Home > AirComm Corporation > Air Conditioner > AirComm Corporation Bell Air Conditioner206AB Installation Instructions TORQLOK PLUMBING

AirComm Corporation Bell Air Conditioner206AB Installation Instructions TORQLOK PLUMBING

    Download as PDF Print this page Share this page

    Have a look at the manual AirComm Corporation Bell Air Conditioner206AB Installation Instructions TORQLOK PLUMBING online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 74 AirComm Corporation manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							  Page 10 of 21 
     206EC-250M 
     Rev E 
    Fitting Torquing Procedures and Torque Values 
     
     
    Insert O-Ring Fitting (Green O-Ring)     Torq-Lok Fitting (Black O-Ring) 
     
        Apply refrigerant oil to O-ring and female side of fitting. 
        Confirm there is no damage / nicks or dirt on fittings. 
        Slide B-nut back away from end of tube so you may see 
        O-ring as you slide the fitting together. 
     
     
     
         Be careful not to pinch O-ring. 
        Engage male end into female fitting being very careful to 
        maintain alignment and not pinch O-ring during this step. 
     
        The male flange should seat fully against the metal side 
        of the female flange without the O-ring being pinched. 
     
        Hold fitting together while siding B-nut forward and engaging threads. 
        Tighten B-nut, and torque to the following settings. 
     
        #6 Fittings: 30-35 in lbs     Do not over torque 
        #8 Fittings: 40-45 in lbs 
        #10 Fittings: 50-55 in lbs 
     
    Once system is charged, check each fitting with an electronic leak detector. (an 
    Electronic Leak Detector is the only reliable method of checking for refrigerant leaks). 
    Once fittings have been checked and are leak free, Torque Seal as appropriate. 
     
    System leak check 
     
    Identification of and elimination of any system fitting leaks is extremely important to 
    insure a trouble free system. 
     
    A system which contains a partial charge can be leak tested and recharged without 
    evacuating the system. The system can be pressurized with nitrogen or R134a 
    refrigerant. A system which has been evacuated should be filled to a pressure of at 
    least 50 psig of refrigerant or 150 psi nitrogen prior to the leak survey. 
      
    						
    							  Page 11 of 21 
     206EC-250M 
     Rev E 
     
    System Leak Check (cont)  
     
    The system should be leak tested using an electronic leak detector. Initial leak check can be 
    accomplished with a refrigerant charge of .5 lbs and the electronic leak detector. Each fitting 
    should be checked and repaired prior to the final charging process. 
    Do not use compressed air for the pressure check! Compressed air can introduce moisture 
    in the system which will cause it to operate poorly or not at all. Take your time, and check all 
    around each fitting. A little extra time during the leak check will save a significant amount of time 
    later  during servicing or troubleshooting. 
     
    All leak checks should be conducted with the air conditioner “off”. Since the refrigerant is 
    heavier than air, leaks are most likely detected on the underside of hoses and fittings. Also the 
    refrigerant will collect in low areas and provide an erroneous leak indication. A stream of “shop 
    air” through a nozzle is useful in clearing an area just before checking for leaks. 
     
    If a leak is detected at an O-ring fitting, reclaim the system and install a new O-ring. Lubricate 
    the O-ring with refrigerant oil prior to installation. 
     
    A small amount of leakage (one once per year) past the compressor seal in normal. Most leak 
    detectors are sensitive enough to show a leak of this magnitude. 
     
    Charging Procedure 
    NOTE 
    This system should be serviced by qualified personnel only. 
     
    1.  Leak check system in accordance with procedures present on pages 9 and 10. 
    2.  Evacuate system for a minimum of 30 minutes. 
    3.  Charge the system with 2.4 lbs (single fwd. Evaporator) or 2.6 lbs (Dual fwd. Evaporator) 
    of R134a refrigerant. System pressures can very depending on temperature / humidity 
    relationships. The most accurate method of charging a system is to add an initial 
    refrigerant charge of 2.0 lbs then continue to add refrigerant until the evaporator outlet 
    air temperature and system suction pressure reaches a minimum and subsequently 
    starts to increase. When adding the refrigerant after the initial charge it should be done 
    in increments of .25 lbs, and a minimum of 10 minutes allowed to elapse before adding 
    each additional .25 lbs of refrigerant charge. This allows the system to stabilize and 
    reach its maximum cooling potential for the given charge. The optimum charge occurs 
    when evaporator outlet air temperatures are at their lowest. Any additional refrigerant will 
    cause the outlet air temperature to increase and system performance to be degraded. 
    Charge the system to the point of noticing the first temperature increase, then reduce 
    charge back to the optimum point where outlet air temperatures were lowest. 
     
    Refrigerant Pressure 
     
      System pressures will very due to temperature and humidity relationships. 
     
    NOTE 
    System overcharging, or operation of system during low ambient conditions may result 
    in tailrotor pedal feedback. 
      
    						
    							  Page 12 of 21 
     206EC-250M 
     Rev E 
     
    System troubleshooting 
     
    Prior to troubleshooting a defective system, conduct a visual inspection for general 
    condition. Inspect condenser fins for damage, comb out bent fins, and Check circuit 
    breakers in baggage compartment. 
     
    The following step-by-step procedures list the easiest checks, and most likely problem 
    sources, first. 
     
    1. Electrical 
     
    With the engine off turn switch to “Blower” and make sure all evaporator blowers 
    operate in both Hi and Low modes. Pull evaporator circuit breaker in battery 
    compartment, and turn switch to A/C. Check that the condenser blower and 
    actuator assy. Is working, and the compressor clutch is engaging. 
     
