Aiphone IS Series Installation Manual
Have a look at the manual Aiphone IS Series Installation Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 161 Aiphone manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
11 ■ Connections 1CX1 1CX2M1 M21MX1 1MX21MX3 2MX12MX2 2MX3 M3 M4D1 D2IP1LAN IP2 IP3 D3 D4 2CX1 2CX23CX1 3CX24CX1 4CX2 P1P2P3P4L1L2L3L4L5L6L7L8S1 E S2 E S3 E S4 E IS-RCUMASTER STATIONIS-SCUIS-IPC DC48V DOOR/SUB STATIONVIDEO/AUDIO PA OUTPUT (600Ω)CONTACT INPUTCHIME INPUT (600Ω)ETHERNETVIDEO OUTPUTCONTACT OUTPUT (AC/DC24V 0.5A) B2B1 V1 V2 CAT5e/6 200m (650)CAT5e/6 200m (650)CAT5e/6 300m (980)CAT5e/6 300m (980) 10m (33)15m (50) 200m (650)CAT5e/6 150m (490)Coax 15m (50) NTSC15m (50) NTSC *2 *3 *4 *1 D C 2C M IP1IP2IP3MX1MX2MX3 Coax CX1/IP1CX2/IP2 PT BNC connector BNC connector BNC connectorBNC connector φ0.65-1.2mm (22-16 AWG) φ0.65-1.2mm (22-16 AWG) 15m (50)φ0.65-1.2mm (22-16 AWG) 15m (50) φ0.8-1.2mm (20-16 AWG) NPNP P P2C 2C 2C *5 NP 2C φ0.65-1.2mm (22-16 AWG) 15m (50) P 2C φ0.65-1.2mm (22-16 AWG) 15m (50)NP 2C φ0.65-1.2mm (22-16 AWG) NP 2C φ0.65-1.2mm (22-16 AWG) CAT5e/6 (x3)CAT5e/6 (x3) *1: This connection is needed when a PA amplifi er that needs a trigger input is connected. (Up to AC/DC 24V 0.5A) *2: This connection is needed when a sound source etc. that needs a trigger input is connected. (Up to AC/DC 24V 0.5A) Connect a timer to the CONTACT INPUT terminals when an external sound source device (CD player etc.) that does not have a timer function is connected. *3: This connection is needed when a sound source that has a trigger output is connected. *4: Refer to the SETTING MANUAL for connection and settings. *5: Do not install two power supplies in parallel to a single input. Be sure to connect a single power supply unit to a control unit. *6: Do not use an external sound source as background music. If the background music is interrupted by another performance during chime paging, the chime paging will not be restored after the performance ends. *7: Outputs images only from a video door station connected to this unit. *8: Output specifi cations Output method N/O or N/C dry closure contact Voltage between terminals 24V AC, 0.5A (resistive load) 24V DC, 0.5A (resistive load) Minimum overload (AC/DC): 100mV, 0.1mA NOTES: Do not use the unoccupied terminals and ports for other purposes. In order to prevent miswiring, label both ends of each cable with the unit and terminal names to which they are to be connected. For connecting other manufacturer’s products, refer to the instruction manuals for those products. The illustration of the unit’s front panel differs from the actual one. This is for simplifying the connection diagram. *9: Input specifi cations Input method N/O or N/C dry closure contact (start signal only detection method) Detection confi rmation time100 ms or more Contact resistance During N/O dry closure: Less than 700 Ω During N/C dry closure: At least 4 k Ω Terminal short current Less than 10 mA Voltage between terminalsLess than 5 V DC (when open between terminals) Monitor 1, Recorder 1Monitor 2, Recorder 2 Door station (IS-DV/IS-DVF/ IS-SS)Power supply unit (IS-PU-UL/IS-PU-S) Master station (IS-MV)Contact output *8(Electric door strike, strobe light, etc.) PA output (50mVrms, 600Ω) PA amplifi erExternal sound source such as CD player, etc. *6 Chime input (50mVrms, 600Ω) Contact input *9 Sensor, etc. Room sub control unit (IS-RCU)Add-on control unit (IS-SCU)PC for setting the system Room sub station (IS-RS)IP control unit (IS-IPC) or (non-shielded) (non-shielded)(non-shielded)(non-shielded)(non-shielded) (non-shielded) (non-shielded) AC transformer NP: Non-polarized P: Polarized *7 *7
