Home
>
American Water Heater
>
Gas Heater
>
American Water Heater 40 Gallon 36000 BTU UltraLow Nox Direct Vent Natural Gas Water Heater DVUG6240S36NV user manual
American Water Heater 40 Gallon 36000 BTU UltraLow Nox Direct Vent Natural Gas Water Heater DVUG6240S36NV user manual
Have a look at the manual American Water Heater 40 Gallon 36000 BTU UltraLow Nox Direct Vent Natural Gas Water Heater DVUG6240S36NV user manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
21 Operating the Temperature Control System Figure 19: Status Codes VAC List of status codes are shown at top of gas control valve/thermostat. Water Temperature Adjustment The water temperature can be adjusted from 55°F to 155°F. Turn the Gas Control/Temperature Knob to the desired setting/temperature. Operating Modes and Settings • Standard Mode - The controller adjusts the water heater to maintain the temperature set by the user. • Vacation Setting - The controller adjusts the water temperature to approximately 55°F. This setting is recommended when the water heater is not in use for a long period of time. This effectively turns the water heater down to a setting that prevents the water from freezing. Status Light Code Normal Flashes: • 0 Flashes Indicates Control Off/Pilot Out. • 1 Flashes Indicates Normal Operation. • Continuous Light indicates the gas control valve/thermostat is shutting down. Diagnostic Flashes: If the water heater is not working look for the following diagnostic flashes after lighting the pilot. 2 Flashes Indicates Thermopile Voltage Low 4 Flashes Indicates Overheat Failure 5 Flashes Indicates Sensor Failure 7 Flashes Indicates Electronic Control Failure 8 Flashes See “Status Light Code Troubleshooting Chart.”
22 Operational Conditions Condensation Moisture from the products of combustion condenses on the tank surface and the outside jacket of the water heater and forms drops of water which may fall onto the burner or other hot surfaces. This will produce a “sizzling” or “frying” noise. NOTE: This condensation is normal and should not be confused with a leaking tank. Condensation may increase or decrease at different times of the year. High efficient energy saver water heaters will produce larger amounts of condensation on initial start-up or when a large amount of hot water is being used. NOTE: Do not confuse this with a “tank leak”. Once the water reaches a temperature of 120°F and the tank warms up (usually 1-2 hours), the condensation will stop. IMPORTANT: It is always recommended that a suitable metal drain pan be installed under the water heater to protect the area from water damage resulting from normal condensation production, a leaking tank or piping connections. Refer to “Location Requirements” on page 5. Under no circumstances is the manufacturer to be held responsible for any water damage in connection with this water heater. Water Heater Sounds During the normal operation of the water heater, sounds or noises may be heard. These noises are common and may result from the following: 1. Normal expansion and contraction of metal parts during periods of heat-up and cool-down. 2. Condensation causes sizzling and popping within the burner area and should be considered normal. 3. Sediment buildup in the tank bottom will create varying amounts of noise and may cause premature tank failure. Drain and flush the tank as directed under “Draining and Flushing”. Smoke/Odor The water heater may give off a small amount of smoke and odor during the initial start-up of the unit. This is due to the burning off of oil from metal parts of a new unit and will disappear after a few minutes of operation. Safety Shut-off This water heater is designed to automatically shut-off in the event of the following: 1. The pilot flame is extinguished for any reason. 2. The water temperature exceeds 189°F (87°C). 3. Excessive combustion chamber temperatures. 4. The ignition of flammable vapors. A thermopile is used to determine if a pilot flame is present, and will shut off the gas supply to the main burner and the pilot if the flame is absent. A temperature limit switch or ECO (Energy Cut Off) sensor located in the gas control valve\ thermostat is used to shut off the water heater if the water temperature exceeds 189°F (87°C). The Diagnostic Status Light will flash a code indicating an “Overheat Failure” (4 Flashes). See “Operating the Temperature Control System.” If the ECO has functioned the gas control valve/thermostat should be replaced by a qualified person. Contact your local dealer for service information. Anode Rod/Water Odor Each water heater contains at least one anode rod, which will slowly deplete (due to electrolysis) prolonging the life of the water heater by protecting the glass-lined tank from corrosion. Adverse water quality, hotter water temperatures, high hot water usage, hydronic heating devices, and water softening methods