Home > American Water Heater > Gas Heater > American Water Heater 30 Gallon 30000 BTU UltraLow Nox Natural Gas Water Heater UG6130T303NV user manual

American Water Heater 30 Gallon 30000 BTU UltraLow Nox Natural Gas Water Heater UG6130T303NV user manual

    Download as PDF Print this page Share this page

    Have a look at the manual American Water Heater 30 Gallon 30000 BTU UltraLow Nox Natural Gas Water Heater UG6130T303NV user manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							11
    Chimney Connection
    IMPORTANT: Before connecting a vent to a chimney, 
    make sure the chimney passageway is clear and free of 
    obstructions. The chimney must be cleaned if previously 
    used for venting solid fuel appliances or fireplaces. Also 
    consult local and state codes for proper chimney sizing and 
    application or, in the absence of local and state codes, the 
    “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current 
    edition.
    •  The connector must be installed above the extreme 
    bottom of the chimney to prevent potentially blocking 
    the flue gases.
    •  The connector must be firmly attached and sealed to 
    prevent it from falling out.
    •  To aid in removing the connector, a thimble or slip joint 
    may be used.
    •  The connector must not extend beyond the inner edge 
    of the chimney as it may restrict the space between it 
    and the opposite wall of the chimney (Figure 10).
    Do not terminate the vent connector in a chimney that has 
    not been certified for this purpose. Some local codes may 
    prohibit the termination of vent connectors in a masonry 
    chimney.
    Vertical Exhaust Gas Vent
    Vertical exhaust gas vents must be installed with U.L. listed 
    type B vent pipe according to the vent manufacturer’s 
    instructions and the terms of its listing. 
    It must be connected to the water heater’s draft hood by a 
    listed vent connector or by directly originating at the draft 
    hood opening.
    Vertical gas vents must terminate with a listed cap or 
    other roof assembly and be installed according to their 
    manufacturer’s instructions.
    Gas vents must be supported to prevent damage, joint 
    separation, and maintain clearances to combustible 
    materials (Figures 11 and 12).
    IMPORTANT: This gas vent must be terminated in a 
    vertical position to facilitate the removal of the burnt gases.
    An unused chimney flue or masonry enclosure may be 
    used as a passageway for the installation of a gas vent 
    (Figure 12).
    Common (combined) venting is allowable with vertical type 
    B vent systems and lined masonry chimneys as long as 
    proper draft for the water heater is established under all 
    conditions of operation.
    IMPORTANT: Do not common vent this water heater with 
    any power vented appliance.  
    Figures 10-12 are examples of vent pipe system 
    installations and may or may not be typical for your specific 
    application. Consult the “National Fuel Gas Code”, NFPA 
    54, ANSI Z223.1-current edition and the guidelines set forth 
    by prevailing local codes.
    * Maintain vent pipe clearance requirements to local, state 
    and/or the “National Fuel Gas Code”, ANSI Z223.1(NFPA 
    54)-current edition.
    ** NFPA 211, Standard for Chimneys, Fireplaces, Vents, 
    and Solid Fuel-Burning Appliances states that these 
    chimneys are intended to be installed in accordance with 
    the installation instructions provided with each chimney 
    support assembly. Minimum air space clearance to 
    combustible materials should be maintained as marked on 
    the chimney sections.
    Slope up 
    1/4 in. 
    per ft. 
    minimum  3 ft. minimum 2 ft. minimum above any  
                object within10 ft.  
                   horizontally 
    2 ft. minimum above any  
                object within10 ft.  
                   horizontally  3 ft. minimum 
    Ve n t  
    connector 
    slope up 
    1/4 in. per ft. 
    minimum 
    * 
    * 
    **  Listed Lined 
    Chimney 
    Support Strap
    Support 
    Strap
    Figure 12
    Venting Through
    a Chimney
    with Type B
    Double Wall
    Vent Pipe.
    MAINTAIN MANUFACTURER’S 
    SPECIFIED MINIMUM CLEARANCE
    LISTED VENT CAP
    VENT  CONNECTOR
    UNUSED CHIMNEY
    FLUE OR MASONRY
    ENCLOSURE
    SEAL
    *MAINTAIN
    CLEARANCE
    VENT
    CONNECTOR
    SLOPE UP 
    1/4 IN. PER FT.