12 Add-on control unit ( IS-SCU) ■ Part names NOTE: The illustration of the unit may differ from the actual one. ■ Specifi cations Add-on control unit (IS-SCU) Power source 48V DC (supplied from the power supply unit) Current consumption Max. 1.2A Ambient temperature 0 - 40°C (+32°F - +104°F) Talk channels ~Video channelsLocal system: 2 talk & 2 video channels, 1 chime Master station(s) Max. 8 Video door station(s) Max. 8 Audio door station(s) Room sub station(s) Video outputNTSC BNC (Video channel 1,2) Mounting Rack-mount (19-inch, 2U rack) or wall mount Material Steel plate Color BlackPOWER switch Turns the power ON ( ) or OFF (). VIDEO OUTPUT port 1 and port 2 Central control unit (IS-CCU) ports * No connection allowed. CONTACT OUTPUT terminals PA (Paging) OUTPUT terminals MASTER STATION ports VIDEO/AUDIO DOOR/SUB STATION portsPOWER LED (green) Lights up when the power is ON. POWER terminals ID setting switch (→P.13) STATUS LED (green) Blinks when this unit is initialized or an error*1 occurs. The LED will light up when this unit returns to the normal state. * 1: Communication error in a unit connected to this unit, or between this unit and a unit connected to it, etc.
13 ■ Connections M1 M2M3 M4M5 M6M7 M8D1 D2MX1MX3 ID 1 2 MX2 D3 D4D5 D6D7 D8 P1P2P3P4L1L2L3L4 MASTER STATIONIS-CCU DC48V VIDEO/AUDIO DOOR/SUB STATION PA OUTPUT (600Ω)VIDEO OUTPUTCONTACT OUTPUT (AC/DC24V 0.5A) V1 V2 CAT5e/6 300m (980)CAT5e/6 300m (980) 15m(50) 200m (650)CAT5e/6 150m (490)Coax 15m (50) NTSC15m (50) NTSC *1 DC 2C M 1MX11MX21MX3 CoaxPT *2 φ0.8-1.2mm (20-16 AWG)CAT5e/6 (x3) BNC connector BNC connector BNC connectorBNC connector P NP 2C φ0.65-1.2mm (22-16 AWG) 15m (50) NP 2C φ0.65-1.2mm (22-16 AWG) NP 2C φ0.65-1.2mm (22-16 AWG) *1: This connection is needed when a PA amplifi er that needs a trigger input is connected. (Up to AC/DC 24V 0.5A) *2: Do not install two power supplies in parallel to a single input. Be sure to connect a single power supply unit to a control unit. *3: Setting the ID setting switch ID No. Switch position Description ID 1ON OFFSet to this position when this unit is connected to 1MX1, 1MX2 and 1MX3 ports of IS-CCU. ID 2 ON OFFSet to this position when this unit is connected to 2MX1, 2MX2 and 2MX3 ports of IS-CCU. *4: Refer to “Output specifi cations” (→P.11). NOTES: Do not use the unoccupied terminals and ports for other purposes. In order to prevent miswiring, label both ends of each cable with the unit and terminal names to which they are to be connected. For connecting other manufacturer’s products, refer to the instruction manuals for those products. The illustration of the unit’s front panel differs from the actual one. This is for simplifying the connection diagram. Door station (IS-DV/IS-DVF/ IS-SS)Power supply unit (IS-PU-UL/IS-PU-S) Master station (IS-MV)Central control unit (IS-CCU) Room sub station (IS-RS)ID setting switch *3 Contact output *4(Electric door strike, strobe light, etc.) Monitor 1, Recorder 1Monitor 2, Recorder 2 or (non-shielded) (non-shielded) (non-shielded)(non-shielded) AC transformer PA output (50mVrms, 600Ω) PA amplifi er NP: Non-polarized P: Polarized
14 Room sub control unit ( IS-RCU) ■ Part names NOTE: The illustration of the unit may differ from the actual one. ■ Specifi cations Room sub control unit (IS-RCU) Power source 48V DC (supplied from the power supply unit) Current consumption Max. 1.8A Ambient temperature 0 - 40°C (+32°F - +104°F) Talk channels Local system: 2 talk channels, 1 chime Audio door station(s) Room sub station(s)Max. 30 Mounting Rack-mount (19-inch, 2U rack) or wall-mount Material Steel plate Color Black CONTACT OUTPUT terminals PA (Paging) OUTPUT terminals AUDIO DOOR/SUB STATION ports Central control unit (IS-CCU) / IP control unit (IS-IPC) ports ID setting switch (→P.15)POWER terminals POWER switch Turns the power ON ( ) or OFF (). POWER LED (green) Lights up when the power is ON. STATUS LED (green) Blinks when this unit is initialized or an error*1 occurs. The LED will light up when this unit returns to the normal state. * 1: Communication error in a unit connected to this unit, or between this unit and a unit connected to it, etc.
