AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 34 CAUTION When reclaiming refrigerant, be sure to note any oil that is removed from the system, and replace the lost oil before or during re-servicing. Maintaining a proper oil and refrigerant charge is critical to the life of the compressor assembly. Excessive system oil charge will reduce cooling performance. 5. AMBIENT TEMPERATURE EFFECTS ON SERVICING Running the system when...
Page 42
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 35 Manually rotate the compressor shaft clockwise a minimum of 10 full revolutions prior to running of compressor. A socket or wrench applied to the shaft nut is recommended method. Always rotate clockwise to insure against loosening the compressor shaft nut. Normal suction and discharge pressures are not expected under these conditions and the evaporators may be cold enough to cause the...
Page 43
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 36 settings. Insure that condenser fan is operating and the airflow direction is correct. Ambient Temperature less than 32 OF: There is no safe way to operate the air conditioning compressor with ambient temperatures below 32 OF. Much of the system can be tested for proper operation even though the compressor cannot be run. Charge the system by refrigerant weight only. Manually rotate the...
Page 44
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 37 flow. The solvent should enter from the expansion valve side and exit on the discharge side until the solvent runs out clean. 6. Purge the condenser using air conditioner solvent (or equivalent i.e. Isopropyl alcohol, Denatured alcohol). 7. Flush the bypass valve with air conditioner solvent. Do not use pressure to force solvent through the valve. 8. Replace the receiver drier bottle. THIS IS...
Page 45
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 38 Containers of DEC PAG or POE will absorb moisture if left open (hygroscopic). Keep containers tightly capped when not in use and keep all system components capped while servicing system. The oil charge is continuously circulated by the refrigerant during the operation of the system. A quantity of oil is trapped by the compressor, as well as by other parts of the system. The following chart...
Page 46
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 39 NOTE Maintaining the correct amount of refrigerant and refrigerant oil in the system is critical for ensuring the long life of the compressor. The quantity of lubrication in the system is critical. If too little lubrication is in the system the compressor life may be reduced. No other component in the A/C system requires lubrication. Too much lubricant in the system will retard heat transfer in the evaporator and condenser...
Page 47
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 40 NOTE Ensure that the O-ring is lubricated with refrigerant oil prior to its installation. A small amount of leakage (approximately one ounce per year) past the compressor shaft seal is normal. Most leak detectors are sensitive enough to show a leak of this magnitude. 9. SUGGESTED EQUIPMENT FOR SERVICING A. Recovery / Recycling / Recharging Station Any model manufactured to comply with specification...
Page 48
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 41 Compressor Drive Belt 7270 (7265 ALT) Receiver / Drier Bottle ES43034-1 Binary Switch ES57178-1 By-pass Valve ES26194-2 Kit S/N 1 thru 146 By-pass Valve ES26194-25 Kit S/N 147 & subsequent Relay – Evaporator W389CX-8 Relay – Condenser W389CX-13 Relay – AC Control W389DCX-3 Temperature Control Switch ES57170-3 HSN O-rings; Insert type (Green) Size #6 O-ring ES44010-2 #8 O-ring ES44010-3 #10 O-ring ES44010-4 HSN...
Page 49
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 42 CHAPTER 7 STANDARD PRACTICES INFORMATION 1. FITTING TORQUING PROCEDURES AND TORQUE VALUES INSERT O-RING FITTINGS TORQ-LOK® FITTINGS Apply a thin coating of refrigerant oil to O-ring and Female side of fitting. Confirm there is no damage (nicks, dirt, etc.) on fittings. Slide B-nut back away from the end of the tube so you can see the O-ring as you slide the fitting together. Be careful not to pinch...
Page 50
AIR CONDITIONER SERVICE MANUAL 407EC-200M-2 Revision 11 Page 43 Once the fittings have been checked and are found to be free of leaks, torque seal as appropriate. 2. REMOVAL & REPLACEMENT OF CONDENSER BLOWER MOTOR & FAN ASSEMBLY REMOVAL CAUTION It is recommended that the battery and external power be disconnected before starting work. A. Remove the (13) thirteen AN525-10R12 Screws that attach the S- 7062EC-1 Blower assembly to the lower contour...