Panasonic Cs A9dkh Cu A9dkh Cs A12dkh Cu A12dkh Repair Manual
Have a look at the manual Panasonic Cs A9dkh Cu A9dkh Cs A12dkh Cu A12dkh Repair Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
DISPOSAL OFOUTDOOR UNITDRAIN WATER • If the drain elbow is used, the unit should be placed on a stand which is taller than 3cm. • If the unit is used in an area where temperature falls below 0° C for 2 or 3 days in succession, it is recommended not to use a drain elbow, for the drain water freezes and the fan will not rotate. CHECK THEDRAINAGE • Open front panel and remove air filters. (Drainage checking can be carriedout without removing the front grille.) • Pour a glass of water into the drain tray-styrofoam. • Ensure that water flows out from drain hose of the indoor unit. EVALUATION OF THEPERFORMANCE • Operate the unit at cooling operation mode for fifteen minutes or more. • Measure the temperature of the intake and discharge air. • Ensure the difference between the intake temperature and the discharge is more than 8°C. 10.6.5. CONNECT THE CABLE TO THE OUTDOOR UNIT 1. Remove the control board cover from the unit by loosening the screw. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 × 1.5 mm 2flexible cord, type designation 245 IEC57 or heavier cord. 3. Secure the cable onto the control board with the holder (clamper). 4. Attach the control board cover back to the original position with the screw. 10.6.6. PIPE INSULATION 1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent water from going inside the piping. 2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM with thickness 6 mm or above. 51 CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH /
CHECK ITEMS Is there any gas leakage at flare nut connections? Has the heat insulation been carried out at flare nut connection? Is the connecting cable being fixed to terminal board firmly? Is the connecting cable being clamped firmly? Is the drainage OK? (Refer to “Check the drainage” section) Is the earth wire connection properly done? Is the indoor unit properly hooked to the installation plate? Is the power supplyvoltage complied with rated value? Is there any abnormal sound? Is the cooling operation normal? Is the thermostat operation normal? Is the remote control’s LCD operation normal? Is the super alleru-buster filter installed? 52 CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH /
11 2-way, 3-way Valve 2-way Valve (Liquid Side)3-way Valve (Gas Side) WorksShaft PositionShaft PositionService Port ShippingCloseCloseClose (With valve cap)(With valve cap)(With cap) EvacuationCloseCloseOpen (Installation and(Counter-Clockwise)(Clockwise)(Push-pin) Re-installation) OperationOpenOpenClose (With valve cap)(With valve cap)(With cap) Pumping downCloseOpenOpen (Transferring)(Clockwise)(Counter-Clockwise)(Connected manifo ld gauge) EvacuationOpenOpenOpen (Servicing)With vacuumpump Gas chargingOpenOpenOpen (Servicing)(Withchargingcylinder) Pressure checkOpen (Servicing)OpenOpen(Connected manifo ld gauge) Gas releasingOpen (Servicing)OpenOpen(Connected manifo ld gauge) 53 CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH /
Required tools: hexagonal wrench, adjustable wrench, torque wrenches, wrench to hold the joints and gas leak detector. The additional gas for air purging has been charged in the outdoor unit. However, if the flare connections have not been done correctly and there gas leaks, a gas cylinder and the charge set will be needed. 1. Recheck the piping connections. 2. Open thevalve stemof the2-wayvalvecounter- clockwise approximately 90°, wait 10 seconds, and then set it to closed position. • Be sure to use a hexagonal wrench to operate the valve stem. 3. Check for gas leakage. • Check the flare connection for gas leakage. 4. Purge the air from the system • Set the 2-way valve to the open position and remove the cap from the3-wayvalve’s service port. • Using the hexagonal wrench to press the valve core pin, discharge for three seconds and then wait for one minute. Repeat this three times. 5. Use torque wrench to tightenthe service port cap to a torque of 1.8 kg.m. (18 N.m).The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration pipings, it will affect the compressor, reduce the coolingcapacity, and could lead to a malfunction. 6. Set the 3-wayvalve to theopened position. 7. Mount thevalve stemnuts to the2-way and 3-way valves. 8. Check for gas leakage. • At this time, especially check for gas leakage from the 2- way and 3-way’s stem nuts,and from the service port cap. CautionIf gas leakage is discovered in step (3) above, take the following measures: Tighten the piping connections. If the leaks stop, continue working from step (4). If the gas leaks do not stop when the connections are retightened, repair the location of the leak, discharge all of the gas through the service port, and then recharge with the specified amount of gas from a gas cylinder. 11.1. Air Purging of the Piping and Indoor Unit 11.1.1. Air purging (Installation) Service port cap Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gas leakage from the refrigeration cycle. Procedure: 54 CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH /
1. Confirm that both the 2-way and 3-wayvalves are set to the opened position. • Remove the valve stem caps and confirm that the valve stems are in the opened position. • Be sure to use a hexagonal wrench to operate the valve stems. 2. Operate the unit for 10 to 15 minutes. 3. Stop operation and wait for 3 minutes, then connect the charge set to the service port of the 3-wayvalve. • Connect the charge hose with the push pin to the Gas service port. 4. Air purging of the charge hose. • Open the low-pressure valveon the charge set slightly to purge air from the charge hose. 5. Set the 2-wayvalve to theclose position. 6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1 kg/cm 2G (0.1 MPa). 7. Immediately set the 3-way valve tothe closed position. • Do this quickly so that the gauge ends up indicating 3 to 5 kg/cm 2G (0.3 to 0.5 MPa). 8. Disconnect the charge set, and mount the 2-way and 3- way valve’s stemnuts and the service port caps. • Use a torque wrench to tighten the service port cap to a torque of 1.8 kg.m (18 N.m). • Be sure to check for gas leakage. 11.1.2. Pumping down (Re-installation) Procedure: 55 CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH /
11.1.3. Re-air purging (Re-installation) 1. Confirm that both the 2-way and 3-wayvalves are set to the closed position. 2. Connect the charge set and a charging cylinder to the service port of the 3-wayvalve. • Leave the valve on the charging cylinder closed. 3. Air purging. • Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on the 2-wayvalve approximately 45° for3 seconds then closing it for 1 minute; repeat 3 times. • After purging the air, use a torque wrench to tighten the flare nut onthe 2-wayvalve. 4. Check for gas leakage. • Check the flare connections for gas leakage. 5. Discharge the refrigerant. • Close the valve on the charging cylinder and discharge the refrigerant until the gauge indicates 3 to 5 kg/cm 2G (0.3 to 0.5 MPa) 6. Disconnect the charge set and the charging cylinder, and set the 2-way and 3-wayvalves tothe open position. • Be sure to use a hexagonal wrench to operate the valve stems. 7. Mount thevalve stemnuts and the service port cap. • Be sure to use a torque wrench to tighten the service port cap to a torque 1.8 kg.m (18 N.m). • Be sure to check for gas leakage. Procedure: 56 CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH /
(Gas leakage) 1. Confirm that both the 2-way and 3-wayvalves are set to the open position. 2. Connect the charge set tothe 3-way valve’s service port. • Leave the valve on the charge set closed. • Connect the charge hose with the push pin to the service port. 3. Open the valves(Low side) on the charge set and discharge the refrigerant until the gauge indicates 0.5 to 1 kg/cm 2G (0.05 to 0.1 MPa). • If there is no air in the refrigeration cycle [ the pressure when the air conditioner is not running is higher than 1 kg/cm 2G (0.1 MPa) ], discharge the refrigerant until the gauge indicates 0.5 to 1 kg/cm2G (0.05 to 0.1 MPa). If this is the case, it will not be necessary to apply a evacuation. • Discharge the refrigerant gradually; if it is discharged too suddenly, the refrigeration oil will be discharged. 11.1.4. Balance refrigerant of the 2-way, 3-way valves Procedure: 57 CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH /
(No refrigerant in the refrigeration cycle) 1. Connect the vacuum pump to the charge set’s centre hose. 2. Evacuation for approximately one hour. • Confirm that the gauge needle has moved toward -0.1 MPa (-76 cmHg) [vacuum of 4 mmHg or less.] 3. Closethe valve(Low side) on thecharge set, turn off the vacuum pump, and confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump). 4. Disconnect the charge hose from the vacuum pump. • Vacuum pump oil If the vacuum pump oilbecomes dirtyor depleted, replenish as needed. 11.1.5. Evacuation (Installation) Procedure: 58 CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH /
11.1.6. Gas charging (After Evacuation) 1. Connect the charge hose to the charging cylinder. • Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. 2. Purge the air from the charge hose. • Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant). 3. Open the valve(Low side) on thecharge set and charge the system with liquid refrigerant. • If the system cannot be charged with the specified amount of refrigerant, it can be charged with a little at a time (approximately 150 g each time) while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure. (pumping down-pin) This is different from previous procedures. Because you are charging with liquid refrigerant fromthe gas side, absolutely do no attempt to charge with large amount of liquid refrigerant while operating the air conditioner. 4. Immediately disconnect the charge hose from the 3- way valve’s service port. • Stopping partwaywill allow the refrigerant to be discharged. • If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner before disconnecting the hose. 5. Mount thevalve stemcaps and the service port cap. • Use torque wrench to tighten the service port cap to a torque of 18 N.m. • Be sure to check for gas leakage. Procedure: 59 CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH /
• Electronic controller and Display Complete unit can be seen by following the below removal procedures. Fig. 1 − Remove the 2 caps and 2 screws at the bottom of the Front Grille. (Fig. 1) Fig. 2 − Remove the Front Grille Complete. (Fig. 2) Fig. 3 − Release the taps on top and on the right side of metal plate cover. (Fig. 3) − Then remove the metal plate cover. (Fig. 3) − Remove the indicator complete screw, and then remove the indicator complete. (Fig. 3) 12 Servicing Information 12.1. Distinction Of Lead Free (PbF) Printed Circuit Board • Printed circuit boards (manufactured) using lead free solder will have a PbF stamp on the Printed Circuit board. CAUTION • Pb free solder has a higher melting pointthan standard solder;typically themelting point is 50 - 70°F (30 - 40°C) higher. Please use a high temperature solder iron and set it to 700 ± 20°F (370 ± 10°C). • Pb free solder will tend to splash when heated too high (about 1100°F/600°C). • If you must use Pb solder, please completely remove all of the Pb free solder on the pin or solder area before applying Pb solder. If this is not practical, be sure to heat the Pb free solder until it melts, before applying Pb solder. 12.2. Indoor Electronic Controllers Removal Procedures 60 CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH /