Home
>
AirComm Corporation
>
Air Conditioner
>
AirComm Corporation Bell 407 Air Conditioner Instructions for Continued Airworthiness User Manual
AirComm Corporation Bell 407 Air Conditioner Instructions for Continued Airworthiness User Manual
Have a look at the manual AirComm Corporation Bell 407 Air Conditioner Instructions for Continued Airworthiness User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 74 AirComm Corporation manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 34 CAUTION When reclaiming refrigerant, be sure to note any oil that is removed from the system, and replace the lost oil before or during re-servicing. Maintaining a proper oil and refrigerant charge is critical to the life of the compressor assembly. Excessive system oil charge will reduce cooling performance. 5. AMBIENT TEMPERATURE EFFECTS ON SERVICING Running the system when the ambient temperature is below 60 OF will present unusual (low) suction and discharge pressures on system gauges. An overcharge condition is likely if the process described in the previous paragraphs A through G is followed when the ambient temperature is below 60 OF. Running the air conditioning system when the outside air temperature is appreciably colder than the normal design operating temperatures may result in damage to the compressor. The following guidelines will provide means to mitigate the chances of system damage. The following assumes that the system is either a freshly installed system or a previously operated system with a newly installed compressor. Ambient temperature above 60OF: If the system was charged by refrigerant weight utilizing a charging station and the compressor has not been rotated since the oil and refrigerant were added, then manually rotate the compressor shaft clockwise a minimum of 10 full revolutions prior to running the compressor. A socket or wrench applied to the shaft nut is the recommended method. Always rotate clockwise to insure against loosening the compressor shaft nut. If the system was charged per Section 3 paragraph F of this Chapter then disregard manual rotation. Operate system normally, check for evaporator fan operation on both high and low speed settings. Insure that condenser fans are operating and airflow direction is correct. Ambient temperature between 60 OF and 80 OF: At these ambient temperatures system charging is to be accomplished by refrigerant weight. The method mentioned in Chapter 6, Section 3, Paragraph F (above) is not applicable at these condenser inlet temperatures. It is recommended that the aircraft heater be used during air conditioner system testing in order to provide a heat load to the evaporators.
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 35 Manually rotate the compressor shaft clockwise a minimum of 10 full revolutions prior to running of compressor. A socket or wrench applied to the shaft nut is recommended method. Always rotate clockwise to insure against loosening the compressor shaft nut. Normal suction and discharge pressures are not expected under these conditions and the evaporators may be cold enough to cause the freeze switch to activate and the bypass valve to open and close in a cyclic pattern. Even though the bypass valve may be cycling this test may be conducted for sufficient time to thoroughly check for condenser blower and fan operation. Check for evaporator fan operation on both high and low speed settings. Insure that the condenser fan is operating and the airflow direction is correct. Low side pressure may be observed to be higher than expected when the bypass valve is open. Ambient Temperatures between 60 OF and 32 OF: At these ambient temperatures system charging is to be accomplished by refrigerant weight. The method mentioned in Chapter 6, Section 3, Para. F (above) is not allowed at these condenser inlet temperatures. It is required that the aircraft heater, or another means of elevating the evaporator inlet air, be used during air conditioner system testing in order to provide a heat load to the evaporators. It is recommended that the aircraft be warmed in a heated hangar immediately prior to running the air conditioner test. Upon removing the aircraft from the heated environment the test should be started within ten minutes or as soon as practical. Manually rotate the compressor shaft clockwise a minimum of 10 full revolutions prior to running of compressor. A socket or wrench applied to the shaft nut is recommended method. Always rotate clockwise to insure against loosening the compressor shaft nut. Normal suction and discharge pressures are not expected under these conditions and the evaporators may be cold enough to cause the freeze switch to activate and the bypass valve to open and close in a cyclic pattern. At these ambient temperatures this test should not be conducted for more than 15 minutes. Testing the evaporator fan operation using the vent position prior to rolling out of the hangar and prior to running the air conditioner system is recommended. Check for evaporator fan operation on both high and low speed
