ADDER ePower Switch 8 Slave Manual
Here you can view all the pages of manual ADDER ePower Switch 8 Slave Manual. The ADDER manuals for Extender are available online for free. You can easily download all the documents as PDF.
Page 11
Page | 9 ePowerSwitch 8XS 2. Allocate an address to each Satellite by positioning the address selection DIP-switches marked Slct on the front panel according to the following table. Remarks − Unplug the power cords of the ePowerSwitch 8XS before changing its DIP switches. − Do NOT use the same address for two different Satellites. Satellite Address DIP-Switch 1 DIP-Switch 2 DIP-Switch 3 DIP-Switch 4 1 Off Off Off Off 2 [ON] Off Off Off 3 Off [ON]...
Page 12
Page | 10 User Guide 5. Controlling the Satellite power outlets through the Master Web Server Start your Web browser and type the IP address of your ePowerSwitch Master or your VizioGuard RMS system. The browser displays the authentication dialog box. Enter a user name and its corresponding password. If you log in as system administrator, you will be able to: - control individually all the power outlets and all the power outlets groups of the Master, - control all the power outlets...
Page 13
Page | 11 ePowerSwitch 8XS 6. Controlling the Satellite power outlets using a Terminal Connection The power outlets of the ePowerSwitch 8XS can be individually controlled and the status of each power outlet can be read out using a simple ASCII protocol through a serial connection. The connection can be done either using the RS232 or the RS485 port of the ePowerSwitch 8XS. 6.1. Using the RS232 port (SubD-9F connector marked RS232 on the front panel). In this case, use the supplied RS232...
Page 14
Page | 12 User Guide 6.3.1. Controlling of the power outlet(s) This command enables to control individually each power outlet or all power outlets of the same ePowerSwitch 8XS in one command. Command to be sent to the ePowerSwitch 8XS: Pxy=z[CR] Pxy=z,t 1[CR] Pxy=z,t 1,t2[CR] Reply from the ePowerSwitch 8XS: Pxy=z[CR] Pxy=z,t 1[CR] Pxy=z,t 1,t2[CR] Explanations: Parameter Value Function/Remark x address of the ePowerSwitch 1 to 16 specifies the address of the ePowerSwitch 8XS...
Page 15
Page | 13 ePowerSwitch 8XS 6.3.2. Reading out the power outlet status This command enables to read out the status of each power outlet. Command to be sent to the ePowerSwitch 8XS: Rxy[CR] Reply from the ePowerSwitch 8XS: Rxy=z[CR] Explanations: Parameter Value Function/Remark x address of the ePowerSwitch 1 to 16 specifies the address of the ePowerSwitch 8XS y number of the Power Outlet 1 to 8 specify the number of the power outlet z status 0 status of the corresponding...
Page 16
Page | 14 User Guide 6.3.3. Setting of the power up delays This command enables to set the Power Up Delay individually for each power outlet. The Delay value can be between 1 and 255 seconds (4 min 15 sec). Command to be sent to the ePowerSwitch 8XS: TUxy=z[CR] Reply from the ePowerSwitch 8XS: TUxy=z[CR] Explanations: Parameter Value Function/Remark x address of the ePowerSwitch 1 to 16 specifies the number of the ePowerSwitch 8XS y number of the power outlet 1 to 8...
Page 17
Page | 15 ePowerSwitch 8XS 6.3.5. Setting the restart delays This command enables to set the Restart Delay individually for each Power Outlet. The Delay value can be between 1 and 255 seconds (4 min 15 sec). Command to be sent to the ePowerSwitch 8XS: TRxy=z[CR] Reply from the ePowerSwitch 8XS: TRxy=z[CR] Explanations: Parameter Value Function/Remark x address of the ePowerSwitch 1 to 16 specifies the address of the ePowerSwitch 8XS y number of the Power Outlet 1 to 8...
Page 18
Page | 16 User Guide 6.3.7. Setting the power up default status This command enables to set the power up default status individually for each power outlet. Settings can be always On, Always Off or Last memorized Status before power failure. Command to be sent to the ePowerSwitch 8XS: DPxy=z[CR] Reply from the ePowerSwitch 8XS: DPxy=z[CR] Explanations: Parameter Value Function/Remark x address of the ePowerSwitch 1 to 16 specifies the number of the ePowerSwitch 8XS y number of the...
Page 19
Page | 17 ePowerSwitch 8XS 6.3.9. Reading out the switching counter values of the relays This command enables to read out the number of power up cycles of the ePowerSwitch 8XS and the number of switching cycles (Off to On) of each power outlet. Command to be sent to the ePowerSwitch 8XS: Cxy[CR] Reply from the ePowerSwitch 8XS: Cxy=z[CR] Explanations: Parameter Value Function/Remark x address of the ePowerSwitch 1 to 16 specifies the address of the ePowerSwitch 8XS y counter 0...
Page 20
Page | 18 User Guide 6.3.10. Resetting the switching counter values of the relays This command enables to reset the switching counter values of the Relays. Command to be sent to the ePowerSwitch 8XS: /RC[CR] Reply from the ePowerSwitch 8XS: No reply The ePowerSwitch 8XS accepts lower case and upper case commands. The ePowerSwitch 8XS sends its reply only after having received a valid command terminated by the character [CR]. 6.3.11. Restoring to factory settings This...