can increase the rate of anode rod depletion. Once the anode rod is depleted, the tank will start to corrode, eventually developing a leak. Certain water conditions will cause a reaction between the anode rod and the water. The most common complaint associated with the anode rod is a “rotten egg smell” produced from the presence of hydrogen sulfide gas dissolved in the water. IMPORTANT: Do not remove this rod permanently as it will void any warranties. A special anode rod may be available if water odor or discoloration occurs. NOTE: This rod may reduce but not eliminate water odor problems. The water supply system may require special filtration equipment from a water conditioning company to successfully eliminate all water odor problems. Artificially softened water is exceedingly corrosive because the process substitutes sodium ions for magnesium and calcium ions. The use of a water softener may decrease the life of the water heater tank. The anode rod should be removed from the water heater tank every 3 years for inspection. NOTE: artificially softened water requires the anode rod to be inspected annually. The following are typical (but not all) signs of a depleted anode rod: • The majority of the rods diameter is less than 3/8”. • Significant sections of the support wire (approx. 1/3 or more of the anode rod’s length) are visible. If the anode rod show signs of either or both it should be replaced. NOTE: Whether re-installing or replacing the anode rod, check for any leaks and immediately correct if found. In replacing the anode: 1. Turn off gas supply to the water heater. 2. Shut off the water supply and open a nearby hot water faucet to depressurize the water tank. 3. Drain approximately 5 gallons of water from tank. (Refer to “Draining and Flushing” for proper procedures). Close drain valve. 4. Remove old anode rod. 5. Use Teflon® tape or approved pipe sealant on threads and install new anode rod. 6. Turn on water supply and open a nearby hot water faucet to purge air from water system. 7. Check for any leaks and immediately correct any if found. 8. Restart the water heater as directed in this manual. See the Repair Parts Illustration for anode rod location. TEFLON ® is a registered trademark of E.I. Du Pont De Nemours and Company. Figure 20:
23 MAINTENANCE OF YOUR WATER HEATER Draining and Flushing It is recommended that the tank be drained and flushed every 6 months to remove sediment which may build up during operation. The water heater should be drained if being shut down during freezing temperatures. To drain the tank, perform the following steps: 1. Turn off the gas to the water heater at the manual gas shut-off valve. 2. Open a nearby hot water faucet until the water is no longer hot. 3. Close the cold water inlet valve. 4. Connect a hose to the drain valve and terminate it to an adequate drain or external to the building. 5. Open the water heater drain valve and allow all of the water to drain from the tank. Flush the tank with water as needed to remove sediment. 6. Close the drain valve, refill the tank, and restart the heater as directed in this manual. If the water heater is going to be shut down for an extended period, the drain valve should be left open. IMPORTANT: Condensation may occur when refilling the tank and should not be confused with a tank leak. Routine Preventative Maintenance At least annually, a visual inspection should be made of the venting and air supply system, piping systems, main burner, and pilot burner. Check the water heater for the following: • Obstructions, damage, or deterioration in the venting system. Make sure the ventilation and combustion air supplies are not obstructed. • Build up of soot and carbon on the main burner and pilot burner. Check for a soft blue flame. • Leaking or damaged water and gas piping. • Presence of flammable or corrosive materials in the installation area. • Presence of combustible materials near the water heater. • After servicing this water heater, check to make sure it is working properly. (See Operating Your Water Heater section of this manual.) IMPORTANT: If you lack the necessary skills required to properly perform this visual inspection, you should not proceed, but get help from a qualified person. Temperature and Pressure Relief Valve Manually operate the temperature and pressure relief valve at least once a year to make sure it is working properly. To prevent water damage, the valve must be properly connected to a discharge line which terminates at an adequate drain. Standing clear of the outlet (discharged water may be hot), slowly lift and release the lever handle on the temperature and pressure relief valve to allow the valve to operate freely and return to its closed position. If the valve fails to completely reset and continues to release water, immediately shut off the manual gas control valve and the cold water inlet valve and call a qualified person.Figure 21 Temperature and Pressure Relief Valve Manual Relief Valve Discharge line to drain Explosion Hazard If the temperature and pressure relief valve is dripping or leaking, have a qualified person replace it. Examples of a qualified person include: licensed plumbers, authorized gas company personnel, and authorized service personnel. Do not plug valve. Do not remove valve. Failure to follow these instructions can result in death, or explosion. WARNING
