Home
>
American Water Heater
>
Gas Heater
>
American Water Heater 40 Gallon 38000 BTU Direct Vent Natural Gas Water Heater DVG6240S38NOV user manual
American Water Heater 40 Gallon 38000 BTU Direct Vent Natural Gas Water Heater DVG6240S38NOV user manual
Have a look at the manual American Water Heater 40 Gallon 38000 BTU Direct Vent Natural Gas Water Heater DVG6240S38NOV user manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
www. americanwaterheater .com 21 CERTIFIED GAS SUPPLY FLEX PIPE (PROPERLY SIZED FOR THE HEATER INPUT RATE) SEDIMENT TRAPGAS CONTROL VA LV E GROUND JOINT UNION (OPTIONAL) CAP 3” MIN. Figure 13 BLACK PIPE SEDIMENT TRAPGAS CONTROL VA LV E GROUND JOINT UNION (OPTIONAL) CAP 3” MIN. Figure 14 SEDIMENT TRAP • Contaminants in gas lines can cause fire or explosion. • Clean all gas piping before installation. • Install sediment trap in accor- dance with NFPA54.Fire and Explosion Hazard WARNING A sediment trap should be installed as close to the inlet of the water heater as practical at the time of water heater installation. The sediment trap should be either a tee fi tting with a capped nipple in the bottom outlet or other device recognized as an effective sediment trap. If a tee fi tting is used, it should be installed in conformance with one of the methods of installation shown in Figure 13 & Figure 14. Contaminants in the gas lines may cause improper operation of the gas control valve/thermostat that may result in fi re or explosion. Before attaching the gas line be sure that all gas pipe is clean on the inside. To trap any dirt or foreign material in the gas supply line, a sediment trap (sometimes called a dirt leg) must be incorporated in the piping. The sediment trap must be readily accessible. Install in accordance with the “Gas Piping” section. Refer to the current edition of the “National Fuel Gas Code” (ANSI Z223.1/NFPA 54) . HIGH ALTITUDE INSTALLATIONS Installations above 7,700’ . require replacement of the burner orifi ce in accordance with the current edition of the “National Fuel Gas Code” (ANSI Z223.1/NFPA 54). Failure to replace the orifi ce could result in improper and ineffi cient operation of the appliance, producing carbon monoxide gas in excess of safe limits, which could result in serious personal injury or death. Contact your gas supplier for any specifi c changes which may be required in your area. Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. • High altitude orifice must be installed for operation above 7,700 ft. • Contact a qualified installer or service agency. Breathing Hazard - Carbon Monoxide Gas WARNING
22 www. americanwaterheater .com VENTING This direct vent water heater uses a sealed venting system to supply fresh combustion air to the heater and to exhaust the products of combustion (fl ue gases) to the outdoors. The venting is a “pipe in a pipe” system. The inner (3”) piping carries out the exhaust fl ue gases while the outer (6”) piping carries in fresh combustion air. The corrugated end of the vent piping connects to the top of the water heater and the opposite end connects to the vent termination hood which will be mounted on the exterior wall (see Figure 16). Figure 16 shows the hot exhaust gas exit and the location of the combustion air intake. Figure 19 thru Figure 26 show how to assemble and connect the venting system. Figure 28 thru Figure 30 show various installation options. DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPO RS AND LIQUIDS IN THE VICINITY OF THE VENT TERMINATION HOOD. NEVER OPERATE THE WATER HEATER UNLESS IT IS VENTED TO THE OUTDOORS AND HAS ADEQUATE AIR SUPPLY TO AVOID RISKS OF IMPROPER OPERATION, FIRE, EXPLOSION OR ASPHYXIATION. DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATING AIR. ADEQUATE AIR FOR COMBUSTION AND VENTILATION MUST BE