    MINIMUM**MAINTAIN
    SPECIFIED
    CLEARANCE
    SUPPORT
    STRAP 
    						
    							12
    Water System Piping
    Piping Installation
    Piping, fittings, and valves should be installed according to 
    the installation drawing (Figure 13). If the indoor installation 
    area is subject to freezing temperatures, the water piping 
    must be protected by insulation.
    The water supply pressure should not exceed 80 psi. If this 
    occurs, a pressure reducing valve with a bypass should be 
    installed in the cold water inlet line. This should be placed 
    on the supply to the entire house in order to maintain equal 
    hot and cold water pressures.
    IMPORTANT: Heat cannot be applied to the water fittings 
    on the heater as they may contain nonmetallic parts. If 
    solder connections are used, solder the pipe to the adapter 
    before attaching the adapter to the hot and cold water 
    fittings.
    IMPORTANT: Always use a good grade of joint compound 
    and be certain that all fittings are drawn up tight.
    1.  Install the water piping and fittings as shown in 
    Figure 13. Connect the cold water supply (3/4” NPT) 
    to the fitting marked “C”. Connect the hot water supply 
    (3/4” NPT) to the fitting marked “H”.
    IMPORTANT:  Some models may contain energy saving 
    heat traps to prevent the circulation of hot water within the 
    pipes. Do not remove the inserts within the heat traps.
    2.  The installation of unions in both the hot and cold water 
    supply lines is recommended for ease of removing the 
    water heater for service or replacement.
    3.  The manufacturer of this water heater recommends 
    installing a mixing valve or an anti-scald device in the 
    domestic hot water line as shown in Figure 14. These 
    valves reduce the point-of-use temperature of the water 
    by mixing cold and hot water and are readily available 
    for use. 
    4.  If installing the water heater in a closed water system, 
    install an expansion tank in the cold water line as 
    specified under “Closed System/Thermal Expansion” 
    section.
    5.  Install a shut-off valve in the cold water inlet line. It 
    should be located close to the water heater and be 
    easily accessible. Know the location of this valve and 
    how to shut off the water to the heater.
    6.  A temperature and pressure relief valve must be 
    installed in the opening marked “Temperature and  
    Pressure (T & P) Relief Valve” on the water heater. 
    A discharge line must be added to the opening of 
    the T&P Relief Valve. Follow the instructions under 
    “Temperature and Pressure Relief Valve” section. 7.  After piping has been properly connected to the water 
    heater, remove the aerator at the nearest hot water 
    faucet. Open the hot water faucet and allow the tank to 
    completely fill with water. To purge the lines of any ex-
    cess air, keep the hot water faucet open for 3 minutes 
    after a constant flow of water is obtained. Close the 
    faucet and check all connections for leaks.
    Metal
    Drain Pan
    1 3/4” depth maximum
    Floor Drain
    Drain line 3/4” 
    ID minimumDischarge Pipe
    Do Not Cap or Plug
    Temperature and
    Pressure Relief Valve
    In a closed system use a
    thermal expansion tank
    Cold Water
    Supply to Fixtures
    Cold Water
    Inlet ValvePressure reducing
    valve with bypass
    Union
    Hot Water
    Outlet
    Massachussetts:
    Install a vacuum relief
    in cold water line per
    section 19 MGL 142.
    Figure 13
    Water Piping Installation
    Main water supply
    6” Maximum
    Air Gap
    1”minimum
    Figure 14
    Typical Mixing
    Valve Installation
    Follow the mixing
    valve manufacturer’s
    instructions.Cold
    Water
    Inlet
    Hot
    Water
    Outlet
    Tempered water
    to fixtures
    Mixing valve
    (Set to 120°F) 
    						
    							13 Please note the following: 
    •  The system should be installed only with piping that is 
    suitable for potable (drinkable) water such as copper, 
    CPVC, or polybutylene. This water heater must not be 
    installed using iron piping or PVC water piping.
    •  Use only pumps, valves, or fittings that are compatible 
    with potable water.
    •  Use only full flow ball or gate valves. The use of valves 
    that may cause excessive restriction to water flow is 
    not recommended.  
    •  Use only 95/5 tin-antimony or other equivalent solder. 
    Any lead based solder must not be used.
    •  Piping that has been treated with chromates, boiler 
    seal, or other chemicals must not be used.
    •  Chemicals that may contaminate the potable water 
    supply must not be added to the piping system.
