Home > Panasonic > Air Conditioner > Panasonic Cs A9dkh Cu A9dkh Cs A12dkh Cu A12dkh Repair Manual

Panasonic Cs A9dkh Cu A9dkh Cs A12dkh Cu A12dkh Repair Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic Cs A9dkh Cu A9dkh Cs A12dkh Cu A12dkh Repair Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							DISPOSAL OFOUTDOOR UNITDRAIN WATER
     • If the drain elbow is used, the unit should be placed on a
    stand which is taller than 3cm.
     • If the unit is used in an area where temperature falls below
    0° C for 2 or 3 days in succession, it is recommended not to
    use a drain elbow, for the drain water freezes and the fan
    will not rotate.
    CHECK THEDRAINAGE
     • Open front panel and remove air filters.
    (Drainage checking can be carriedout without removing the
    front grille.)
     • Pour a glass of water into the drain tray-styrofoam.
     • Ensure that water flows out from drain hose of the indoor
    unit.
    EVALUATION OF THEPERFORMANCE
     • Operate the unit at cooling operation mode for fifteen
    minutes or more. • Measure the temperature of the intake and discharge air.
     • Ensure the difference between the intake temperature and
    the discharge is more than 8°C.
    10.6.5. CONNECT THE CABLE TO THE OUTDOOR UNIT
     1. Remove the control board cover from the unit by loosening the screw.
     2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 × 1.5 mm
    2flexible cord,
    type designation 245 IEC57 or heavier cord.
     3. Secure the cable onto the control board with the holder (clamper).
     4. Attach the control board cover back to the original position with the screw.
    10.6.6. PIPE INSULATION
     1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap
    the insulated piping end to prevent water from going inside the piping.
     2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM
    with thickness 6 mm or above.
    51
    CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH / 
    						
    							CHECK ITEMS
    Is there any gas leakage at flare nut connections?
    Has the heat insulation been carried out at flare nut
    connection?
    Is the connecting cable being fixed to terminal board firmly?
    Is the connecting cable being clamped firmly?
    Is the drainage OK?
    (Refer to “Check the drainage” section)
    Is the earth wire connection properly done?
    Is the indoor unit properly hooked to the installation plate?
    Is the power supplyvoltage complied with rated value?
    Is there any abnormal sound?
    Is the cooling operation normal?
    Is the thermostat operation normal?
    Is the remote control’s LCD operation normal?
    Is the super alleru-buster filter installed?
    52
    CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH / 
    						
    							11 2-way, 3-way Valve
    2-way Valve (Liquid Side)3-way Valve (Gas Side)
    WorksShaft PositionShaft PositionService Port
    ShippingCloseCloseClose
    (With valve cap)(With valve cap)(With cap)
    EvacuationCloseCloseOpen
    (Installation and(Counter-Clockwise)(Clockwise)(Push-pin)
    Re-installation)
    OperationOpenOpenClose
    (With valve cap)(With valve cap)(With cap)
    Pumping downCloseOpenOpen
    (Transferring)(Clockwise)(Counter-Clockwise)(Connected manifo ld
    gauge)
    EvacuationOpenOpenOpen
    (Servicing)With vacuumpump
    Gas chargingOpenOpenOpen
    (Servicing)(Withchargingcylinder)
    Pressure checkOpen
    (Servicing)OpenOpen(Connected manifo ld
    gauge)
    Gas releasingOpen
    (Servicing)OpenOpen(Connected manifo ld
    gauge)
    53
    CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH / 
    						
