEFORE LIGHTING: ENTIRE SYSTEM MUST BE FILLED 
    WITH WATER AND AIR PURGED FROM ALL LINESFLAMMABLE
    WARNING: If you do not follow these instructions exactly, a fire or explosion may 
    result causing property damage, personal injury or loss of life.
    FOR YOUR SAFETY READ BEFORE LIGHTING
      
    						
    							   www.  
     
    americanwaterheater  
     
    .com 29
    TEMPERATURE REGULATION
     TEMPERATURE  REGULATION
     
     Temperature  Adjustment
    Valves for reducing the point-of-use temperature by mixing 
    cold and hot water are available (see Figure 8). Also 
    available are inexpensive devices that attach to faucets to 
    limit hot water temperatures. Contact a licensed plumber 
    or the local plumbing authority.
    Note: During low demand periods, a lower thermostat 
    setting will reduce energy losses and may satisfy your 
    normal hot water needs. If hot water use is expected to 
    be more than normal, a higher thermostat setting may be 
    required to meet the increased demand. When leaving 
    your home for extended periods (e.g., vacations etc.) turn 
    the temperature dial to its lowest setting. This will maintain 
    the water at low temperatures with minimum energy losses 
    and prevent the tank from freezing during cold weather.
    GAS CONTROL VALVE/THERMOSTAT 
    SETTINGS
    GAS CONTROL/
    TEMPERATURE KNOB
    STATUS 
    LIGHT
    IGNITER120°F 
    MARK130°F 
    MARK155°F 
    MARK 150°F 
    MARK 140°F 
    MARK
    91°F 
    MARK
     
    Figure 31 
    The thermostat is adjusted to the “OFF” position when 
    it is shipped from the factory. Water temperature can be 
    regulated by moving the temperature dial to the preferred 
    setting. The preferred starting point is  120°F  at the “HOT” 
    setting. Align the knob with the desired water temperature 
    as shown in Figure 31. There is a hot water scald potential 
    if the thermostat is set too high.
    Note: Temperatures shown on the gas control valve/
    thermostat are approximates. The actual temperature of 
    the heated water may vary.
    Important: Adjusting the thermostat past the  120°F  mark 
    on the temperature dial will increase the risk of scald injury. 
    Hot water can produce fi rst degree burns within:
    Water 
    Temperature 
      °F Time for 1st
    Degree Burns
    (Less Severe Burns)Time for Permanent 
    Burns 2nd & 3rd 
    Degree (Most 
    Severe Burns)
      110  (normal shower temp.)
      116 (pain threshold)
      116  35 minutes 45 minutes
      122  1 minute 5 minutes
      131  5 seconds 25 seconds
      140  2 seconds 5 seconds
      149  1 second 2 seconds
      154 instantaneous 1 seconds
    (U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, 
    Sept. 15,1978)
    Table 2
    Should overheating occur or the gas supply fail to shut off, 
    turn “OFF” the manual gas shut-off valve to the appliance 
    (see Figure 1, item 18).
       OPERATING THE TEMPERATURE CONTROL 
    SYSTEM
     Water  Temperature  Adjustment
    The water temperature setting can be adjusted from  91°F  
    to  155°F . Turn the Gas Control Valve/Temperature Knob 
    to the desired setting/temperature.
    Note: The temperatures indicated are approximates. The 
    actual temperature of the heated water may vary.
     Operating Modes And Settings
    Standard Mode - The controller adjusts the water heater 
    to maintain the temperature set by the user.
    Setting for vacation - The “LOW” position sets the controller 
    at approximately  91°F . This setting is recommended for 
    times when the water heater will not be in use for an 
    extended period of time. It effectively turns the controller 
    temperature setting down to a temperature that prevents 
    the water in the water heater from freezing while still 
    conserving energy.  
    						
    							30 www.  
     
    americanwaterheater  
     
    .com  
    FOR YOUR INFORMATION
     EXTERNAL  DAMAGE
    Do not operate the water heater until it has been fully 
    checked out by a qualifi ed technician, if the water heater:
    • Has been exposed to fi re or damage.
    • Displays evidence of sooting.
    • Produces steam or unusually hot water.
    If the water heater has been fl ooded it must be replaced.
     START UP CONDITIONS
    NEVER OPERATE THE HEATER WITHOUT FIRST 
    BEING CERTAIN IT IS FILLED WITH WATER AND A 
    TEMPERATURE AND PRESSURE RELIEF VALVE IS 
    INSTALLED IN THE RELIEF VALVE OPENING OF THE 
    HEATER. DO NOT ATTEMPT TO OPERATE HEATER 
    WITH COLD WATER INLET VALVE CLOSED.
       Condensate
    Whenever the water heater is fi lled with cold water, some 
    condensate will form while the burner is on. A water 
    heater may appear to be leaking when in fact the water is 
    condensate. This usually happens when:
    a.  A new water heater is fi lled with cold water for the 
    fi rst time.
    b.  Burning gas produces water vapo r in water heaters, 
    particularly high efficiency models where flue 
    temperatures are lower.
    c.  Large amounts of hot water are used in a short time 
    and the refi ll water in the tank is very cold.
    Moisture from the products of combustion condense on 
    the cooler tank surfaces and form drops of water which 
    may fall onto the burner or other hot surfaces to produce 
    a “sizzling” or “frying” noise.
    Because of the suddenness and amount of water, 
    condensate water may be diagnosed as a “tank leak”. 
    After the water in the tank warms up (about 1-2 hours), 
    the condition should disappear.
    Do not assume the water heater is leaking until there has 
    been enough time for the water in the tank to warm up.
    An undersized water heater will cause more condensation. 
    The water heater must be sized properly to meet the 
    family’s demands for hot water including dishwashers, 
    washing machines and shower heads.
    Excessive condensate may be noticed during the 
    winter and early spring months when incoming water 
    temperatures are at their lowest.
    Good venting is essential for a gas fi red water heater 
    to operate properly as well as to carry away products of 
    combustion and water vapo r.
     Smoke/Odo r
    It is not uncommon to experience a small amount of smoke 
    and odo r during the initial start-up. This is due to burning off 
    of oil from metal parts, and will disappear in a short while.
     THERMAL  EXPANSION
    Water supply systems may, because of such events as 
    high line pressure, frequent cut-offs, the effects of water 
    hammer among others, have installed devices such 
    as pressure reducing valves, check valves, back fl ow 
    preventers, etc. to control these types of problems. When 
    these devices are not equipped with an internal by-pass, 
    and no other measures are taken, the devices cause the 
    water system to be closed. As water is heated, it expands 
    (thermal expansion) and closed systems do not allow for 
    the expansion of heated water.
    As water is heated, it expands (thermal expansion). As the 
    volume of water increases, there will be a corresponding 
    increase in water pressure due to thermal expansion. 
    Thermal expansion can cause premature tank failure 
    (leakage). This type of failure is not covered under the 
    limited warranty. Thermal expansion can also cause 
    intermittent temperature-pressure relief valve operation: 
    water discharged from the valve due to excessive pressure 
    build up. The temperature-pressure relief valve is not 
    intended for the constant relief of thermal expansion. This 
    condition is not covered under the limited warranty.
    A properly-sized thermal expansion tank should be 
    installed on all closed systems to control the harmful 
    effects of thermal expansion. Contact a plumbing service 
    agency or your retail supplier regarding the installation of 
    a thermal expansion tank.  
    						
    All American Water Heater manuals Comments (0)

    Related Manuals for American Water Heater 40 Gallon 38000 BTU Direct Vent Natural Gas Water Heater DVG6240S38NOV user manual