    Closed System/Thermal Expansion
    Explosion Hazard
    If the temperature and pressure relief valve 
    is dripping or leaking, have a qualified 
    person replace it.
    Examples of a qualified person include:
    licensed plumbers, authorized gas company 
    personnel, and authorized service 
    personnel.
    Do not plug valve.
    Do not remove valve.
    Failure to follow these instructions can 
    result in death, or explosion.
    WARNING
    As water is heated, it expands (thermal expansion). In 
    a closed system, the volume of water will grow. As the 
    volume of water grows, there will be a corresponding 
    increase in water pressure due to thermal expansion.  
    Thermal expansion can cause premature tank failure 
    (leakage). This type of failure is not covered under the 
    limited warranty. Thermal expansion can also cause 
    intermittent temperature-pressure relief valve operation: 
    water discharged from the valve due to excessive pressure 
    build up. The temperature-pressure relief valve is not 
    intended for the constant relief of thermal expansion. This 
    condition is not covered under the limited warranty.
    A properly-sized thermal expansion tank should be 
    installed on all closed systems to control the effects of 
    thermal expansion.  Contact a plumbing service agency or 
    your retail supplier regarding the installation of a thermal 
    expansion tank. 
    						
    							14
    Temperature and Pressure 
    Relief Valve
    For protection against excessive pressures and 
    temperatures, a temperature and pressure relief valve must 
    be installed in the opening marked “T & P RELIEF VALVE” 
    (see Figure 15A). This valve must be design certified by 
    a nationally recognized testing laboratory that maintains 
    periodic inspection of the production of listed equipment or 
    materials as meeting the requirements for Relief Valves and 
    Automatic Shut-off Devices for Hot Water Supply Systems, 
    ANSI Z21.22. The function of the temperature and pressure 
    relief valve is to discharge water in large quantities in the 
    event of excessive temperature or pressure developing 
    in the water heater. The valve’s relief pressure must not 
    exceed the working pressure of the water heater as stated 
    on the data plate.IMPORTANT: Only a new temperature and pressure relief 
    valve should be used with your water heater. Do not use an 
    old or existing valve as it may be damaged or not adequate 
    for the working pressure of the new water heater. Do not 
    place any valve between the relief valve and the tank.
    The Temperature & Pressure Relief Valve:
    •  Must not be in contact with any electrical part.
    •  Must be connected to an adequate discharge line.
    •  Must not be rated higher than the working pressure 
    shown on the data plate of the water heater.
    The Discharge Line: 
    •  Must not be smaller than the pipe size of the relief 
    valve or have any reducing coupling installed in the 
    discharge line.
    •  Must not be capped, blocked, plugged or contain any 
    valve between the relief valve and the end of the dis-
    charge line.
    •  Must terminate a maximum of six inches above a floor 
    drain or external to the building. In cold climates, it is 
    recommended that the discharge pipe be terminated at 
    an adequate drain inside the building.
    •  Must be capable of withstanding 250°F (121°C) without 
    distortion.
    •  Must be installed to allow complete drainage of both 
    the valve and discharge line.
    T&P Relief Valve and Pipe Insulation (Some Models)
    1.   Locate the temperature and pressure relief valve on 
    the water heater (also known as a T&P relief valve).  
    See Figure 15B.
    2.   Locate the slit running the length of the T&P relief 
    valve insulation.
    3.   Spread the slit open and fit the insulation over the T&P 
    relief valve.  See Figure 15B.  Apply gentle pressure 
    to the insulation to ensure that it is fully seated on the 
    T&P Relief Valve. Once seated, secure the insulation 
    with duct tape, electrical tape or equivalent  
    IMPORTANT: The insulation or tape should not block 
    or cover the T&P relief valve drain opening. Also, the 
    insulation or tape should not block or hinder access to 
    the manual relief lever (Figure 15B).
    4.   Locate the hot water (outlet) & cold water (inlet) pipes 
    to the water heater.
    5.   Locate the slit running the length of a section of pipe 
    insulation.
    6.   Spread the slit open and slip the insulation over the 
    cold water (inlet) pipe. Apply gentle pressure along the 
    length of the insulation to ensure that it is fully seated 
    around the pipe. Also, ensure that the base of the 
    insulation is flush with the water heater.  Once seated, 
    secure the insulation with duct tape.  
