Home
>
AirComm Corporation
>
Air Conditioner
>
AirComm Corporation Bell 407 Air Conditioner Instructions for Continued Airworthiness User Manual
AirComm Corporation Bell 407 Air Conditioner Instructions for Continued Airworthiness User Manual
Have a look at the manual AirComm Corporation Bell 407 Air Conditioner Instructions for Continued Airworthiness User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 74 AirComm Corporation manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 64 CHAPTER 8 TROUBLESHOOTING 1. SYSTEM TROUBLESHOOTING Prior to troubleshooting a defective system, it is advisable to conduct a visual inspection for general condition, and obvious signs of damage or failure. The following matrix lists the easiest checks, and the most likely problems. Problem Probable Cause Solution System not Cooling (Evaporator blowers still operating) a. System is low or empty of refrigerant. a. Evacuate the system, determine the origin of the refrigerant leak, and re- charge the system as prescribed in chapter 6. b. Moisture or air in the system. b. Evacuate the system, Replace the receiver / drier, and place the system under a vacuum for a minimum of 45 minutes before recharging the system. c. Compressor c. If the compressor has failed, it must be replaced, as per chapter 7. d. Compressor drive belt d. If the compressor drive belt has failed it will need to be replaced. Replace and adjust compressor drive belt as per chapter 7. e. By-pass valve e. Check to ensure the temperature control knob on the A/C control panel in the cockpit is in the full cold position, and the temperature control circuit breaker has not tripped. If the valve remains open (by-passing refrigerant) the valve will need replacement, as per chapter 7. f. Condenser blower motor / fan assembly. f. Check to ensure the condenser blower motor / fan assembly are receiving power, and the circuit breakers have not tripped. If the blowers still do not function, they may have failed internally and must be replaced as per chapter 7. g. Condenser Scoop Door & Scoop Door Actuator g. Check to ensure the condenser scoop door is fully extended when the air conditioner is running. If the scoop door is closed or not fully extended the scoop actuator circuit breaker may have tripped, or the scoop door actuator may have failed, and must be replace as per chapter 7. System not cooling (Evaporator blowers not operating) h. Air conditioner control circuit breaker tripped. h. Reset circuit breaker. If breaker will not reset, check for short in circuit. i. Forward or Aft evaporator blower circuit breaker tripped. i. Reset circuit breaker. If breaker will not reset, check for short in circuit.
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 65 Problem Probable Cause Solution System not cooling (Evaporator blowers not operating) j. Forward and aft evaporator blower motor(s) j. Check for power to the motor(s), and for the free movement of the blower wheel. If the motor shaft does not turn smoothly the motor must be replaced, as per chapter 7. Loss of cooling limited to one evaporator. k. Expansion valve malfunction. k. If cooling is lost in only one of the evaporators, and the blowers continue to function, it is most likely a blockage at the expansion valve orifice. This is most often caused by dirt in the system forming a blockage as the refrigerant passes through the valve. Evacuating the system and changing the receiver drier should cure this problem. If the above actions do not resolve the problem, the evaporator assembly should be replaced External moisture (Condensate) in the area of forward / aft evaporator l. Leak in evaporator, or evaporator drainage system. l. If water is noted in the area near the evaporators. This is normally caused by a loose, cracked, plugged, or disconnected drain line. NOTE The drain line consists of a tube which extends from the lower surface of the evaporators through the outer contour of the helicopter. (Contact Air Comm Corporation Service Department for current pricing and availability of replacement components and parts).
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 66 Figure 27: General Arrangement – Air Conditioning System Installation. 407EC -614 & 616 Evaporator Instl 407EC -802 & 804 Electrical Instl
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 67 Figure 28: Air Conditioning System Electrical Schematic (Dual Forward Evaporator System)
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 68 Figure 29: Electrical Schematic – Temperature Control Circuitry & Transient Suppression Circuitry / Wiring Schematic (Dual and Single Forward Evaporator Systems)
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 69 Figure 30: Refrigerant Plumbing Schematic (Dual Forward Evaporator System) Through 1st Quarter 2015
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 70 Figure 31: Refrigerant Plumbing Schematic (Dual Forward Evaporator System) After March 1, 2015
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 71 Figure 32: Air Conditioning System Electrical Schematic (Single Forward Evaporator System)
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 72 Figure 33: Refrigerant Plumbing Schematic (Single Forward Evaporator System)
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 73 APPENDIX A Weight and Balance Information Weight breakdown – Bell 407 Air Conditioner System: Ref. Drawings 407EC-201, 407EC-202, 407EC-203 NOTE The weight change between the 407EC-201, 407EC-202, and the 407EC- 203 installations is negligible. Dwg 407EC-201-1 Single LH Fwd Evaporator with 407EC-620-1 Panasonic Motor Install Dwg 407EC-201-2 Dual Fwd Evaporator with 407EC-620-1 Panasonic Motor Install Dwg 407EC-201-3 Single RH Fwd Evaporator with 407EC-620-1 Panasonic Motor Install Wt (lbs) Arm (in) M (in-lb Total (-1 & -3 Single Fwd Evap) 94.57 138.0 13052 Total (-2 Dual Fwd Evaps) 104.77 126.5 13256 Dwg 407EC-201-2 Dual Fwd Evaporator with 407EC-620-2 High Output Advanced Industries Motor Install Wt (lbs) Arm (in) M (in-lb Total (-2 Dual Fwd Evaps) 108.74 128.5 13978 Dwg 407EC-201-1 Single LH Fwd Evaporator with 407EC-622-1 FASCO Motor Install Dwg 407EC-201-2 Dual Fwd Evaporator with 407EC-622-1 FASCO Motor Install Dwg 407EC-201-3 Single RH Fwd Evaporator with 407EC-622-1 FASCO Motor Install Wt (lbs) Arm (in) M (in-lb) Total (-1 & -3 Single Fwd Evap) 95.27 138.3 13179 Total (-2 Dual Fwd Evaps) 105.47 126.9 13383 Dwg 407EC-202-1 Single LH Fwd Evaporator with 407EC-622-1 FASCO Motor Install Dwg 407EC-202-2 Dual Fwd Evaporator with 407EC-622-1 FASCO Motor Install Dwg 407EC-202-3 Single RH Fwd Evaporator with 407EC-622-1 FASCO Motor Install Wt (lbs) Arm (in) M (in-lb) Total (-1 & -3 Single Fwd Evap) 95.27 138.3 13179 Total (-2 Dual Fwd Evaps) 105.47 126.9 13383