    Have a look at the manual Panasonic Cs W18bd3n Cs W24bd3n Cs W28bd3n Series Repair Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							31 
    						
    							33 
    						
    							6 OPERATING INSTRUCTION
    6.1. Wired Remote Control
    Name and function of each part
    34 
    						
    							35 
    						
    							7 REFRIGERATION CYCLE
    7.1. Heating Model
    CS-W18BD3N / CU-W18BBN5
    CS-W24BD3N / CU-W24BBN5
    CS-W28BD3N / CU-W28BBN5 , 8
    36 
    						
    							CS-W34BD3N / CU-W34BBN8
    CS-W43BD3N / CU-W43BBN8
    37 
    						
    							8 OPERATION RANGE
    The applicable voltage range for each unit is given in “thefollowing table”. The workingvoltage among the three phases
    must be balanced within 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher
    than 85% of the rated voltage.
    Power Supply
    Model
    CU-Unit Main PowerApplicable VoltageModel
    CU-Unit Main PowerApplicable Voltage
    Phase, VoltsHzMaximumMinimumPhase, VoltsHzMaximumMinimum
    W18BBN5
    W24BBN5
    W28BBN51~22050242198W28BBN8
    W34BBN8
    W43BBN83N~38050418342
    1~230502532073N~40050440360
    1~240502642163N~41550457374
    Indoor and Outdoor Temperature
    
     
    Heat pumptype
    Model 50Hz ...W18BBN5,W24BBN5,W28BBN5 (8), W34BBN8,W43BBN8
    OperatingHzIndoor Temp. (D.B./W.B.) (°C)Outdoor Temp. (D.B./W.B.) (°C)
    MaximumMinimumMaximumMinimum
    Cooling5032/2321/1543/--5/-
    Heating5027/-16/-24/18-10/-
    38 
    						
    							Correction of cooling and heating capacities according to
    the connecting pipe length.
    The data of cooling capacities (marked on the name plate)
    are based on 7.5 metres connecting pipe and horizontal
    installation.
    (Cooling)
    Equivalent Length = actual pipe length +
    number of elbow x ELE + number of oil
    trap x ELO
    ELE : equivalent length ofelbow.
    ELO : equivalent length of oil trap.
    9.2. REFRIGERANT ADDITIONAL
    CHARGE
     
        • 
    • •  • 
    The piping length exceeds 30 metres.
    APPLICABLE FOR ALLMODELS
    Before shipment, this air conditioner is filled with the rated
    amoun t of refrigerant subject to 30m piping length. (The
    rated amoun t of refrigerant is indicated on the name plate.)
    But when the piping length exceed s 30m, additio nal charge
    is required according to the following table.For other pipe length of other installation multiply
    by the following correction factor to determine the
    revised cooling capacity.
    (Heating)
    Outer diameter of gas
    side pipe mm (inch)
    9.520.18
    12.7 (1/2)0.20
    15.88 (5/8)0.25
    19.05 (3/4)0.35
    ModelRef. Charge
    2.0~2.5HP20g per 1m
    3~5HP50g per 1m
    Example :
    CS-W24BD3N
    In case of 30m long pipe (one-way), the
    amoun t of refrigerant to be replenished is:
    (30 - 30) x 20 = 0g
    CS-W43BD3N
    In case of 50m long pipe (one-way), the
    amoun t of refrigerant to be replenished is:
    (50 - 30) x 50 = 1,000g
    9 PIPE LENGTH
    9.1. CORRECTION OF COOLING AND HEATING CAPACITIES
    39 
    						
    							9.3. Piping installation by existing piping
    
    Heat pumptype(50Hz)
    Model NameStandard piping specification
    Liquid piping (dia.mm)Gas piping (dia.mm)Gas charge-less length (m)Additional gas volume
    (g/m)
    CU-W18BBN56.3512.73020
    CU-W24BBN56.3515.883020
    CU-W28BBN59.5215.883050
    CU-W28BBN89.5215.883050
    CU-W34BBN89.5219.053050
    CU-W43BBN89.5219.053050