    							Required tools: hexagonal wrench, adjustable wrench, torque
    wrenches, wrench to hold the joints and gas leak detector.
    The additional gas for air purging has been charged in the
    outdoor unit.
    However, if the flare connections have not been done correctly
    and there gas leaks, a gas cylinder and the charge set will be
    needed.
     1. Recheck the piping connections.
     2. Open thevalve stemof the2-wayvalvecounter-
    clockwise approximately 90°, wait 10 seconds, and
    then set it to closed position.
     • Be sure to use a hexagonal wrench to operate the valve
    stem.
     3. Check for gas leakage.
     • Check the flare connection for gas leakage.
     4. Purge the air from the system
     • Set the 2-way valve to the open position and remove the
    cap from the3-wayvalve’s service port.
     • Using the hexagonal wrench to press the valve core pin,
    discharge for three seconds and then wait for one
    minute.
    Repeat this three times.
     5. Use torque wrench to tightenthe service port cap to a
    torque of 1.8 kg.m. (18 N.m).The air in the indoor unit and in the piping must be purged. If air
    remains in the refrigeration pipings, it will affect the
    compressor, reduce the coolingcapacity, and could lead to a
    malfunction.
     6. Set the 3-wayvalve to theopened position.
     7. Mount thevalve stemnuts to the2-way and 3-way
    valves.
     8. Check for gas leakage.
     • At this time, especially check for gas leakage from the 2-
    way and 3-way’s stem nuts,and from the service port
    cap.
    CautionIf gas leakage is discovered in step (3) above, take
    the following measures:
    Tighten the piping connections. If the leaks stop,
    continue working from step (4).
    If the gas leaks do not stop when the connections are
    retightened, repair the location of the leak, discharge
    all of the gas through the service port, and then
    recharge with the specified amount of gas from a gas
    cylinder.
    11.1. Air Purging of the Piping and Indoor Unit
    11.1.1. Air purging (Installation)
    Service port cap
    Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gas
    leakage from the refrigeration cycle.
    Procedure:
    54
    CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH / 
    						
    							 1. Confirm that both the 2-way and 3-wayvalves are set to
    the opened position.
     • Remove the valve stem caps and confirm that the valve
    stems are in the opened position.
     • Be sure to use a hexagonal wrench to operate the valve
    stems.
     2. Operate the unit for 10 to 15 minutes.
     3. Stop operation and wait for 3 minutes, then connect the
    charge set to the service port of the 3-wayvalve.
     • Connect the charge hose with the push pin to the Gas
    service port.
     4. Air purging of the charge hose.
     • Open the low-pressure valveon the charge set slightly
    to purge air from the charge hose. 5. Set the 2-wayvalve to theclose position.
     6. Operate the air conditioner at the cooling cycle and
    stop it when the gauge indicates 1 kg/cm
    2G (0.1 MPa).
     7. Immediately set the 3-way valve tothe closed position.
     • Do this quickly so that the gauge ends up indicating 3 to
    5 kg/cm
    2G (0.3 to 0.5 MPa).
     8. Disconnect the charge set, and mount the 2-way and 3-
    way valve’s stemnuts and the service port caps.
     • Use a torque wrench to tighten the service port cap to a
    torque of 1.8 kg.m (18 N.m).
     • Be sure to check for gas leakage.
    11.1.2. Pumping down (Re-installation)
    Procedure:
    55
    CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH / 
    						
    							11.1.3. Re-air purging (Re-installation)
     1. Confirm that both the 2-way and 3-wayvalves are set to
    the closed position.
     2. Connect the charge set and a charging cylinder to the
    service port of the 3-wayvalve.
     • Leave the valve on the charging cylinder closed.
     3. Air purging.
     • Open the valves on the charging cylinder and the
    charge set. Purge the air by loosening the flare nut on
    the 2-wayvalve approximately 45° for3 seconds then
    closing it for 1 minute; repeat 3 times.
     • After purging the air, use a torque wrench to tighten the
    flare nut onthe 2-wayvalve.
     4. Check for gas leakage.
     • Check the flare connections for gas leakage. 5. Discharge the refrigerant.
     • Close the valve on the charging cylinder and discharge
    the refrigerant until the gauge indicates 3 to 5 kg/cm
    2G
    (0.3 to 0.5 MPa)
     6. Disconnect the charge set and the charging cylinder,
    and set the 2-way and 3-wayvalves tothe open
    position.
     • Be sure to use a hexagonal wrench to operate the valve
    stems.
     7. Mount thevalve stemnuts and the service port cap.
     • Be sure to use a torque wrench to tighten the service
    port cap to a torque 1.8 kg.m (18 N.m).
     • Be sure to check for gas leakage.
    Procedure:
    56
    CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH / 
    						