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 36 settings. Insure that condenser fan is operating and the airflow direction is correct. Ambient Temperature less than 32 OF: There is no safe way to operate the air conditioning compressor with ambient temperatures below 32 OF. Much of the system can be tested for proper operation even though the compressor cannot be run. Charge the system by refrigerant weight only. Manually rotate the compressor shaft clockwise a minimum of 10 full revolutions. A socket or wrench applied to the shaft nut is recommended method. Always rotate clockwise to insure against loosening the compressor shaft nut. Temporarily disconnect the wire energizing the compressor clutch. Run the aircraft and turn the switch to air conditioning. Check the condenser fan for operation and correct direction of airflow. Check evaporator fans for airflow on both high and low settings. 6. PURGING PROCEDURE If the system has become contaminated or if the amount of oil in the system is unknown, the following purge steps will prep the system for charging. 1. Remove all refrigerant from the system and discard. Ensure the charging station is cleaned afterwards from the contaminated oil and refrigerant. 2. Disconnect all tubing and hoses from the system components. 3. Purge all hoses and tubes using solvents specifically made for air conditioning systems such as Four Seasons Dura II A/C flush solvent (Isopropyl alcohol or Denatured alcohol are acceptable substitutes). A/C flushing equipment available from sources such as hecatinc.com is also recommended. 4. (This step does not need to be completed if the compressor is being replaced) Remove the compressor from the aircraft, remove the drain plug and let the compressor drain. Rotate the compressor and allow it to drain again. Repeat this process until the compressor no longer has fluid inside. Do not use solvent to clean the compressor. This will damage and possibly destroy the compressor. Add 8.0 ounces of Ultra PAG oil to the compressor (see section 3.0 below) and ensure the O- ring on the drain plug is undamaged and retighten. 5. Purge the evaporators using air conditioner solvent (or equivalent i.e. Isopropyl alcohol, Denatured alcohol). Flush the evaporator in the same direction as refrigerant
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 37 flow. The solvent should enter from the expansion valve side and exit on the discharge side until the solvent runs out clean. 6. Purge the condenser using air conditioner solvent (or equivalent i.e. Isopropyl alcohol, Denatured alcohol). 7. Flush the bypass valve with air conditioner solvent. Do not use pressure to force solvent through the valve. 8. Replace the receiver drier bottle. THIS IS CRITICAL AND MUST BE PERFORMED. 9. Reconnect all components. Replace O-rings as needed. 10.Reconnect the compressor hose and place the system on a constant vacuum for 1 hour minimum. 11. Service the system with fresh R134a refrigerant and run an operational check out. 7. LUBRICATION INFORMATION SYSTEM REFRIGERANT & OIL CHARGE System Description Refrigerant Charge Oil Charge 407 Air Conditioner Single Forward Evaporator 2.4 lbs. 1.1 kg. 8.0 fl. oz. 237 ml. 407 Air Conditioner Dual Forward Evaporator 2.6 lbs. 1.2 kg. 8.0 fl. oz. 237 ml. CAUTION This system may be serviced with either Polyolester (POE) or Double End Capped Polyalkylene Glycol (DEC PAG) oil. Polyalkylene Glycol oil is preferred due to its superior lubricating properties and improved compressor service life. There are several types of PAG available. Only the “Double End Capped” type is permissible in Air Comm Corporation air conditioning systems. Double End Capped PAG oil is available from Air Comm Corporation in 8 ounce bottles (P/N ES94006-13). Mixing of POE and PAG is acceptable. Disregard previous statements to the contrary. They referenced PAG oil that was not “Double End Capped”. Current versions of compressors are designed to be operated using PAG oil. Testing by Air Comm Corporation has shown that “Double End Capped” PAG is compatible with POE and can therefore be mixed. “Double End Capped” is a reference to the chemical structure of the molecule and not to the container. Do not use Mineral oil in this system with R134a refrigerant. Do not use any refrigerant oil other than Double End Capped Polyalkylene Glycol (also known as “ULTRA PAG”) or Polyolester (also POE).