    7.   Repeat steps 5 and 6 for the hot water (outlet) pipe.
    8.   Add additional sections of pipe insulation as needed.
    Figure 15A
    Temperature and Pressure
    Relief Valve Installation
    Discharge Pipe
    (Do not cap or plug.)
    6 Maximum
    Air Gap
    Metal Drain Pan
    Temperature and
    Pressure Relief Valve Optional location
    some models only
    Floor
    Drain
    Drain Line
    3/4” ID minimum
    Explosion Hazard
    If the temperature and pressure relief valve 
    is dripping or leaking, have a qualified 
    person replace it.
    Examples of a qualified person include:
    licensed plumbers, authorized gas company 
    personnel, and authorized service 
    personnel.
    Do not plug valve.
    Do not remove valve.
    Failure to follow these instructions can 
    result in death, or explosion.
    WARNING
    Figure 15B  
    T&P Relief Valve Insulation 
    T&P Relief Valve
    T&P Relief Valve 
    Drain LineManual Relief Lever
    T&P Relief Valve Insulation 
    						
    							15
    Special Applications
    Combination Space Heating/Potable 
    Water System
    Some water heater models are equipped with inlet/outlet 
    tappings suitable for combination water (potable) heating 
    and space heating and not suitable for space heating 
    applications only. If this water heater is to be used to supply 
    both space heating and domestic potable (drinking) water, 
    the instructions listed below must be followed.
    •  Be sure to follow the manual(s) shipped with the air 
    handler system.
    •  This water heater is not to be used as a replacement 
    for an existing boiler installation.
    •  Do not use with piping that has been treated with 
    chromates, boiler seal or other chemicals and do not 
    add any chemicals to the water heater piping.
    •  If the space heating system requires water tempera-
    tures in excess of 120°F, a mixing valve or an anti-
    scald device should be installed per its manufacturer’s 
    instructions in the domestic (potable) hot water supply 
    to limit the risk of scald injury.
    •  Pumps, valves, piping and fittings must be compatible 
    with potable water.
    •  A properly installed flow control valve is required to pre-
    vent thermosiphoning. Thermosiphoning is the result 
    of a continuous flow of water through the air handler 
    circuit during the off cycle. Weeping (blow off) of the 
    temperature and pressure relief valve  (T & P) or higher 
    than normal water temperatures are the first signs of 
    thermosiphoning.
    •  The domestic hot water line from the water heater 
    should be vertical past any mixing valve or supply line 
    to the air handler to remove air bubbles from the sys-
    tem. Otherwise, these bubbles will be trapped in the air 
    handler heat exchanger coil, reducing the efficiency.
    •  Do not connect the water heater to any system or 
    components previously used with non-potable water 
    heating appliances when used to supply potable water.Some jurisdictions may require a backflow preventer 
    in the incoming cold water line. This may cause the 
    temperature and pressure relief valve on the water heater 
    to discharge or weep due to expansion of the heated water. 
    A diaphragm-type expansion tank suitable for potable 
    water will normally eliminate this weeping condition. Please 
    read and follow the manufacturer’s instructions for the 
    installation of such tanks.
    Also see “Water System Piping” section for additional 
    instructions on the proper installation and operation of this 
    water heater.
    Solar Installation
    If this water heater is used as a solar storage heater 
    or as a backup for the solar system, the water supply 
    temperatures to the water heater tank may be in excess of 
    120°F. A mixing valve or other temperature limiting valve 
    must be installed in the water supply line to limit the supply 
    temperature to 120°F. The unit must be set to Standard 
    Mode (See Operating the Temperature Control System 
    section).
    NOTE: Solar water heating systems can often supply water 
    with temperatures exceeding 180°F and may result in water 
    heater malfunction.
    Figure 16
    Typical Mixing Valve Installation
    Combination Space Heating/Potable
    Water Heating System
    Metal Drain PanFloor Drain
    Unions Mixing
    ValveCoil
    Air
    HandlerShut-off
    ValveTo
    Air
    Handler
    Massachusetts code
    does not allow this
    type of installation.PumpFlow Control
    Valve
    InOut
    Domestic
    Hot Water
    OutCold
    Water
    Inlet
    Hot
    Water
    Out
    6 Maximum
    Air Gap
    Discharge P ipe
    Do Not Cap o r Plug
    Must be vertical to
    remove air bubbles 
    						
    							16
    Water Heater Location
    Water heater location is important and can affect system 
    performance. Please check the following:
    □   Installation area free of corrosive elements and 
    flammable materials.