PROVIDED FOR SAFE OPERATION. **Minimum 12 in. Minimum 12 in. above grade or anticipated snow level Minimum 12 in. under veranda, porch, deck or balcony (see footnote 1) Minimum 3 ft. above if within 10 ft. horizontally to a mechanical air supply inlet Minimum 9 in. to a non mechanical air supply inlet into building or combustion air inlet to another appliance Minimum 12 in. from soffit *Minimum 9 in. to a window or door that may be opened **Minimum 18 in. from outside corner 1. Permitted only if veranda, porch, deck or balcony is fully opened on a minimum of two sides beneath the floor. 2. A vent shall not terminate above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings. AREA WHERE TERMINAL IS NOT PERMITTED VENT TERMINAL AIR SUPPLY INLETMinimum 3 ft. clearance to a service regulator vent outlet** Or as required by local authorities. Figure 15 Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. • Install vent system In accordance with codes. • Do not operate water heater if flood damaged. • Install water heater in accordance with the instruction manual. • Do not operate if soot buildup is present. • Do not obstruct water heater air intake. • Do not place chemical vapor emitting products near water heater or vent terminal hood. • Gas and carbon monoxide detectors are available. • Never operate the heater unless it is vented to the outdoors and has adequate air supply to avoid risks of improper operation, fire, explosion or asphyxia- tion. • Analyze the entire vent system to make sure that condensate will not become trapped in a section of vent pipe and therefore reduce the open cross sectional area of the vent. • Chemical corrosion of flue and vent system can cause serious injury or death. Breathing Hazard - Carbon Monoxide Gas WARNING VENT TERMINAL CLEARANCES The vent system must terminate so that proper clearances are maintained as cited in local codes or the current edition of the “National Fuel Gas Code”, ANSI Z223.1/NFPA 54 as follows:
www. americanwaterheater .com 23 FRESH COMBUSTION AIR IN HOT EXHAUST GAS OUT SCREW Figure 16 Be sure venting is properly connected to prevent escape of dangerous flue gases which could cause deadly asphyxiation. DV TERMINATION SAFETY COVER When the heater is in operation the vent termination hood will be hot (see Figure 16). A Safety cover (see Figure 17) is available to prevent accidental contact with the vent terminal. Contact your Customer Service Department for ordering information. Figure 17 Alternatively, a wire mesh or louvered fencing guard can be built around the termination as shown in Figure 18. Figure 18 VENT CONNECTIONS After the location for the vent terminal has been selected as outlined in Figure 6 & Figure 15, use the following illustrations for installation: LOCATING CLEARANCE HOLE FOR VENT Cut a clearance hole, approximately 7” in diameter, through the exterior wall for the vent assembly. The recommended height is 64” for 40 gal. models, 73” for 50 gal. models and 74” for 50 gal. Hi-Input models, as measured from the hole center to bottom of water heater. Where the wall is combustible and the wall thickness is over 14” , 1” clearance to combustible surfaces around the vent terminal is needed. The fi rst 14” is zero clearance (see Figure 21). STANDARD VENT ARRANGEMENT * If the horizontal length of the venting is less than 30” the restricter plate must be installed (see Figure 22, Figure 28 thru Figure 30). • Do not use the restricter plate in an offset installation (see Figure 26). • Do not use the restricter plate the horizontal length of the venting is greater than 30” . Note: The length of “unstretched” corrugated tube could cause the length of the vent run to exceed the minimum. In this case cut off a piece of the corrugated tube to achieve the 17” minimum vent length.
