    Have a look at the manual Panasonic Cs A18gkd Cs A18gkd Cu A18gkd Cu A24gkh Repair Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							51
    14 Troubleshooting Guide
    14.1. Refrigeration Cycle System
    In order to diagnose malfunctions, make sure that there are no
    electrical problems before inspecting the refrigeration cycle.
    Such problems include insufficient insulation, problem with the
    power source, malfunction of a compressor and a fan.
    The normal outlet air temperature and pressure of the
    refrigeration cycle depends on various conditions, the standard
    values for them are shown in the table on the right. 
    						
    							52
    14.1.1. Relationship between the condition of the air conditioner and pressure and electric
    current
    • Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
    14.1.2. Diagnosis methods of a malfunction of a compressor and 4-Way Valve
    Cooling Mode Heating Mode
     
    Low Pressure High PressureElectric current 
    during operatingLow Pressure High PressureElectric current 
    during operating Condition of the air 
    conditioner
    Insufficient refrigerant
    (gas leakage)
    Clogged capillary tube
    or Strainer
    Short circuit in the
    indoor unit
    Heat radiation deficiency
    of the outdoor unit
    Inefficient compression
    Nature of fault Symptom
    Insufficient compressing of a compressor• Electric current during operation becomes approximately 20% lower than the normal value.
    • The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C).
    • The difference between high pressure and low pressure becomes almost zero.
    Locker compressor• Electric current reaches a high level abnormally, and the value exceeds the limit of an
    ammeter. In some cases, a breaker turns off.
    • The compressor has a humming sound.
    Insufficient switches of the 4-way valve• Electric current during operation becomes approximately 80% lower than the normal value.
    • The temperature different between from the discharge tube to the 4-way valve and from
    suction tube to the 4-way valve becomes almost zero. 
    						
    							53
    15 Disassembly and Assembly Instructions
    15.1. Indoor Electronic Controllers and Control Board Removal Procedures
    WARNING
    • Cautions! When handling electronic controller, be careful of electrostatic discharge.
    • Be sure to return the wiring to its original position.
    • There are many high voltage components within the heat sink cover so never touch the interior during operation. Wait at least two minutes after
    power has been turned off. 
    						
    							55 
    						
    							56
    15.2. Indoor Fan Motor and Cross Flow Fan Removal Procedures 
    						
    							57 
    						
    							58
    16 Technical Data
    16.1. Thermostat Characteristics 
    						
    							59
    16.2. Operation Characteristics 
    						