15 ■ Connections C1 C2CX1/IP1 ID 1 2 3 4CX2/IP2 C3 C4C5 C6C7 C8C9 C10C11 C12C13 C14C15 C16C17 C18C19 C20C21 C22C23 C24C25 C26C27 C28C29 C30 P1P2P3P4L1L2L3L4 IS-CCU/ IS-IPC DC48V AUDIO DOOR/SUB STATION PA OUTPUT (600Ω)CONTACT OUTPUT (AC/DC24V 0.5A) CAT5e/6 300m (980)15m (50) 200m (650)CAT5e/6 150m (490) *1 CD 1CX11CX2 PT *2 10m (33) IP1IP2 CAT5e/6 (x2) CAT5e/6 (x2) φ0.8-1.2mm (20-16 AWG)2C P NP 2C φ0.65-1.2mm (22-16 AWG) NP 2C φ0.65-1.2mm (22-16 AWG) NP 2C φ0.65-1.2mm (22-16 AWG) 15m (50) *1: This connection is needed when a PA amplifi er that needs a trigger input is connected. (Up to AC/DC 24V 0.5A) *2: Do not install two power supplies in parallel to a single input. Be sure to connect a single power supply unit to a control unit. *3: Setting the ID setting switch ID No. Switch position Description ID 1 ON OFFSet to this position when this unit is connected to 1CX1 and 1CX2 ports of IS-CCU. Set to this position when this unit is connected to IS-IPC. ID 2 ON OFFSet to this position when this unit is connected to 2CX1 and 2CX2 ports of IS-CCU. ID 3 ON OFFSet to this position when this unit is connected to 3CX1 and 3CX2 ports of IS-CCU. ID 4 ON OFFSet to this position when this unit is connected to 4CX1 and 4CX2 ports of IS-CCU. *4: Refer to “Output specifi cations” (→P.11). NOTES: Do not use the unoccupied terminals and ports for other purposes. In order to prevent miswiring, label both ends of each cable with the unit and terminal names to which they are to be connected. For connecting other manufacturer’s products, refer to the instruction manuals for those products. The illustration of the unit’s front panel differs from the actual one. This is for simplifying the connection diagram. Audio door station (IS-SS)Power supply unit (IS-PU-UL/IS-PU-S) Central control unit (IS-CCU) IP control unit (IS-IPC) Room sub station (IS-RS)Contact output *4(Electric door strike, strobe light, etc.) or or (non-shielded)(non-shielded)(non-shielded) (non-shielded) ID setting switch *3 AC transformer PA output (50mVrms, 600Ω) PA amplifi erNP: Non-polarized P: Polarized
16 IP control unit ( IS-IPC) IPThis unit is needed to connect a local system to a standard (IP) system. ■ Part names NOTE: The illustration of the unit may differ from the actual one. ■ Specifi cations IP control unit (IS-IPC) Power source 48V DC (supplied from the power supply unit) Current consumption Max. 105mA Ambient temperature 0 - 40°C (+32°F - +104°F) Talk channels ~Video channels, other channels2 talk & 2 constrained video channels, 1 chime, and 1 telephone (North America only) Central control unit Max. 1 Room sub control unit LAN Ethernet (10 BASE-T, 100 BASE-TX) Mounting Rack-mount (19-inch, 2U rack) or wall-mount Material Steel plate Color BlackPOWER switch Turns the power ON ( ) or OFF (). POWER terminals LAN port CO port (Telephone) Link/ACT LED (green) Operates when this unit is connected to LAN.POWER LED (green) Lights up when the power is ON. Central control unit (IS-CCU) / Room sub control unit (IS-RCU) portsSTATUS LED (green) Blinks when this unit is initialized or an error* 1 occurs. The LED will light up when this unit returns to the normal state. * 1: Communication error in a unit connected to this unit, or between this unit and a unit connected to it, etc.