24 www. americanwaterheater .com VENT ASSEMBLY The vent piping and the vent termination hood are to be connected as shown in Figure 20. Maintain vent clearances to combustibles as shown in Figure 21. Depending on your access to where the vent termination passes through the wall, you may wish to connect the piping and vent termination hood together fi rst. Inside the vent piping there are springs that hold the two corrugated pipes in position. When the pipes are stretched to the required length, the springs will remain properly spaced. To connect the vent piping to the vent termination hood, fi rst slide the inner (3”) corrugated pipe over the inner vent termination pipe. Continue this action until the locking clip on the corrugated pipe snaps into position in the corresponding groove (see Figure 19). Secure corrugated pipe with screw (supplied) inserted through hole opposite the locking clip. Repeat this process with the outer (6”) corrugated pipe and lock it into position on the outer pipe on the vent termination (see Figure 19). Secure corrugated pipe with screw (supplied) inserted through hole opposite the locking clip. Note: To reduce the friction between the corrugated pipe and the O-rings, it is recommended to dampen the O-rings with water. The completed connection is shown in Figure 20. INNER CORRUGATED PIPEINNER VENT TERMINATION PIPEOUTER VENT TERMINATION PIPE O-RING OUTER CORRUGATED PIPE LOCKING CLIP GROOVE LOCKING CLIP Figure 19 SCREW Figure 20 SECURING VENT TERMINATION ASSEMBLY TO THE EXTERIOR WALL Some models are supplied with trim plates which may be used to cover the holes in the wall (see Figure 1 and Figure 21). Slide one trim plate (if supplied) over the outer corrugated tube, then insert the outer corrugated tube through the clearance hole from exterior wall. Secure the trim plate to the exterior wall, then secure the vent terminal to the exterior wall with 4 screw anchors (included) appropriate for the type of wall construction. Caulk the junction of the vent terminal base plate and the exterior wall with exterior type sealant (not included). Slide the trim plate (inside) over the outer corrugated tube and fasten the trim plate to the interior wall. Caulk the junction of the outer corrugated tube and the trim plate (inside) with suitable sealant. The vent termination hood attaches to the vent piping as shown in Figure 20. TRIM PLATE (INSIDE)TRIM PLATE (OUTSIDE) APPLY SEALANT SPRING CUTAWAY TO SHOW SPRING PLACEMENT APPLY SEALANT 14” ZERO CLEARANCE 1” CLEARANCE Figure 21 VENT RESTRICTER PLATE The vent restricter plate (see Figure 22) is required for short horizontal runs on low vent installations (see Figure 29) and high vent installations (see Figure 30). For short horizontal vent runs (see Figure 29) place the restricter plate over the fl ue tube reducer before connecting the inner corrugated tube to the fl ue tube reducer. DO NOT use the restricter plate if the horizontal run is greater than 30” . For high vertical runs use the restricter plate only when the vertical run of the venting above the heater is greater than 48” (see Figure 30). UPPER AIR INLET BOX FLUE TUBE REDUCER RESTRICTER PLATE Figure 22 UNCOMPRESSING THE CORRUGATED TUBING 1. Pull the inner corrugated tube towards the water heater and leave some length over the water heater’s center for bending (see Figure 23). 2. Pull the outer corrugated tube toward the water heater and leave it 2” shorter than the inner corrugated tube. 3. Make sure there are two springs evenly spaced at the bend in the tube. 4. Use metal hangers to keep venting level or with a slope upward from the heater to terminal.
www. americanwaterheater .com 25 INNER CORRUGATED PIPEOUTER CORRUGATED PIPE RESTRICTER PLATEFLUE TUBE REDUCER APPLY SILICONE Figure 23 VENT CONNECTION TO THE WATER HEATER Bend both the corrugated pipes toward the fl ue connection on the water heater. Pull and connect the inner corrugated pipe to the water heater’s fl ue tube reducer with hi-temp red silicone (included) and gear clamp. Make sure this connection is tight and leak proof (see Figure 24). *The sealant between the inner corrugated pipe and water heater’s fl ue tube reducer must be hi-temp red silicone or other material suitable for 600°F continuous service. Note: If you are using the vent restricter plate, the inner vent pipe is to go over the side legs and down the stops. SMOOTH, EASY CURVE GEAR CLAMP CUTAWAY TO SHOW DETAILS RESTRICTER PLATE STOP Figure 24 Apply hi-temp red silicone (included) around the collar on air manifold box. Pull the outer corrugated pipe all the way on to collar and secure with the gear clamp. Pull the free end of the corrugated pipe past the gear clamp and secure with one sheet metal screw (see Figure 25). GEAR CLAMP APPLY SILICONE TO AIRBOX BEFORE ATTACHING PIPING SECURE WITH A SHEET METAL SCREW SMOOTH, EASY CURVE Figure 25 OFFSET VENT ARRANGEMENT Where a straight vent arrangement is impossible, a horizontal 90° maximum bend can be made. Use the water heater casing outer diameter as a template to form the corrugated tube. SMOOTH, EASY CURVE 90° MAXIMUM BEND Figure 26 Figure 27 Note: To ensure good exhaust gas fl ow, bend vent piping using a smooth, easy curve as shown in Figure 24 thru Figure 26. Do not use reverse or compound curves as shown in Figure 27.
