Have a look at the manual Panasonic Cs W18bd3n Cs W24bd3n Cs W28bd3n Series Repair Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
6 OPERATING INSTRUCTION 6.1. Wired Remote Control Name and function of each part 34
7 REFRIGERATION CYCLE 7.1. Heating Model CS-W18BD3N / CU-W18BBN5 CS-W24BD3N / CU-W24BBN5 CS-W28BD3N / CU-W28BBN5 , 8 36
8 OPERATION RANGE The applicable voltage range for each unit is given in “thefollowing table”. The workingvoltage among the three phases must be balanced within 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the rated voltage. Power Supply Model CU-Unit Main PowerApplicable VoltageModel CU-Unit Main PowerApplicable Voltage Phase, VoltsHzMaximumMinimumPhase, VoltsHzMaximumMinimum W18BBN5 W24BBN5 W28BBN51~22050242198W28BBN8 W34BBN8 W43BBN83N~38050418342 1~230502532073N~40050440360 1~240502642163N~41550457374 Indoor and Outdoor Temperature Heat pumptype Model 50Hz ...W18BBN5,W24BBN5,W28BBN5 (8), W34BBN8,W43BBN8 OperatingHzIndoor Temp. (D.B./W.B.) (°C)Outdoor Temp. (D.B./W.B.) (°C) MaximumMinimumMaximumMinimum Cooling5032/2321/1543/--5/- Heating5027/-16/-24/18-10/- 38
Correction of cooling and heating capacities according to the connecting pipe length. The data of cooling capacities (marked on the name plate) are based on 7.5 metres connecting pipe and horizontal installation. (Cooling) Equivalent Length = actual pipe length + number of elbow x ELE + number of oil trap x ELO ELE : equivalent length ofelbow. ELO : equivalent length of oil trap. 9.2. REFRIGERANT ADDITIONAL CHARGE • • • • The piping length exceeds 30 metres. APPLICABLE FOR ALLMODELS Before shipment, this air conditioner is filled with the rated amoun t of refrigerant subject to 30m piping length. (The rated amoun t of refrigerant is indicated on the name plate.) But when the piping length exceed s 30m, additio nal charge is required according to the following table.For other pipe length of other installation multiply by the following correction factor to determine the revised cooling capacity. (Heating) Outer diameter of gas side pipe mm (inch) 9.520.18 12.7 (1/2)0.20 15.88 (5/8)0.25 19.05 (3/4)0.35 ModelRef. Charge 2.0~2.5HP20g per 1m 3~5HP50g per 1m Example : CS-W24BD3N In case of 30m long pipe (one-way), the amoun t of refrigerant to be replenished is: (30 - 30) x 20 = 0g CS-W43BD3N In case of 50m long pipe (one-way), the amoun t of refrigerant to be replenished is: (50 - 30) x 50 = 1,000g 9 PIPE LENGTH 9.1. CORRECTION OF COOLING AND HEATING CAPACITIES 39
9.3. Piping installation by existing piping Heat pumptype(50Hz) Model NameStandard piping specification Liquid piping (dia.mm)Gas piping (dia.mm)Gas charge-less length (m)Additional gas volume (g/m) CU-W18BBN56.3512.73020 CU-W24BBN56.3515.883020 CU-W28BBN59.5215.883050 CU-W28BBN89.5215.883050 CU-W34BBN89.5219.053050 CU-W43BBN89.5219.053050 40