17 ■ Connections IP1 IP2 IP3LAN IS-RCU IS-CCU DC48V ETHERNET CO TELEPHONE 10m (33) 10m (33)15m (50) 2C IP1IP2IP3 φ0.8-1.2mm (20-16 AWG)IP1 IP2 IP3 IS-RCU IS-CCU CAT5e/6 (x3)10BASE-T 100BASE-TX 100m (330) CX1/IP1CX2/IP2 CAT5e/6 (x2) P *3 *1: When connecting a central control unit (IS-CCU) to this unit, connect it to the IP1, IP2 and IP3 ports. *2: When connecting a room sub control unit (IS-RCU) to this unit, connect it to the IP1 and IP2 ports. *3: Do not install two power supplies in parallel to a single input. Be sure to connect a single power supply unit to a control unit. NOTES: Do not use the unoccupied terminals and ports for other purposes. In order to prevent miswiring, label both ends of each cable with the unit and terminal names to which they are to be connected. For connecting other manufacturer’s products, refer to the instruction manuals for those products. The illustration of the unit’s front panel differs from the actual one. This is for simplifying the connection diagram. Power supply unit (IS-PU-UL/IS-PU-S) Central control unit (IS-CCU) *1 Room sub control unit (IS-RCU) *2PBX/Telephone (North America only)Switch (Hub) or (non-shielded)(non-shielded) P: Polarized
18 Color monitor master station (IS-MV) For the part names and their functions, see the OPERATION MANUAL.* ■ Accessories ~Mounting bracket × 1 ~Name card × 1 ~Desktop stand × 1 ~Screw (15mm (5/8), for wall-mounting) × 4 ~Tie-wrap × 1 ~Screw (25mm (1), for gang box) × 4 ~Name plate × 1 ~Screw (10mm (7/16), for desktop stand) × 4 ~China RoHS paper × 1 ■ Mounting When mounting on a wall Mounting bracket (attached to the unit with shipment) Mounting bracket (attached to the unit with shipment) 3-gang box The unit Screw (for gang box) × 4 (included) Option wires CAT5e/6 cable 83.5mm (3-5/16) 92mm (3-5/8) NOTE: A single-gang box can also be used for wiring. When using a single-gang box, fasten the mounting bracket to the wall directly by using the screw holes for 3-gang box. Screw (for wall-mounting) × 4 (included) The unit Fasten the mounting 1 bracket to the wall. Connect the CAT5e/6 cable 2 and option wires to the unit. Mount the unit on the 3 mounting bracket. Connect the CAT5e/6 cable and option wires to the unit and route them as shown. Filling in the target names on the name card 1 Remove the transparent name plate by pushing either upper or lower side of the plate. * Remove the name card if necessary. 2 Fill in the target names on the white space of the name card. 3 Replace the name plate. *1: The name plate and name card are attached to the unit with shipment. Name card × 1 (included*1) Name plate × 1 (included* 1)
19 When mounting on a desktop stand 30r 45r 60r ■ Connections M VVAA VIDEO OUTPUT AUDIO OUTPUT M1M4 CAT5e/6 Coax2C M1M8 CAT5e/6 P NP NTSC NOTES: Do not use the unoccupied terminals and ports for other purposes. In order to prevent miswiring, label both ends of each cable with the unit and terminal names to which they are to be connected. For connecting other manufacture’s products, refer to the instruction manuals for those products. The illustration of the unit’s rear panel differs from the actual one. This is for simplifying the connection diagram. NOTES: Attach the screws to the screw holes for 3-gang box on the mounting bracket to make both sides of the