26 www. americanwaterheater .com ABOVE ANTICIPATED SNOW LEVEL OR 12” ABOVE GRADE A B Low Vent installation 7 6 8 1 C 519 Figure 28 DIM. 4038 5040 5047 A 80” MAX. B 9” MIN. C (RECOMMENDED) 63.63” 73.00” 74.00” C (MINIMUM) 60.75 69.50 70.50 D 14.25” MIN. NOTE: Dimension “C” is the height above to fl oor to the center of the termination hole through the exterior wall. D 4 Minimum Vent installation C ABOVE ANTICIPATED SNOW LEVEL OR 12” ABOVE GRADE3 9” Figure 29 12” MIN. BELOW SOFFIT 72” MAX. 6 2 High Vent installation 51 1 17” MIN. Figure 30 NOTES: (applies to Figure 28 thru Figure 30) 1. In any installation the total of dimension “A” plus dimension “B” must not exceed 89” . 2. This heater can be installed with 0” clearance to a wall. 3. Minimum vent pipe clearance to combustibles is 1” (see Figure 21). 4. Minimum distance from center of heater to wall is 14.25” . 5. Dimension “A” includes wall thickness. 6. Hole diameter in wall is 7” . 7. Venting must slope up away from the heater a minimum of 0.25” per foot of length to prevent condensation from collecting and to provide suffi cient draft. 8. Distance above horizontal at full extension is 2” . 9. Use support stays to hold the venting to avoid sags or valleys.
www. americanwaterheater .com 27 INSTALLATION CHECKLIST Note: Use and complete this checklist before lighting the heater. Correct any conditions that do not meet these instructions. Water Heater Location Centrally located with the water piping system. Located as close to gas piping and vent pipe system as possible. Located indoors and in a vertical position. Protected from freezing temperatures. Proper clearances from combustible surfaces maintained and not installed directly on a carpeted floor. Provisions made to protect the area from water damage. Metal drain pan installed and piped to an adequate drain. Installation area free of corrosive elements, flammable material and flammable vapo r emitting products. Sufficient room to service the water heater. Gas Supply and Piping Gas supply is the same type as listed on the water heater data plate. Gas line equipped with shut-off valve, union and sediment trap. Adequate pipe size and of approved material. Approved pipe joint compound or tape used. Chloride-free soap and water solution or other approved means used to check all connections and fittings for possible gas leaks. Vent Pipe System Evenly stretched out between water heater and vent termination hood. Smooth bend with adequate support to prevent sagging, 0.25” per foot . Inside pipe (3”) and outside pipe (6”) securely fastened to vent termination hood. Vent restricter plate installed on heater flue outlet as applicable. Inside pipe (3”) and outside pipe (6”) securely fastened to water heater with silicone and gear clamps. Not obstructed in any way. Vent Termination Hood Securely fastened to exterior wall. Above anticipated snow level or 12” above grade. Proper clearances from windows, doors, corners, other vent openings etc. Area around vent termination hood clear and unobstructed. No flammable vapo r emitting products stored nearby. Safety covers in place (when applicable). Water System Piping Temperature-Pressure relief valve properly installed with a discharge line run to an open drain and protected from freezing. All piping properly installed and free of leaks. Heater completely filled with water. Closed system pressure build-up precautions installed. Mixing valve installed (when applicable). After all actions on checklist are checked/ completed, read the Lighting Instructions and proceed with lighting the heater.