24 Replacement Parts Replacement parts may be ordered through your plumber or the local distributor. Parts will be shipped at prevailing prices and billed accordingly. When ordering replacement parts, always have the following information ready: 1. model, serial, and product number 2. type of gas 3. item number 4. parts description See pages 30-31 for a list of available repair parts. Removing the Burner Door Assembly 1. Turn off the gas to the water heater at the manual shut-off valve (Figure 3). 2. Turn the gas control/temperature knob to the “OFF” position (Figure 18). 3. Remove the outer door. 4. Remove the four screws (1/4” nut driver) securing the burner door assembly to the combustion chamber (Figure 23). 5. Disconnect the pilot tube (7/16” wrench), the igniter wire from the igniter lead wire, and manifold tube (3/4” wrench) at the gas control valve/thermostat. Also disconnect the red (+) and white (-) thermopile wires from the gas control valve/thermostat. See Figures 22 & 23. 6. Grasp the manifold tube and push down slightly, carefully remove the burner door assembly from the burner compartment. NOTE: Be sure not to damage internal parts. Natural Gas Burner (Ultra Low Nox) Check the burner to see if it is dirty or clogged. The burner may be cleaned with soft paint brush (Figure 24). Do not use a wire brush or any tool that may damage the burner screen. Important: Do not use the burner if the burner screen is damaged. NOTE: Damage may be rips or holes in the burner screen. Discoloration is normal. Igniter WireRed Wire (Left Side) Pilot Tube Manifold Tube Igniter Button Figure 22 Gas Control Valve/ Thermostat Igniter Lead Wire White Wire (Right Side) VAC Figure 23 Burner Door Assembly Removal Burner Door Screws (4) Manifold Component BlockBurner Door Pilot Tube Manifold Tube ViewportThermopile Wire Connections Piezo Igniter ButtonGas Control Valve/Thermostat VAC Outer Door Not Shown Figure24 NaturalGas(Low Nox) Burner Door Assembly Burner Use brush on this surface.Pilot Assembly
25 Replacing the Pilot/Thermopile Assembly 1. Remove the burner door assembly as directed previously. 2. Lift the retainer clip straight up from the back of the manifold component block (using a flat-blade screwdriver), then remove the manifold component block from the burner door assembly (Figure 25). 3. Locate and remove the phillips screw attaching the pilot to the pilot bracket, then pull the pilot/thermopile assembly (including the igniter wire) out of the burner door assembly. 4. Using a 7/16” wrench, loosen the nut securing the pilot tube to the pilot assembly (right-hand threads). 5. Pull the pilot tube from the pilot assembly (Figure 26). IMPORTANT: Be careful not to bend or alter the position of the pilot assembly components. 6. Using the old pilot tube as a guide, bend the new pilot tube to match the old one. Make only the bends closest to the pilot before going to the next step. 7. Reconnect the pilot tube and tighten the nut securing it to the pilot assembly. To prevent any bending of the pilot bracket, use pliers to hold the pilot assembly bracket while tightening the pilot nut. IMPORTANT: Keep the pilot orifice in the pilot when making the connection. DO NOT operate the water heater without the pilot orifice installed. 8. Push the new pilot assembly connectors through the opening in the burner door (See Figure 25). 9. Attach the pilot assembly to the Burner Door Assembly. 10. Position the new thermopile wires through the top opening of the manifold component block (Figure 25). Be sure that the igniter wire is positioned through the middle opening of the manifold component block. Position the pilot tube through the bottom opening of the manifold component block. 11. See “Replacing the Burner Door Assembly”. Figure 25 Manifold Component Block AssemblyThermopile Connectors Manifold Component BlockPilot Tube Igniter Wire Burner Door Opening Retainer Clip Figure 26 Pilot/Thermopile Assembly Pilot/Thermopile Assembly Igniter Connector PilotThermopile Thermopile Connectors Pilot Tube (Ferrule Nut Not Shown) result in death, explosion, or fire. WARNING Replace manifold component block if missing or removed. Replace door gasket if damaged. Failure to follow these instructions can Replace viewport if glass is missing or damaged.Tighten all burner door screws securely.Explosion Hazard Remove any fiberglass between gasket and combustion chamber.