    □   Centrally located with the water piping system. 
    Located as close to the gas piping and vent pipe 
    system as possible.
    □   Located indoors and in a vertical position. Protected 
    from freezing temperatures.
    □   Proper clearances from combustible surfaces 
    maintained and not installed directly on a carpeted 
    floor.
    □   Provisions made to protect the area from water 
    damage. Metal drain pan installed and piped to an 
    adequate drain.
    □   Sufficient room to service the water heater. See 
    “Clearances and Accessibility” section of this 
    manual.
    □   Water heater not located near an air moving device.
    □  Is the installed environment dirty (excessive 
    amounts of lint, dirt, dust, etc.)?  If so, the flame 
    arrestor located on the bottom of the water heater 
    will need to be cleaned periodically.  Refer to the 
    “Maintenance of your Water Heater” section of this 
    manual for information on cleaning the flame-trap. 
    Combustion Air Supply and Ventilation
    Check for sufficient combustion air supply.  Insufficient air 
    for the combustion of gas will result in the flame becoming 
    “lazy”, thereby allowing the burner operating temperature 
    to decrease.  This causes the gas control to shut off the 
    gas supply. Is the water heater installed in a closet or other 
    small, enclosed space? If so:
    □  Are there openings for make-up air to enter and 
    exit the room/area? 
    □ Are the openings of sufficient size?  Remember, 
    if there are other gas-fired or air-consuming 
    appliances in the same room, you need more 
    make-up air.  Refer to the “Location Requirements” 
    section of this water heater manual for specific 
    requirements.
    Fresh air not taken from areas that contain negative 
    pressure producing devices such as exhaust fans, 
    fireplaces, etc.
    □   Is there a furnace/air handler in the same room 
    space as the water heater?  If so, has a return air 
    duct system been attached that exits the room? 
    If so, check for leaks on the air duct system. If no 
    air duct system is present, correct immediately 
    by contacting a local Heating, Ventilation, Air-
    Conditioning & Refrigeration (HVAC-R) authorized 
    service provider. 
    □   Fresh air supply free of corrosive elements and 
    flammable vapors.
    □   Fresh air openings sized correctly with consideration 
    given to the blocking effect of louvers and grilles.
    □   Ductwork is the same cross-sectional area as the 
    openings.
    Vent Pipe System
    Check for proper drafting at the water heater draft hood. 
    Refer to the “Checking the Draft” section of this manual for 
    the test procedure. If the procedure shows insufficient draft 
    is present, please check the following.
    □   Draft hood properly installed.
    □   Vent connectors securely fastened with screws and 
    supported properly to maintain six inch clearance.
    □   Vent connector made of approved material and 
    sized correctly.
    □   Vent pipe system installed according to all local 
    and state codes or, in the absence of local and 
    state codes, the “National Fuel Gas Code”, ANSI 
    Z223.1(NFPA 54)-current edition.
    □   Flue baffle properly positioned in the flue tube.
    □   Check the vent system for restrictions/obstructions 
    and check the vent termination height.  Refer to the 
    “Air Supply and Ventilation” section of this water 
    heater manual for specific requirements.
    □  Recheck for sufficient combustion air supply.
    Water System Piping
    □   Temperature and pressure relief valve properly 
    installed with a discharge line run to an open drain 
    and protected from freezing.
    □   All piping properly installed and free of leaks.
    □   Heater completely filled with water.
    □   Closed system pressure build-up devices installed.
    □   Mixing valve (when applicable) installed per 
    manufacturer’s instructions (see “Water Temperature 
    Regulation” section).
    Gas Supply and Piping
    □  Gas type is the same as that listed on the water 
    heater data plate.
    □   Gas line equipped with shut-off valve, union, and  
    drip leg.
    □   Adequate pipe size and approved pipe material.
    □   An approved noncorrosive leak detection solution 
    used to check all connections and fittings for possible 
    gas leaks. If such a solution is not available, use a 
    mixture of dish washing soap and water (one part 
    soap to 15 parts water) or children’s soap bubble 
    solution. Bubbles forming indicate a leak. Correct 
    any leak found.
    TEFLON ® is a registered trademark of E.I. Du Pont De Nemours and Company.
    Important Information About This Water Heater
    This gas water heater was manufactured to voluntary safety standards to reduce the likelihood of a flammable vapor 
    ignition incident. The new technology used in meeting these standards makes this product more sensitive to installation 
    errors. Please review the following checklist and make any required installation upgrades or changes. 
    Questions? Reference the number on the cover of this manual for service information.
    Installation Checklist 
    						
    							17
    OPERATING YOUR WATER HEATER
    Lighting Instructions
    Read and understand these directions thoroughly before 
    attempting to light or re-light the pilot. Make sure the 
    viewport is not missing or damaged. (See Figure 23) Make 
    sure the tank is completely filled with water before lighting 
    the pilot. Check the data plate near the gas control valve/
    thermostat for the correct gas. Do not use this water heater 
    with any gas other than the one listed on the data plate. 
    If you have any questions or doubts, consult your gas 
    supplier or gas utility company.
    Lighting the Pilot:
    1.  Read and follow the lighting instructions on the water 
    heater’s label.
    2.  Turn the Control Knob to Pilot. Press the Knob in fully and 
    hold it in. (The knob will travel in about 1/4-inch if it is set to 
    Pilot correctly.)
    3.  Click the Igniter button continuously for up to 90 seconds 
    or until the Status Light begins to blink. If the Status Light 
    does not begin to blink after 90 seconds, STOP. Wait 10 
    minutes before attempting to relight the Pilot. Repeat these 
    steps 2-3 times, if necessary
    The circuitry in this gas valve requires that you wait 10 
    minutes between lighting attempts. If the Status Light 
    blinks, release the Control Knob and turn it to the desired 
    setting. (“Hot” is approximately 120°F).
    If the Status Light Does Not Blink:
    1.  Wait 10 minutes before another lighting attempt.
    2.  If the Status Light did not blink, repeat the lighting 
    procedure by following the lighting instructions on the water 
    heater’s label. Remove the outer door
    The Control Knob must be set to Pilot and held in 
    continuously while clicking the igniter button (about once 
    per second for up to 90 seconds). To observe the Pilot, 
    remove the outer door and look through the view port (sight 
    glass). See Figure 23.
    3.  Continue clicking the Igniter button (for up to 90 seconds) 
    until Pilot lights.
    4.  Once the Pilot is lit, continue to hold the Control Knob in 
    until the Status Light begins to blink.
    5.  Release Control Knob and set Knob to desired temperature 
    setting. (“Hot” is approximately 120°F.)
    6.  Replace the outer door.
    If the Pilot Does Not Light:
    1.  Wait 10 minutes before another lighting attempt. If the pilot 
    does not light, the Igniter may not be sparking or the unit 
    may not be getting gas (or for a new installation, there may 
    still be air in the gas line).
    Each time you click the igniter button, you should be able 
    to see the spark by looking through the view port.See 
    Figure 23. (You may have to darken the room lights to see WARNING
    Explosion Hazard
    Replace viewport if glass is missing 
    or damaged.
    Failure to do so can result in death, 
    explosion or fire.
    the spark.) You do not have to push the Control Knob in to 
    check the Igniter button. Simply look through the sight glass 
    while clicking the Igniter button and look for a spark. If you 
    can’t see a spark when the Igniter button is clicked, check 
    the wiring connections from the Igniter button and make 
    sure that they are tight.
    2.  If you see the Igniter spark, try relighting the pilot by 
    following the instructions on the water heater’s label. 
    Ensure that the gas supply is tuned on. There may be air in 
    the gas line, and several lighting attempts may be needed 
    to completely fill the line with gas and successfully light the 
    pilot.
    If the Pilot Lights but the Status Light Does Not Blink:
    1.  If the pilot lights, continue to hold the Control Knob in until 
    the Status Light blinks. If the pilot is lit and remains lit for 
    90 seconds and the Status Light still does not blink, the 
    thermopile connections may be loose, the thermal switch 
    may need to be reset, or the thermopile may be defective.
    2.  Remove the outer door.
    3.  Press the reset button on the thermal switch (Figure 23).
    4.  If switch clicks, it may have tripped. Do not light the Pilot 
    if flammable vapors are present. Check flame arrestor for 
    signs of discoloration (which could be caused by flammable 
    vapors). If the flame arrestor is discolored, do not attempt 
    to relight the Pilot. Have the water heater inspected by a 
    qualified service technician.
