Home
>
AirComm Corporation
>
Air Conditioner
>
AirComm Corporation Bell Air Conditioner206AB Installation Instructions TORQLOK PLUMBING
AirComm Corporation Bell Air Conditioner206AB Installation Instructions TORQLOK PLUMBING
Have a look at the manual AirComm Corporation Bell Air Conditioner206AB Installation Instructions TORQLOK PLUMBING online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 74 AirComm Corporation manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Page 10 of 21 206EC-250M Rev E Fitting Torquing Procedures and Torque Values Insert O-Ring Fitting (Green O-Ring) Torq-Lok Fitting (Black O-Ring) Apply refrigerant oil to O-ring and female side of fitting. Confirm there is no damage / nicks or dirt on fittings. Slide B-nut back away from end of tube so you may see O-ring as you slide the fitting together. Be careful not to pinch O-ring. Engage male end into female fitting being very careful to maintain alignment and not pinch O-ring during this step. The male flange should seat fully against the metal side of the female flange without the O-ring being pinched. Hold fitting together while siding B-nut forward and engaging threads. Tighten B-nut, and torque to the following settings. #6 Fittings: 30-35 in lbs Do not over torque #8 Fittings: 40-45 in lbs #10 Fittings: 50-55 in lbs Once system is charged, check each fitting with an electronic leak detector. (an Electronic Leak Detector is the only reliable method of checking for refrigerant leaks). Once fittings have been checked and are leak free, Torque Seal as appropriate. System leak check Identification of and elimination of any system fitting leaks is extremely important to insure a trouble free system. A system which contains a partial charge can be leak tested and recharged without evacuating the system. The system can be pressurized with nitrogen or R134a refrigerant. A system which has been evacuated should be filled to a pressure of at least 50 psig of refrigerant or 150 psi nitrogen prior to the leak survey.
Page 11 of 21 206EC-250M Rev E System Leak Check (cont) The system should be leak tested using an electronic leak detector. Initial leak check can be accomplished with a refrigerant charge of .5 lbs and the electronic leak detector. Each fitting should be checked and repaired prior to the final charging process. Do not use compressed air for the pressure check! Compressed air can introduce moisture in the system which will cause it to operate poorly or not at all. Take your time, and check all around each fitting. A little extra time during the leak check will save a significant amount of time later during servicing or troubleshooting. All leak checks should be conducted with the air conditioner “off”. Since the refrigerant is heavier than air, leaks are most likely detected on the underside of hoses and fittings. Also the refrigerant will collect in low areas and provide an erroneous leak indication. A stream of “shop air” through a nozzle is useful in clearing an area just before checking for leaks. If a leak is detected at an O-ring fitting, reclaim the system and install a new O-ring. Lubricate the O-ring with refrigerant oil prior to installation. A small amount of leakage (one once per year) past the compressor seal in normal. Most leak detectors are sensitive enough to show a leak of this magnitude. Charging Procedure NOTE This system should be serviced by qualified personnel only. 1. Leak check system in accordance with procedures present on pages 9 and 10. 2. Evacuate system for a minimum of 30 minutes. 3. Charge the system with 2.4 lbs (single fwd. Evaporator) or 2.6 lbs (Dual fwd. Evaporator) of R134a refrigerant. System pressures can very depending on temperature / humidity relationships. The most accurate method of charging a system is to add an initial refrigerant charge of 2.0 lbs then continue to add refrigerant until the evaporator outlet air temperature and system suction pressure reaches a minimum and subsequently starts to increase. When adding the refrigerant after the initial charge it should be done in increments of .25 lbs, and a minimum of 10 minutes allowed to elapse before adding each additional .25 lbs of refrigerant charge. This allows the system to stabilize and reach its maximum cooling potential for the given charge. The optimum charge occurs when evaporator outlet air temperatures are at their lowest. Any additional refrigerant will cause the outlet air temperature to increase and system performance to be degraded. Charge the system to the point of noticing the first temperature increase, then reduce charge back to the optimum point where outlet air temperatures were lowest. Refrigerant Pressure System pressures will very due to temperature and humidity relationships. NOTE System overcharging, or operation of system during low ambient conditions may result in tailrotor pedal feedback.
Page 12 of 21 206EC-250M Rev E System troubleshooting Prior to troubleshooting a defective system, conduct a visual inspection for general condition. Inspect condenser fins for damage, comb out bent fins, and Check circuit breakers in baggage compartment. The following step-by-step procedures list the easiest checks, and most likely problem sources, first. 1. Electrical With the engine off turn switch to “Blower” and make sure all evaporator blowers operate in both Hi and Low modes. Pull evaporator circuit breaker in battery compartment, and turn switch to A/C. Check that the condenser blower and actuator assy. Is working, and the compressor clutch is engaging. 2. System Charge (See page 11, “Charging Procedures”) 3. Expansion Valve Malfunction If the cooling loss is limited to only one evaporator, it is most likely a defective expansion valve. Loss of cooling in all evaporators (assuming that there were no problems identified during steps 1 or 2) could be caused by refrigerant flow blockage at the expansion valves. This blockage could be due to ice or dirt. Replacement of the drier bottle and a thorough system evacuation might be a fix (remove the possibility of ice at the expansion valve nozzles). 4. Compressor Malfunction If the system will not maintain the pressures and there are no system leaks, the problem could be a failed compressor. The compressor must then be replaced.
Page 13 of 21 206EC-250M Rev E SYSTEM TROUBLESHOOTING TABLE Problem Cause Solution 1. Premature Belt Failure a. Belt too loose b. Compressor misalign. c. System over charged a. Adjust belt tension b. Re-install/align compressor c. Adjust system charge 2. Condenser blower motor Circuit Breaker “Pops” a. Probable cause- Overheating of condenser blower motor a. Check for loose or rubbing of fan blade, or possible replacement of motor 3. Water (Condensate) in area of the aft evaporator a. Condensate drain fitting on evaporator not sealed b. Evaporator housing not sealed c. Drain line / check valve not installed properly d. Condensate forming on plumbing fittings a.b.c. Verify that installation conforms to drawing requirements. (remove evaporator inlet duct, and pour 1/2 ltr. of water into housing assy. To check for leaks & drainage. d. apply cork insulation to all exposed refrigerant lines. 4. Water in chin bubble area of forward evaporator a. Forward evaporator housing not sealed b. Condensate drain line fittings not secure at evaporator connection. c. Drain line check valve not installed a. Same as problem #3 a.b.c. 5. Conditioned air outlet louvers broken / loose a. Replace Louvers 6. Evaporator Coil freeze up a. System suction pressure (temperature) too low. System suction pressure should not be below 20 psi. a. Adjust system charge to 25 - 32 psi. 7. System not Cooling a. Loss of refrigerant b. Water in system a. Evacuate system, leak check and recharge. b. Evacuate system, replace receiver drier bottle, & recharge 8.System with Poor Cooling a. By-pass valve a. Check to insure the temperature control knob is in the full cold position, and the temperature control circuit breaker has not tripped. If the valve remains open (by- passing refrigerant) the valve will need replacement.
Page 14 of 21 206EC-250M Rev E PERIODIC INSPECTIONS AND OVERHAUL SCHEDULE Item Prior to Cooling Season Every 100 hr. Operation Overhaul / Replacement Hours 3 Check Evap. Blower Operation Hi/Low X X Check Cond. Blower Operation X X Belt wear & Tension 1 X X Condenser Fins X X Placards Compressor Mounting Lugs For Cracks X X Condenser Blower Motor - - On Condition Replace Belt 2 When evidence of excessive wear Notes: 1 It is acceptable to remove the compressor drive belt during the cold weather season. Care should be taken to insure that the compressor is securely supported by the belt tension link. 2 The belt tension on a newly installed belt should be reset after two hours of operation. 3 The warranty period of the condenser blower motor is 1000 hours or 1 year whichever occurs first. It is acceptable to operate the condenser blower beyond the warranty period as no safety-of-flight issues are involved. Failure of the condenser blower will cause the system over-pressure switch to electrically shut the system off. You may elect to purchase a new condenser blower motor after 1000 hours of operation, or wait until the blower motor failure occurs.
Page 15 of 21 206EC-250M Rev E General Arran gement – Air Conditioner S ystem with sin gle Forward Eva porato r
Page 16 of 21 206EC-250M Rev E General Arrangement – Air Conditioning System with Dual Forward Evaporator
Page 17 of 21 206EC-250M Rev E General Arrangement – Electrical Systems Components