26 1. Check the door gasket for damage or imbedded debris prior to installation. 2. Inspect the viewport for damage and replace as required. 3. Insert the burner door assembly into the burner compartment. 4. Inspect the door gasket and make sure there is no fiberglass insulation between the gasket and the combustion chamber. 5. Replace the four screws which secure the burner door assembly to the combustion chamber and tighten securely. There should be no space between the gasket part of the burner door and combustion chamber. IMPORTANT: Do not operate the water heater if the door gasket does not create a seal between the burner door and the combustion chamber. 6. Reconnect the manifold tubing (3/4” wrench), pilot tubing (7/16” wrench), temperature sensor wires, and thermopile wires to the gas control valve/thermostat. (See Figure 22 for the correct position of the thermopile wires.) Do not cross-thread or apply any thread sealant to the fittings. 7. Reconnect the igniter wire. 8. Turn the gas supply on and refer to the “Lighting Instructions” on page 18. 9. Check for leaks by brushing on an approved noncorrosive leak detection solution. Bubbles forming indicate a leak. Correct any leak found. IMPORTANT: All leaks must be fixed immediately. 10. Replace the outer door. result in death, explosion, or fire. Replacing the Burner Door Assembly WARNING Replace manifold component block if missing or removed. Replace door gasket if damaged. Failure to follow these instructions can Replace viewport if glass is missing or damaged.Tighten all burner door screws securely.Explosion Hazard Remove any fiberglass between gasket and combustion chamber. Figure 28A Combustion Chamber Door GasketCombustion Chamber Figure 28B Close-up inside view of the combustion chamber Combustion Chamber Piezoelectric Igniter System The piezoelectric igniter system consists of the igniter button, electrode, and wire. The pilot is ignited by an electric spark generated when the igniter button is pressed. (See Figure 29). Use only factory authorized piezoelectric igniter parts for replacement. Testing the Igniter System Turn off the gas to the water heater at the manual gas shut- off valve. Watch the electrode tip while activating the igniter. A visible spark should jump from the electrode. To avoid shock, do not touch the burner or any metal part on the pilot or pilot assembly. If no spark is visible, check the wire connections and make sure the electrode is not broken. Replace the igniter if defective. Dirt and rust on the pilot or electrode tip can prevent the igniter spark. Wipe clean with a damp cloth and dry completely. Rust can be removed from the electrode tip and metal surfaces by lightly sanding with an emery cloth or fine grit sandpaper. VAC Pilot/Thermopile Bracket (Opposite Side)Electrode Thermopile Pilot Igniter ButtonWire to Electrode Figure 29 Gas Igniter Assembly
27 Removing and Replacing the Gas Control Valve/Thermostat IMPORTANT: The gas control valve/thermostat is a standard valve with wire leads that connect to the thermopile. Removing the Gas Control Valve/Thermostat: 1. Turn the gas control/temperature knob to the “OFF” position (Figure 18). 2. Turn off the gas at the manual shut-off valve on the gas supply pipe (Figure 3). 3. Drain the water heater. Refer to the section of “Draining and Flushing” and follow the procedure. 4. Disconnect the igniter wire from the igniter lead wire. Disconnect the temperature sensor wire. Disconnect the red (+) and white (-) thermopile wires. Disconnect the pilot tube (7/16” wrench) and manifold tube (3/4” wrench) at the gas control valve/thermostat (Figure 22). 5. Refer to “Gas Piping” (Figure 3) and disconnect the ground joint union in the gas piping. Disconnect the remaining pipe from the gas control valve/thermostat. 6. To remove the gas control valve/thermostat, thread a 4” section of gas pipe into the inlet and use it to turn the gas control valve/thermostat (counterclockwise.) Do not use pipe wrench or equivalent to grip body. Damage may result, causing leaks. Do not insert any sharp objects into the inlet or outlet connections. Damage to the gas control valve/thermostat may result. Gas Control Valve/Thermostat: To replace the gas control valve/thermostat, reassemble in reverse order. When replacing the gas control valve/ thermostat, thread a section of 4” gas pipe into the inlet and use it to turn the gas control valve/thermostat (clockwise.) DO NOT OVER TIGHTEN, damage may result. • Be sure to use approved Teflon® tape or pipe joint compound on the gas piping connections and fitting on the back of the gas control valve that screws into tank. • Be sure to remove the pilot ferrule nut from the new gas control valve/thermostat. • Turn the gas supply on and check for leaks. Test the water heater by brushing on an approved noncorrosive leak detection solution. Bubbles forming indicate a leak. Correct any leak found. • Be sure tank is completely filled with water before lighting and activating the water heater. Follow the “Lighting Instructions” on page 18. • If additional information is required, reference the number on the cover of this manual for service information. Operational Checklist TROUBLESHOOTING CHART 4. No leaks at pilot and manifold connection. 