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 38 Containers of DEC PAG or POE will absorb moisture if left open (hygroscopic). Keep containers tightly capped when not in use and keep all system components capped while servicing system. The oil charge is continuously circulated by the refrigerant during the operation of the system. A quantity of oil is trapped by the compressor, as well as by other parts of the system. The following chart may be used to calculate the amount of oil to be added in case a component is being replaced with a new part. Component Oil Amount Compressor See Instructions Evaporator 1.0 oz. per evaporator Condenser 1.5 oz. Receiver Drier 1.5 oz. Hose - Vapor 1.0 oz. per 10 foot Hose – Liquid 1.0 oz. per 20 foot Compressor Replacement – To properly calculate the amount of oil required in the replacement compressor, it is necessary to pour the oil out of the old compressor into a clean container. Drain the oil out of the fill plug hole and then pour oil out of the suction and discharge ports while rotating the center shaft clockwise. Measure the total amount of oil removed from the old compressor. Add ½ oz. to the total measured to account for unrecoverable oil in the old compressor. This total is what is needed in the new compressor. Use a minimum of 3 oz. if less was recovered. New compressors come from Air Comm charged with 8 oz. (237 cc) of oil. This should be adjusted according to the amount of oil recovered from the old compressor and any other components being replaced. The receiver drier should always be replaced when the compressor is replaced or when the system has been open for an appreciable time, which accounts for another 1.5 oz. of oil that should be added. Below is an example of a compressor (and receiver drier) replacement for illustration: Evacuating the system recovers 1.5 oz. of oil. Draining the old compressor recovered 2.0 oz. of oil. Adding 0.5 oz. of residual unrecoverable oil in the compressor gives 2.5 oz. The new receiver/drier requires an additional 1.5 oz., plus 1.5 oz. lost when the refrigerant was evacuated from the system. So the total oil needed in the replacement compressor for this case is 5.5 oz. Since the new compressor comes with 8 oz. of oil, remove the oil fill plug and pour out 2.5 oz. of oil. Torque compressor oil fill cap to 132-216 in-lb. The total system oil charge is 7.5 – 8.0 fl. oz. (237 ml.) of Refrigerant Oil. The compressor is charged with 8.0 fl. oz. of oil at the factory.
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 39 NOTE Maintaining the correct amount of refrigerant and refrigerant oil in the system is critical for ensuring the long life of the compressor. The quantity of lubrication in the system is critical. If too little lubrication is in the system the compressor life may be reduced. No other component in the A/C system requires lubrication. Too much lubricant in the system will retard heat transfer in the evaporator and condenser coils and reduce the cooling capacity of the system. The Service Ports for this system are located in the upper aft right-hand corner of the baggage compartment. 8. SYSTEM LEAK CHECK Identification and elimination of system fitting leaks is extremely important to ensure a trouble-free operation of this system. A system which contains a partial charge of refrigerant can be leak tested with the aid of an electronic leak detector, and be recharged without evacuating the system. A new or empty system can be pressurized with nitrogen 70-80 psi (5.1-5.6 kg/cm) or R134a 50 psi (3.5 kg/cm) to conduct a leak survey. DO NOT USE COMPRESSED AIR. Compressed air will introduce moisture into the system, which will degrade the operation of the system. The preferred method is to use an electronic leak detector in conjunction with a small charge of R134a refrigerant. All checks done in this manner should be conducted with the air conditioner off. Since the refrigerant is heavier than air, leaks are most likely to be detected on the underside of hoses and fittings. Refrigerant will collect in low areas and provide erroneous leak detection. A stream of compressed air from a nozzle may be useful in clearing the area just prior to conducting a leak test. If the nitrogen method is used, it will be necessary to mix together a water and mild soap solution. Each fitting or suspected leak area should be brushed with this soap solution and watched for evidence of bubbles formed by the escaping nitrogen. If a leak is detected at an O-ring fitting check to ensure proper torque has been applied to the fitting. If the system continues to leak, reclaim the system refrigerant, and install a new O-ring.