28 www. americanwaterheater .com LIGHTING INSTRUCTIONS 1. Turn the gas control/temperature knob counterclockwise to the OFF position. The status light will stop blinking and stay on for a short time after the water heater is turned off. See Figure ‘A’. 329352-000 TO TURN OFF GAS TO APPLIANCE 1. STOP! It is imperative that you read all safety warnings before lighting the pilot. 2. Turn the gas control/temperature knob counterclockwise to the OFF position. 3. Wait ten (10) minutes to clear out any gas. If you then smell gas, STOP! Follow “ B” in the safety information above on this label. If you do not smell gas, go to the next step. 4. Turn the gas control/temperature knob clockwise to “PILOT”. See Figure ‘B’. 5. Press the gas control/temperature knob all the way in and hold it in. The knob should travel in about 1/4 inch if it is set to PILOT correctly. While holding the gas control/temperature knob in, click the igniter button continuously (about once a second) for up to 90 seconds or until status light begins to blink. The pilot flame should envelop the thermopile. See Figure ‘D’. 6. When the status light starts blinking, release the gas control/temperature knob. Set the gas control/temperature knob to the desired setting. See Figure ‘C’. • If the status light does not start blinking within 90 seconds, repeat steps 2 through 5 up to THREE (3) times, waiting 10 minutes between lighting attempts. • The circuitry in this advanced gas valve requires that you wait 10 minutes between lighting attempts. • If the status light turns a solid color, release the gas control/temperature knob and repeat steps 2 through 5 (waiting 10 minutes before attempting to relight the pilot). If the status light does not start blinking after three lighting attempts, turn the gas control/temperature knob to the OFF position and call a qualified service technician or your gas supplier. DANGER: Hotter water increases the risk of scald injury. Consult the instruction manual before changing the temperature setting. Refer to the Lighting Instructions in the Installation Manual for more detailed troubleshooting information. DANGER: FIGURE D Main Burner Thermopile Pilot FlameFIGURE A OFF POSITIONFIGURE B PILOT POSITIONFIGURE C ON POSITION 120°F Mark120°F Mark CONTROL KNOB 120°F Mark GAS CONTROL Gas Control & Temperature Knob Status Light Igniter Button LIGHTING INSTRUCTIONS A. This appliance has a pilot which is lit by a piezoelectric spark gas ignition system. Do not open the inner door of the appliance and try to light the pilot by hand. B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS • Do not try to light any appliance. • Do not touch any electric switch; do not use any phone in your building. • Immediately call your gas supplier from a neighbors phone. Follow the gas suppliers instructions. • If you cannot reach your gas supplier, call the fire department. C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, dont try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part has been under water. Immediately contact a qualified installer or service agency to replace a flooded water heater. Do not attempt to repair the unit! It must be replaced! BEFORE LIGHTING: ENTIRE SYSTEM MUST BE FILLED WITH WATER AND AIR PURGED FROM ALL LINESFLAMMABLE WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. FOR YOUR SAFETY READ BEFORE LIGHTING
www. americanwaterheater .com 29 TEMPERATURE REGULATION TEMPERATURE REGULATION Temperature Adjustment Valves for reducing the point-of-use temperature by mixing cold and hot water are available (see Figure 8). Also available are inexpensive devices that attach to faucets to limit hot water temperatures. Contact a licensed plumber or the local plumbing authority. Note: During low demand periods, a lower thermostat setting will reduce energy losses and may satisfy your normal hot water needs. If hot water use is expected to be more than normal, a higher thermostat setting may be required to meet the increased demand. When leaving your home for extended periods (e.g., vacations etc.) turn the temperature dial to its lowest setting. This will maintain the water at low temperatures with minimum energy losses and prevent the tank from freezing during cold weather. GAS CONTROL VALVE/THERMOSTAT SETTINGS GAS CONTROL/ TEMPERATURE KNOB STATUS LIGHT IGNITER120°F MARK130°F MARK155°F MARK 150°F MARK 140°F MARK 91°F MARK Figure 31 The thermostat is adjusted to the “OFF” position when it is shipped from the factory. Water temperature can be regulated by moving the temperature dial to the preferred setting. The preferred starting point is 120°F at the “HOT” setting. Align the knob with the desired water temperature as shown in Figure 31. There is a hot water scald potential if the thermostat is set too high. Note: Temperatures shown on the gas control valve/ thermostat are approximates. The actual temperature of the heated water may vary. Important: Adjusting the thermostat past the 120°F mark on the temperature dial will increase the risk