5. Manifold door screws securely tightened. 1. Manifold gasket properly sealed. 2. Viewport not damaged or cracked. 3. Manifold component block properly installed. PROBLEM POSSIBLE CAUSE(S) CORRECTIVE ACTION BURNER WILL NOT IGNITE 1. Pilot not lit 2. Thermostat set too low 3. No gas 4. Dirt in the gas lines 5. Pilot line clogged 6. Main burner line clogged 7. Non-functioning thermopile 8. Non-functioning thermostat 9. Heater installed in a confined area1. Light pilot 2. Turn temp. dial to desired temperature 3. Check with gas utility company 4. Notify utility-install trap in gas line 5. Clean, locate source and correct 6. Clean, locate source and correct 7. Replace thermopile 8. Replace thermostat 9. Provide fresh air ventilation SMELLY WATER 1. Sulfides in the water 1. Replace the anode with a special anode BURNER FLAME YELLOW-LAZY1. Insufficient secondary air 2. Low gas pressure 3. Flue clogged 4. Main burner line clogged 5. Obstruction in main burner orifice1. Provide ventilation to water heater 2. Check with gas utility company 3. Clean, locate source and correct 4. Clean, locate source and correct 5. Clean or replace orifice PILOT WILL NOT LIGHT OR REMAIN LIT1. Non-functioning igniter 2. Thermopile connection loose 3. Air in gas line 4. Proper Lighting Sequence not followed. Gas Control /Temperature Knob was not held in for sufficient time 5. Low gas pressure 6. No gas 7. Dirt in gas lines 8. Cold drafts 9. Thermostat ECO switch open 10. Pilot line or orifice clogged 11. Non-functioning thermopile1. Replace igniter pilot assembly 2. Seat connector firmly in socket 3. Bleed the air from the gas line 4. Do not attempt to relight if the red light is lit, and the pilot flame is not visible through the view port. Wait until the red light is no longer lit, then follow lighting instructions on the water heater 5. Check with gas utility company 6. Check with gas utility company 7. Notify utility-install dirt trap in gas line 8. Locate source and correct 9. Replace thermostat 10. Clean, locate source and correct 11. Replace thermopile
28 PROBLEM POSSIBLE CAUSE(S) CORRECTIVE ACTION HIGH OPERATION COSTS 1. Thermostat set too high 2. Sediment or lime in tank 3. Water heater too small for job 4. Wrong piping connections 5. Leaking faucets 6. Gas leaks 7. Wasted hot water 8. Long runs of exposed piping 9. Hot water piping in exposed wall1. Set temperature dial to lower setting 2. Drain/flush-provide water treatment if needed 3. Install adequate heater 4. Correct piping-dip tube must be in cold inlet 5. Repair faucets 6. Check with utility-repair at once 7. Advise customer 8. Insulate piping 9. Insulate piping INSUFFICIENT HOT WATER 1. Thermostat set too low 2. Sediment or lime in tank 3. Water heater too small 4. Wrong piping connections 5. Leaking faucets 6. Wasted hot water 7. Long runs of exposed piping 8. Hot water piping in outside wall 9. Low gas pressure1. Turn temperature dial to desired setting 2. Drain/flush-provide water treatment if needed 3. Install adequate heater 4. Correct piping-dip tube must be in cold inlet 5 Repair faucets 6. Advise customer 7. Insulate piping 8. Insulate piping 9. Check with gas utility company SLOW HOT WATER RECOVERY1. Insufficient secondary air 2. Flue clogged 3. Low gas pressure 4. Improper calibration 5. Thermostat set too low 6. Water heater too small 7. Wrong piping connections 8. Wasted hot water1. Provide ventilation to water heater. Check flue way, flue baffle, and burner 2. Clean flue, locate source and correct 3. Check with gas utility company 4. Replace thermostat 5. Turn temperature dial to desired setting 6. Install adequate heater 7. Correct piping-dip tube must be in cold inlet 8. Advise customer DRIP FROM RELIEF VALVE 1. Excessive water pressure 2. Heater stacking 3. Closed water system1. Use a pressure reducing valve and relief valve 2. Lower the thermostat setting 3. See “Closed System/Thermal Expansion” THERMOSTAT FAILS TO SHUT-OFF1. Thermostat not functioning