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 40 NOTE Ensure that the O-ring is lubricated with refrigerant oil prior to its installation. A small amount of leakage (approximately one ounce per year) past the compressor shaft seal is normal. Most leak detectors are sensitive enough to show a leak of this magnitude. 9. SUGGESTED EQUIPMENT FOR SERVICING A. Recovery / Recycling / Recharging Station Any model manufactured to comply with specification SAE J2788 B. Electronic Leak Detector (R134a compatible) (Example: Micro-Tech III, Robinair, Snap-on, or equivalent) C. Manifold and gauge set (R134a compatible) (Example: Robinair, Snap-on, or equivalent) 10. CONSUMABLE MATERIALS A. Refrigerant: This system is to be charged with DuPont, or equivalent HFC R134a refrigerant only. B. Lubricant: Ultra PAG refrigerant oil. See Lubrication information, pg. 35. C. O-rings: As this system is charged with R134a refrigerant, it must be fitted with Highly Saturated Nitrile (HSN) O-rings. This system incorporates two different O-ring fittings, TORQ-LOK® and Insert. The HSN O-rings for the TORQ LOK® fittings are BLACK in color and the HSN O-rings for the Insert fittings are GREEN in color. D. Loctite thread sealer 554 (or equivalent). E. Torque-Seal Anti Sabotage Lacquer. 6. SUGGESTED SPARES LIST Item Part Number Affectivity Fwd Evaporator Blower Motor ES61064-10 Aft Evaporator Blower Motor ES61062-2 Kit S/N 1 thru 131 (See Note) Aft Evaporator Blower Motor ES61142-1 Kit S/N 132 & Subsequent Condenser Blower Assembly ES73186-1 (ES73190-1 ALT) Compressor Assembly S-3008EC-6
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 41 Compressor Drive Belt 7270 (7265 ALT) Receiver / Drier Bottle ES43034-1 Binary Switch ES57178-1 By-pass Valve ES26194-2 Kit S/N 1 thru 146 By-pass Valve ES26194-25 Kit S/N 147 & subsequent Relay – Evaporator W389CX-8 Relay – Condenser W389CX-13 Relay – AC Control W389DCX-3 Temperature Control Switch ES57170-3 HSN O-rings; Insert type (Green) Size #6 O-ring ES44010-2 #8 O-ring ES44010-3 #10 O-ring ES44010-4 HSN O-rings; TORQ LOK® Type (Black) #6 O-ring ES44012-2 #8 O-ring ES44012-3 #10 O-ring ES44012-4 Note: ES61062-2 Motor is no longer available. Order replacement S-6102EC-4 Blower Assembly and S-6058EC-10 Elbow.
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 42 CHAPTER 7 STANDARD PRACTICES INFORMATION 1. FITTING TORQUING PROCEDURES AND TORQUE VALUES INSERT O-RING FITTINGS TORQ-LOK® FITTINGS Apply a thin coating of refrigerant oil to O-ring and Female side of fitting. Confirm there is no damage (nicks, dirt, etc.) on fittings. Slide B-nut back away from the end of the tube so you can see the O-ring as you slide the fitting together. Be careful not to pinch O-ring during assembly. Engage the male end into the female fitting being careful to maintain alignment. The male flange should seat fully against the female fitting without the O-ring being pinched. It is important to hold the fitting together while sliding the B-nut forward and engaging the threads. Tighten the B-nut by hand and then torque as follows. Tightening specifications CAUTION: ALWAYS USE BACK UP WRENCH. EXCESSIVE TORQUE WILL DAMAGE THE JOINT, COMPROMISING THE INTEGRITY OF THE SEAL. Insert O-Ring Fittings (regardless of size): Hand tighten, then turn an additional 60 deg. (one flat on the nut). TORQ-LOK ® fittings (regardless of size): Hand tighten, then turn an additional 30 deg. INSERT O-RING FITTINGS TORQ-LOK® FITTINGS Once the system is charged, check each fitting with an electronic leak detector. (An electronic leak detector is the only reliable method of checking for refrigerant leaks).
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 43 Once the fittings have been checked and are found to be free of leaks, torque seal as appropriate. 2. REMOVAL & REPLACEMENT OF CONDENSER BLOWER MOTOR & FAN ASSEMBLY REMOVAL CAUTION It is recommended that the battery and external power be disconnected before starting work. A. Remove the (13) thirteen AN525-10R12 Screws that attach the S- 7062EC-1 Blower assembly to the lower contour of the belly panel. This will allow the condenser scoop assembly to pivot on the forward hinged support plate. CAUTION Be sure to support the blower assembly when removing the attaching hardware to prevent damage to the condenser housing, blower assembly, or the aircraft. B. Remove safety wire that secures the (4) AN3H-3A bolts (2) two on each side that attach the ES73186-1 Blower motor & Fan assembly to the condenser scoop assembly, and remove bolts. C. Disconnect the ES73186-1 Blower motor & Fan assembly at the Molex connector. D. Once the mounting bolts have been removed, the blower can be removed and replaced as required. REPLACEMENT A. Locate the new blower assembly and install the fasteners, torqueing the bolts to 50 to 70 inch lbs. (5.7-8.0 Nm) and safety using .032 safety wire. B. Reconnect the Molex connector. C. Reinstall the (13) thirteen AN525-10R12 Screws that secure the S- 7062EC-1 Blower assembly to the lower contour of the belly panel. D. Apply power, and operate the Air conditioner by placing the control switch in the A/C position several times to ensure there is no binding and for proper operation of the Blower motor & Fan assembly.