    5.  Check the wiring connections from the thermopile and the 
    thermal switch to the gas control valve/thermostat.
    Ensure that all wiring connections are tight. See Figure 23.
    6.  Replace the outer door.
    7.  Wait 10 minutes and try to light the Pilot according to the 
    instructions on the water heater’s label.
    8.  While clicking the Igniter button continuously, the Control 
    Knob must be set to Pilot and held in until the Status Light 
    blinks. Once the Status Light blinks, release the Control 
    Knob and set the Knob to the desired temperature setting. 
    (“Hot” is approximately 120°F.) 
    						
    							18
    FOR YOUR SAFETY READ BEFORE LIGHTING
    A. This appliance has a pilot which is lighted by a 
    piezoelectric igniter. When lighting the pilot, follow these
    instructions exactly.
    B. BEFORE LIGHTING smell all around the appliance area
    for gas. Be sure to smell next to the floor because some
    gas is heavier than air and will settle on the floor.
            WHAT TO DO IF YOU SMELL GAS:
    ‡Do not try to light any appliance.
    ‡Do not touch any electrical switch; do not use any
    phone in your building.
    ‡Immediately call your gas supplier from a 
    neighbor’s phone. Follow the gas supplier’s 
    instructions.
    ‡If you cannot reach your gas supplier, call the fire
     department.C. Use only your hand to push in or turn the gas control 
    temperature knob. Never use tools. If the knob will not 
    push in or move by hand, don’t try to repair it, call a 
    qualified service technician. Force or attempted repair 
    may result in a fire or explosion.
    D. Do not use this appliance if any part has been under 
    water. Immediately call a qualified service technician to
    inspect the appliance. Water heaters subjected to flood
    conditions or anytime the gas controls, main burner or
    pilot have been submerged in water require replacement
    of the entire water heater.
    E. DO NOT USE THIS APPLIANCE IF THERE HAS BEEN AN
    IGNITION OF VAPORS. Immediately call a qualified service
    technician to inspect the appliance. Water heaters
    subjected to a flammable vapors ignition will show a 
    discoloration on the air intake grid (bottom of combustion 
    chamber) and require replacement of the entire water heater.
    WARNING:  If you do not follow these instructions exactly, a fire or explosion
    may result causing property damage, personal injury or loss of life.
    TO TURN OFF GAS TO APPLIANCE
    1. Turn the gas control/temperature knob counterclockwise           to 
    the OFF setting. The status light will stop blinking and stay on for a
    short time after the water heater is turned off.
    LIGHTING INSTRUCTIONS
    5.
    1. STOP! It is imperative that you read all safety warnings
    before lighting the pilot.
    2. Turn the gas control/temperature knob counterclockwise
            to the OFF setting.
    3. Wait ten (10) minutes to clear out any gas.
    If you then smell gas, STOP! Follow “ B”  in the safety
    information above on this label. If you do not smell gas, 
     go to the next step.
    4. Turn the gas control/temperature knob clockwise
             to “ PILOT” .
    Igniter
    Button Gas control/
    temperature knob
    Status light120° F (48.9° C)
     Mark
    Index mark
    Press the gas control/temperature knob all the way in 
    and hold it in. The knob should travel in about 1/4 inch 
    (6.35 mm) if it is set to PILOT correctly.  
    While holding the gas control/temperature knob in, 
    click the igniter button continuously (about once a 
    second) for up to 90 seconds or until Status Light 
    begins to blink.    
    If the status light turns solid red, release the gas 
    control/temperature knob and repeat steps 2 through 5 
    (waiting 10 minutes before attempting to relight the pilot).
    6.
    If the status light does not start blinking after three lighting 
    attempts, turn the gas control/temperature knob to OFF 
    and call a qualified service technician or your gas supplier.
    When the status light starts blinking, release the gas 
    control/temperature knob.  Set the gas control/ tempera-
    ture knob to the desired setting.
    If the status light does not start blinking within 90 
    seconds, repeat steps 2 through 5 up to THREE (3) 
    times, waiting 10 minutes between lighting attempts.
    The circuitry in this advanced gas valve requires that 
    you wait 10 minutes between lighting attempts.