properly 2. Improper calibration1. Replace thermostat 2. Replace thermostat COMBUSTION ODORS 1. Insufficient secondary air 2. Flue clogged1. Provide ventilation to water heater. Check flue way, flue baffle, and burner 2. Clean, locate source and correct SMOKING AND CARBON FORMATION (SOOTING)1. Insufficient secondary air 2. Low gas pressure 3. Flue clogged 4. Thermostat not functioning properly 5. Burner flame yellow-lazy1. Provide ventilation to water heater. Check flue way, flue baffle, burner 2. Check with gas utility company 3. Clean, locate source and correct 4. Replace thermostat 5. See “Burner Flame Yellow-Lazy” CONDENSATION 1. Temperature setting too low 1. Increase the temperature setting BURNER FLAME FLOATS AND LIFTS OFF PORTS1. Orifice too large 2. High gas pressure 3. Flue clogged 4. Cold drafts1. Replace with correct orifice 2. Check with gas utility company 3. Clean flue and burner-locate source and correct 4. Locate source and correct BURNER FLAME TOO HIGH 1. Orifice too large 1. Replace with correct orifice FLAME BURNS AT ORIFICE 1. Thermostat not functioning properly 2. Low gas pressure1. Replace thermostat 2. Check with gas utility company PILOT FLAME TOO SMALL1. Pilot line or orifice clogged 2. Low gas pressure1. Clean, locate source and correct 2. Check with gas utility company
29 STATUS LIGHT CODE TROUBLESHOOTING CHART LED STATUS PROBLEM CORRECTIVE ACTION 0 FLASHES (LED NOT LIT) Pilot light is not lit. Not enough power (millivolts) to keep it lit.Follow the lighting instructions on the front of the water heater and record any diagnostic codes. See Diagnostic Status Light Code section. 1 FLASH (EVERY 3 SECONDS) Normal operation. No corrective action necessary. 2 FLASHES Insufficient power (millivolts) to the gas control valve/thermostat.1. Check all wiring connections. If problem persists proceed to step 2. 2. Replace the thermopile. If you feel uncomfortable with this procedure contact a qualified person. 4 FLASHES High water temperature has activated the over heat sensor.Replace the gas control valve/thermostat. If you feel uncomfortable with this procedure contact a qualified person. 5 FLASHES Sensor failure Replace the gas control valve/thermostat. If you feel uncomfortable with this procedure contact a qualified person. 7 FLASHES Gas Control Valve/Thermostat failure.Replace the gas control valve/thermostat. If you feel uncomfortable with this procedure contact a qualified person. 8 FLASHES This condition only appears if the gas control/temperature knob has been turned off and the thermopile continued to produce electric power. This condition can occur if the thermopile does not cool down as quickly as expected when the unit is shut off. This condition can also occur if the gas control/ temperature knob has been turned off and the pilot continues to operate because the pilot valve is stuck in the open position.Make sure that the gas control valve/thermostat knob is set to OFF. Wait one minute. Remove the outer door. Look through the sight glass for a pilot flame. If a pilot flame is observed with the gas control valve/thermostat knob set to the OFF position, the pilot valve is stuck open. Turn the main gas supply OFF. Replace the gas control valve/ thermostat. If you feel uncomfortable with this procedure contact a qualified person. If the pilot flame is not observed when the gas control valve/thermostat knob is set to the OFF position, wait 10 minutes for the thermopile to cool, then attempt to relight the pilot by following the lighting instructions on the water heater’s label. If this condition returns, replace the gas control valve/ thermostat. If you feel uncomfortable with this procedure contact a qualified person.
30 REPAIR PARTS ILLUSTRATION Item No.Parts Description 1 VENT CAP ASSEMBLY 2 OUTER WALL PLATE 3 INNER WALL PLATE 4 FLEX VENT PIPE (WITH CLAMPS) 5 UPPER AIR BOX 6 4” TO 3” REDUCER 7 DRAIN VALVE 8 FLUE BAFFLE 9 DIP TUBE 10 LOWER AIR BOX 11 SNAP IN PLUG 12 TEMPERATURE & PRESSURE RELIEF VALVE 13 GAS CONTROL VALVE/THERMOSTAT 14* MANIFOLD DOOR GASKET 15 FLANGE 16 DRAIN VALVE 17 ANODE ROD 18* VIEWPORT 19 DOOR SCREW 20* BURNER DOOR ASSEMBLY (NAT. GAS) 21* MANIFOLD COMPONENT BLOCK 22 OUTER DOOR 23 OPTIONAL VENT GUARD (SEE PAGE 12, -KIT # 6907245) *Pictured on next page. When ordering repair parts always give the following information: 1. Model, serial, and product number 2. Type of gas 3. Item number 4. Parts description Repair Parts List LEGEND Special anode rod (see page 22) Temperature and Pressure Relief Valve is required, but may not be factory installed 54 1 2 7 12 6 17 18 2119 22 1920 14 13 9 11 10 11 1615 8 3