    							(Gas leakage)
     1. Confirm that both the 2-way and 3-wayvalves are set to
    the open position.
     2. Connect the charge set tothe 3-way valve’s service
    port.
     • Leave the valve on the charge set closed.
     • Connect the charge hose with the push pin to the
    service port.
     3. Open the valves(Low side) on the charge set and
    discharge the refrigerant until the gauge indicates 0.5
    to 1 kg/cm
    2G (0.05 to 0.1 MPa).
     • If there is no air in the refrigeration cycle [ the pressure
    when the air conditioner is not running is higher than 1
    kg/cm
    2G (0.1 MPa) ], discharge the refrigerant until the
    gauge indicates 0.5 to 1 kg/cm2G (0.05 to 0.1 MPa). If
    this is the case, it will not be necessary to apply a
    evacuation.
     • Discharge the refrigerant gradually; if it is discharged
    too suddenly, the refrigeration oil will be discharged.
    11.1.4. Balance refrigerant of the 2-way, 3-way valves
    Procedure:
    57
    CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH / 
    						
    							(No refrigerant in the refrigeration cycle)
     1. Connect the vacuum pump to the charge set’s centre
    hose.
     2. Evacuation for approximately one hour.
     • Confirm that the gauge needle has moved toward -0.1
    MPa (-76 cmHg) [vacuum of 4 mmHg or less.]
     3. Closethe valve(Low side) on thecharge set, turn off
    the vacuum pump, and confirm that the gauge needle
    does not move (approximately 5 minutes after turning
    off the vacuum pump).
     4. Disconnect the charge hose from the vacuum pump.
     • Vacuum pump oil
    If the vacuum pump oilbecomes dirtyor depleted,
    replenish as needed.
    11.1.5. Evacuation (Installation)
    Procedure:
    58
    CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH / 
    						
    							11.1.6. Gas charging
    (After Evacuation)
     1. Connect the charge hose to the charging cylinder.
     • Connect the charge hose which you disconnected from
    the vacuum pump to the valve at the bottom of the
    cylinder.
     2. Purge the air from the charge hose.
     • Open the valve at the bottom of the cylinder and press
    the check valve on the charge set to purge the air (be
    careful of the liquid refrigerant).
     3. Open the valve(Low side) on thecharge set and charge
    the system with liquid refrigerant.
     • If the system cannot be charged with the specified
    amount of refrigerant, it can be charged with a little at a
    time (approximately 150 g each time) while operating
    the air conditioner in the cooling cycle; however, one
    time is not sufficient, wait approximately 1 minute and
    then repeat the procedure. (pumping down-pin)
    This is different from previous procedures. Because you are
    charging with liquid refrigerant fromthe gas side, absolutely do
    no attempt to charge with large amount of liquid refrigerant
    while operating the air conditioner.
     4. Immediately disconnect the charge hose from the 3-
    way valve’s service port.
     • Stopping partwaywill allow the refrigerant to be
    discharged.
     • If the system has been charged with liquid refrigerant
    while operating the air conditioner, turn off the air
    conditioner before disconnecting the hose.
     5. Mount thevalve stemcaps and the service port cap.
     • Use torque wrench to tighten the service port cap to a
    torque of 18 N.m.
     • Be sure to check for gas leakage.
    Procedure:
    59
    CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH / 
    						
    							 • Electronic controller and Display Complete unit can be seen
    by following the below removal procedures.
    Fig. 1
     − Remove the 2 caps and 2 screws at the bottom of the
    Front Grille. (Fig. 1)
    Fig. 2
     − Remove the Front Grille Complete. (Fig. 2)
    Fig. 3
     − Release the taps on top and on the right side of metal
    plate cover. (Fig. 3)
     − Then remove the metal plate cover. (Fig. 3)
     − Remove the indicator complete screw, and then remove
    the indicator complete. (Fig. 3)
    12 Servicing Information
    12.1. Distinction Of Lead Free (PbF) Printed Circuit Board
     • Printed circuit boards (manufactured) using lead free solder will have a PbF stamp on the Printed Circuit board.
    CAUTION
     • Pb free solder has a higher melting pointthan standard solder;typically themelting point is 50 - 70°F (30 - 40°C) higher.
    Please use a high temperature solder iron and set it to 700 ± 20°F (370 ± 10°C).
     • Pb free solder will tend to splash when heated too high (about 1100°F/600°C).
     • If you must use Pb solder, please completely remove all of the Pb free solder on the pin or solder area before applying Pb
    solder. If this is not practical, be sure to heat the Pb free solder until it melts, before applying Pb solder.
    12.2. Indoor Electronic Controllers Removal Procedures
    60
    CS-A9DKH CU-A9DKH / CS-A12D KH CU-A12D KH / 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Cs A9dkh Cu A9dkh Cs A12dkh Cu A12dkh Repair Manual