    2. System Charge 
     
    (See page 11, “Charging Procedures”) 
     
    3. Expansion Valve Malfunction 
     
    If the cooling loss is limited to only one evaporator, it is most likely a defective 
    expansion valve. 
     
    Loss of cooling in all evaporators (assuming that there were no problems 
    identified during steps 1 or 2) could be caused by refrigerant flow blockage at the 
    expansion valves. This blockage could be due to ice or dirt. 
     
    Replacement of the drier bottle and a thorough system evacuation might be a fix 
    (remove the possibility of ice at the expansion valve nozzles). 
     
    4. Compressor Malfunction 
     
    If the system will not maintain the pressures and there are no system leaks, the 
    problem could be a failed compressor. The compressor must then be replaced. 
     
     
     
     
     
     
     
     
      
    						
    							  Page 13 of 21 
     206EC-250M 
     Rev E 
     
    SYSTEM TROUBLESHOOTING TABLE 
     
    Problem Cause Solution 
     
    1. Premature Belt Failure  a.  Belt too loose 
    b. Compressor misalign. 
    c.  System over charged a.  Adjust belt tension 
    b. Re-install/align 
    compressor 
    c.  Adjust system charge 
    2. Condenser blower motor 
    Circuit Breaker “Pops” a. Probable cause- 
    Overheating of condenser 
    blower motor a. Check for loose or rubbing 
    of fan blade, or possible 
    replacement of motor 
    3. Water (Condensate) in area 
    of the aft evaporator a.  Condensate drain fitting 
    on evaporator not sealed 
    b. Evaporator housing not 
    sealed 
    c.  Drain line / check valve 
    not installed properly 
    d.  Condensate forming on 
    plumbing fittings a.b.c. Verify that installation 
    conforms to drawing 
    requirements. (remove 
    evaporator inlet duct, and 
    pour 1/2 ltr. of water into 
    housing assy. To check for 
    leaks & drainage. 
    d. apply cork insulation to all 
    exposed refrigerant lines. 
    4. Water in chin bubble area 
    of forward evaporator a. Forward evaporator 
    housing not sealed 
    b.  Condensate drain line 
    fittings not secure at 
    evaporator connection. 
    c.  Drain line check valve not 
    installed a. Same as problem #3 a.b.c. 
    5. Conditioned air outlet 
    louvers broken / loose  a. Replace Louvers 
    6. Evaporator Coil freeze up  a. System suction pressure 
    (temperature) too low. System 
    suction pressure should not 
    be below 20 psi. a. Adjust system charge to 25 
    - 32 psi. 
    7. System not Cooling  a.  Loss of refrigerant 
    b.  Water in system a.  Evacuate system, leak 
    check and recharge. 
    b.  Evacuate system, replace 
    receiver drier bottle, & 
    recharge  
    8.System with Poor Cooling  a. By-pass valve  a. Check to insure the 
    temperature control knob is in 
    the full cold position, and the 
    temperature control circuit 
    breaker has not tripped. If the 
    valve remains open (by-
    passing refrigerant) the valve 
    will need replacement. 
     
     
      
    						
    							  Page 14 of 21 
     206EC-250M 
     Rev E 
     
    PERIODIC INSPECTIONS AND OVERHAUL SCHEDULE 
     
    Item  Prior to  
    Cooling  
    Season Every 
    100 hr. 
    Operation Overhaul / 
    Replacement 
    Hours 
    3 
     
        
    Check Evap. Blower 
    Operation Hi/Low X X  
        
    Check Cond. Blower 
    Operation X X  
        
    Belt wear & Tension 
    1 X X  
        
    Condenser Fins  X  X   
        
    Placards    
        
    Compressor Mounting 
    Lugs For Cracks X X  
        
    Condenser Blower 
    Motor - - On Condition 
     
    Replace Belt 2      When evidence of excessive wear 
     
     
    Notes: 
     
    1   It is acceptable to remove the compressor drive belt during the cold weather season. 
    Care should be taken to insure that the compressor is securely supported by the belt 
    tension link. 
     
    2 The belt tension on a newly installed belt should be reset after two hours of 
    operation. 
     
    3 The warranty period of the condenser blower motor is 1000 hours or 1 year 
    whichever occurs first. It is acceptable to operate the condenser blower beyond the 
    warranty period as no safety-of-flight issues are involved. Failure of the condenser 
    blower will cause the system over-pressure switch to electrically shut the system off. 
    You may elect to purchase a new condenser blower motor after 1000 hours of 
    operation, or wait until the blower motor failure occurs. 
     
     
     
       
    						
    							  Page 15 of 21 
     206EC-250M 
     Rev E 
     
     
     
    General Arran
    gement – Air Conditioner S
    ystem with sin
    gle Forward Eva
    porato
    r  
    						
    							  Page 16 of 21 
     206EC-250M 
     Rev E 
     
     
     
    General Arrangement – Air Conditioning System with Dual Forward Evaporator  
    						
    							  Page 17 of 21 
     206EC-250M 
     Rev E 
     
     
    General Arrangement – Electrical Systems Components  
    						
    							  Page 18 of 21 
     206EC-250M 
     Rev E 
     
      
    						
    All AirComm Corporation manuals Comments (0)

    Related Manuals for AirComm Corporation Bell Air Conditioner206AB Installation Instructions TORQLOK PLUMBING