    Thermopile
    Pilot 
    						
    							19
    Burner Flames
    Inspect the burner flames through the viewport. Flames 
    should be very small with a blue haze and small amounts 
    of yellow or orange at the edges. After several minutes 
    of operation, the burner screen may glow red. If large 
    flames are observed at any time, shut-off unit and call a 
    qualified person.
    Water Temperature Stacking
    Stacking occurs when a series of short draws of hot water 
    (3 gallons or less) are taken from the water heater tank. 
    This causes increased cycling of the burner and can result 
    in increased water temperatures at the hot water outlet. 
    This water heater’s temperature control has been designed 
    to accurately regulate the water temperature. However, 
    under certain operating conditions, the water temperature 
    may temporarily exceed the dial setting. Consequently, in 
    addition to setting the temperature no higher than 120°F, 
    we recommend the installation of a mixing valve or an 
    anti-scald device in the hot water supply line or at the point 
    of use to further reduce the risk of scald injury.  These 
    devices can be obtained from a plumbing service agency or 
    your retail supplier.
    Emergency Shut Down
    IMPORTANT: Should overheating occur or the gas supply 
    fails to shut off, turn off the water heater’s manual gas 
    control valve and call a qualified person.
    Checking the Draft
    After successfully lighting the water heater, allow the unit 
    to operate for 15 minutes and check the drafthood relief 
    opening for proper draft. Make sure all other appliances 
    in the area are operating and all doors are closed when 
    performing the draft 
    test. Pass a match 
    flame around the 
    relief opening of the 
    drafthood. A  steady 
    flame drawn into the 
    opening indicates 
    proper draft. If 
    the flame flutters 
    or is blown out, 
    combustion products 
    are escaping from 
    the relief opening. If this occurs, do not operate the water 
    heater until proper adjustments or repairs are made to the 
    vent pipe system and/or air supply requirements.
    Figure 17
    MatchRelief
    OpeningDrafthood
    Figure 18
    Flame Characteristics
    Correct flame
    soft blue
    Burn Hazard
    Do not touch vent.
    Doing so can result in burns.
    WARNING 
    						
    							20
    Water Temperature Regulation
    The thermostat is adjusted to the pilot position when it 
    is shipped from the factory. Water temperature can be 
    regulated by moving the temperature dial to the preferred 
    setting. The preferred starting point is 120°F at the “HOT” 
    setting. Align the knob with the desired water temperature 
    as shown in Figure 19A. There is a hot water scald 
    potential if the thermostat is set too high. 
    NOTE: Temperatures shown on the gas control valve/
    thermostat are approximates. The actual temperature of the 
    heated water may vary. IMPORTANT:  Adjusting the thermostat past the 120°F bar 
    on the temperature dial will increase the risk of scald injury. 
    Hot water can produce first degree burns within:
    Table 4:
    Water 
    Temperature °FTime for 1st 
    Degree Burn 
    (Less Severe Burns)Time for 
    Permanent Burns 
    2nd & 3rd Degree 
    (Most Severe Burns)
    11 0
    11 6
    11 6
    122
    131
    140
    149
    154(normal shower temp.)
    (pain threshold)
    35 minutes
    1 minute
    5 seconds
    2 seconds
    1 second
    instantaneous45 minutes
    5 minutes
    25 seconds
    5 seconds
    2 seconds
    1 seconds
    (U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15,1978)
    VAC
    Figure 19A
    Gas Control Valve/Thermostat
    Settings
    Gas Control/Temperature Knob
    Status
    Light
    Igniter120°F
    Mark
    NOTE:  During low demand periods when hot water is not 
    being used, a lower thermostat setting will reduce energy 
    losses and may satisfy your normal hot water needs. 
    If hot water use is expected to be more than normal, a 
    higher thermostat setting may be required to meet the 
    increased demand. When leaving your home for extended 
    periods (vacations, etc.) turn the temperature dial to the 
    vacation (VAC) setting. This will maintain the water at low 
    temperatures with minimum energy losses and prevent the 
    tank from freezing during cold weather. 
    Water temperature over 125°F can cause 
    severe burns instantly or death from scalds.
    Children, disabled and elderly are at highest 
    risk of being scalded.
    Feel water before bathing or showering.
    Temperature limiting valves are available.
    WARNING 
    						
    All American Water Heater manuals Comments (0)

    Related Manuals for American Water Heater 30 Gallon 30000 BTU UltraLow Nox Natural Gas Water Heater UG6130T303NV user manual