of scald injury. Hot water can produce fi rst degree burns within: Water Temperature °F Time for 1st Degree Burns (Less Severe Burns)Time for Permanent Burns 2nd & 3rd Degree (Most Severe Burns) 110 (normal shower temp.) 116 (pain threshold) 116 35 minutes 45 minutes 122 1 minute 5 minutes 131 5 seconds 25 seconds 140 2 seconds 5 seconds 149 1 second 2 seconds 154 instantaneous 1 seconds (U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15,1978) Table 2 Should overheating occur or the gas supply fail to shut off, turn “OFF” the manual gas shut-off valve to the appliance (see Figure 1, item 18). OPERATING THE TEMPERATURE CONTROL SYSTEM Water Temperature Adjustment The water temperature setting can be adjusted from 91°F to 155°F . Turn the Gas Control Valve/Temperature Knob to the desired setting/temperature. Note: The temperatures indicated are approximates. The actual temperature of the heated water may vary. Operating Modes And Settings Standard Mode - The controller adjusts the water heater to maintain the temperature set by the user. Setting for vacation - The “LOW” position sets the controller at approximately 91°F . This setting is recommended for times when the water heater will not be in use for an extended period of time. It effectively turns the controller temperature setting down to a temperature that prevents the water in the water heater from freezing while still conserving energy.
30 www. americanwaterheater .com FOR YOUR INFORMATION EXTERNAL DAMAGE Do not operate the water heater until it has been fully checked out by a qualifi ed technician, if the water heater: • Has been exposed to fi re or damage. • Displays evidence of sooting. • Produces steam or unusually hot water. If the water heater has been fl ooded it must be replaced. START UP CONDITIONS NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN IT IS FILLED WITH WATER AND A TEMPERATURE AND PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF THE HEATER. DO NOT ATTEMPT TO OPERATE HEATER WITH COLD WATER INLET VALVE CLOSED. Condensate Whenever the water heater is fi lled with cold water, some condensate will form while the burner is on. A water heater may appear to be leaking when in fact the water is condensate. This usually happens when: a. A new water heater is fi lled with cold water for the fi rst time. b. Burning gas produces water vapo r in water heaters, particularly high efficiency models where flue temperatures are lower. c. Large amounts of hot water are used in a short time and the refi ll water in the tank is very cold. Moisture from the products of combustion condense on the cooler tank surfaces and form drops of water which may fall onto the burner or other hot surfaces to produce a “sizzling” or “frying” noise. Because of the suddenness and amount of water, condensate water may be diagnosed as a “tank leak”. After the water in the tank warms up (about 1-2 hours), the condition should disappear. Do not assume the water heater is leaking until there has been enough time for the water in the tank to warm up. An undersized water heater will cause more condensation. The water heater must be sized properly to meet the family’s demands for hot water including dishwashers, washing machines and shower heads. Excessive condensate may be noticed during the winter and early spring months when incoming water temperatures are at their lowest. Good venting is essential for a gas fi red water heater to operate properly as well as to carry away products of combustion and water vapo r. Smoke/Odo r It is not uncommon to experience a small amount of smoke and odo r during the initial start-up. This is due to burning off of oil from metal parts, and will disappear in a short while. THERMAL EXPANSION Water supply systems may, because of such events as high line pressure, frequent cut-offs, the effects of water hammer among others, have installed devices such as pressure reducing valves, check valves, back fl ow preventers, etc. to control these types of problems. When these devices are not equipped with an internal by-pass, and no other measures are taken, the devices cause the water system to be closed. As water is heated, it expands (thermal expansion) and closed systems do not allow for the expansion of heated water. As water is heated, it expands (thermal expansion). As the volume of water increases, there will be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause premature tank failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent temperature-pressure relief valve operation: water discharged from the valve due to excessive pressure build up. The temperature-pressure relief valve is not intended for the constant relief of thermal expansion. This condition is not covered under the limited warranty. A properly-sized thermal expansion tank should be installed on all closed systems to control the harmful effects of thermal expansion. Contact a plumbing service agency or your retail supplier regarding the installation of a thermal expansion tank.