mounting bracket contact the desktop stand. If necessary, secure the CAT5e/6 cable with the tie-wrap (included). The unit Screw (for desktop stand) × 4 (included) Desktop stand (included) Set up the desktop 1 stand. Set up the desktop stand on * a level surface etc. so that it is stabilized. Fix the desktop stand in place if needed. The desktop stand allows you * to adjust it in 3 setup angles. Put the leg in a groove on the base that corresponds to the desired angle.Fasten the mounting 2 bracket to the desktop stand. Connect the CAT5e/6 cable 3 and option wires to the unit. Mount the unit on the 4 mounting bracket. Leg Base Central control unit (IS-CCU) Video output Monitor, etc. Audio output (50mVrms, 600Ω) Recorder, etc. Add-on control unit (IS-SCU) or (non-shielded) 15m (50)10m (33) 300m (980) 300m (980)(Select one port.) (Select one port.) (non-shielded) Mounting bracket (attached to the unit with shipment) Option wiresCAT5e/6 cable NP: Non-polarized P: Polarized
20 Vandal-resistant video door station (IS-DV, IS-DVF), Vandal-resistant audio door station (IS-SS) ■ Accessories ~Screw (for wall-mounting) × 4 (IS-DV only) ~Special screwdriver × 1 ~Anchor × 4 (IS-DV only) ~Back box × 1 (IS-DVF and IS-SS only) ~Transparent name plate × 2 (IS-DV and IS-DVF only) ~China RoHS paper × 1 ~Special screw × 4 (IS-DVF and IS-SS only) ■ Mounting locations (IS-DV and IS-DVF) Do not install this unit in any of the following locations where lighting or the ambient environment could impact the display on the video monitor due to the characteristics of the door stations camera. a Locations subject to direct sunlightb There is a white wall behind the callerc Other locations subject to strong lighting or backlighting conditions ■ Mounting positions and image view area of video door station (IS-DV and IS-DVF) Wide picture An area over a range of approx. 170° in a 500 mm (20) radius from the camera displays. (The display range is a rough estimation and may change due to the installation environment.) Up/DownMounting position 1,500 mm (5)Mounting position 1,300 mm (4 3) Left/Right Unit centerApprox. 1,050 mm (3 5) Approx. 2,050 mm (6 9) Approx. 1,000 mm (3 4) 1,500 mm (5) 500 mm (20) 500 mm (20) Approx. 170° Approx. 1,050 mm (3 5) Approx. 1,850 mm (6 1) Approx. 800 mm (2 7)Unit center 1,300 mm (4 3) 500 mm (20) Up/Down Left/Right Zoom Unit center Approx. 2,300 mm (7 7) Approx. 850 mm (2 9) Approx. 1,450 mm (4 9) 500 mm (20)1,500 mm (5)Zoom Approx. 750 mm (2 5) Approx. 1,600 mm (5 4) Approx. 850 mm (2 9) 500 mm (20) Unit center 1,500 mm (5) Zoom 500 mm (20) Approx. 100 mm (4) Approx. 1,300 mm (4 3) Zoom 500 mm (20) Approx. 900 mm (3) Zoom 500 mm (20) Approx. 1,300 mm (4 3) Approx. 100 mm (4) Wide picture Zoom picture The zoom position can be changed. (Refer to the OPERATION MANUAL.) The factory setting is Center for Zoom mode.Approx. 1,050 mm (3 5) Approx. 700 mm (2 3) Approx. 900 mm (3) Objects appear smaller due to greater distortion in the surrounding sections compared to the central section, but a wider area is displayed. The display range is a rough estimation and may change due to the installation environment. Zoom picture (when mounting position is 1,500 mm (5)) Zoom 1,500 mm (5) Approx. 1,900 mm (6 3) Approx. 700 mm (2 3) Approx. 1,200 mm (3 11)Unit center 500 mm (20)