Home > Kenmore > Water Heater > Kenmore Power Miser 6 Owners Manual

Kenmore Power Miser 6 Owners Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Kenmore Power Miser 6 Owners Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 23 Kenmore manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							11
    Position the valve downward and provide tubing so that any
    discharge will exit only within 6 inches (153 mm) above, or at
    any distance below the structural floor.  Be certain that no contact
    is made with any live electrical part.  The discharge opening
    must not be blocked or reduced in size under any
    circumstances.  Excessive length, over 30 feet (9.14 m), or use
    of more than four elbows can cause restriction and reduce the
    discharge capacity of the valve.
    No valve or other obstruction is to be placed between the relief
    valve and the tank.  Do not connect tubing directly to discharge
    drain unless a 6 inch air gap is provided.  To prevent bodily
    injury, hazard to life, or property damage, the relief valve must
    be allowed to discharge water in quantities should
    circumstances demand.  If the discharge pipe is not connected
    to a drain or other suitable means, the water flow may cause
    property damage.
    The Discharge Pipe:
    • Shall not be smaller in size than the outlet pipe size of the
    valve, or have any reducing couplings or other restrictions.
    • Shall not be plugged or blocked.
    • Shall be of material listed for hot water distribution.
    • Shall be installed so as to allow complete drainage of both
    the temperature-pressure relief valve, and the discharge
    pipe.
    • Shall terminate at an adequate drain.
    • Shall not have any valve between the relief valve and tank.
    The temperature-pressure relief valve must be manually
    operated at least once a year.  Caution should be taken to
    ensure that (1) no one is in front of or around the outlet of the
    temperature-pressure relief valve discharge line, and (2) the
    water manually discharged will not cause any bodily injury or
    property damage because the water may be extremely hot.If after manually operating the valve, it fails to completely reset
    and continues to release water, immediately close the cold
    water inlet to the water heater, follow the draining instructions,
    and replace the temperature-pressure relief valve with a new
    one.
                   
    FIGURE 10.
    Filling the Water Heater
    Never use this water heater unless it is completely full of water.
    To prevent damage to the tank and heating element, the tank
    must be filled with water. Water must flow from the hot water
    faucet before turning “ON” power.
    To fill the water heater with water:
    1. Close the water heater drain valve by turning the handle to
    the right (clockwise). The drain valve is located on the lower
    front of the water heater.
    2. Open the cold water supply valve to the water heater.
    NOTE: The cold water supply valve must be left open when
    the water heater is in use.
    3. To insure complete filling of the tank, allow air to exit by
    opening the nearest hot water faucet. Allow water to run until
    a constant flow is obtained. This will let air out of the water
    heater and the piping.
    4. Check all new water piping for leaks. Repair as needed. 
    						
    							12
    Converting the Lower Element
    These instructions only cover the conversion of the convertible
    element, read this entire manual before attempting to install or
    operate the water heater. The water heater is factory set to
    operate at 3800 watts. The lower element can be converted to
    operate at 5500 watts. Refer to “Facts to Consider About the
    Convertible Lower Element” section.
    The Upper Element, (if double element model) is a
    conventional 3800 watt element which only operates at its rated
    wattage on 240 volts. (See rating plate on the water heater.
    The lower Element of the water heater can be converted from
    operation at 3800 watts to 5500 watts on a 240 volt system.
    If after reading these instructions and this manual, if you do not
    understand any portion call Sears Service Center.
    Before making the conversion to 5500 watts, check the (1)
    power supply . . . must be 240 volts, (2) wiring . . . 10 gauge
    AWG @ Type TW, 60°C or equivalent, and (3) Circuit breakers
    or fusing . . .capable of 30 amp loading. Also, the installation
    must conform with this manual, local codes and electric utility
    rules. Failure to comply can result in DEATH, SERIOUS BODILY
    INJURY, OR PROPERTY DAMAGE.
    NOTE: Whether or not the element conversion is made the
    model rating plate must be marked. Using a hard point ink
    pen, check the appropriate block within the model rating plate,
    which is located adjacent to the lower access panel.
                 
    FIGURE 11.
    Necessary element conversion parts are located in a small
    bag contained within the electrical junction box on top of the
    water heater.
                          
    FIGURE 12.
    1. Before beginning the conversion turn “OFF” electric power
    supply to the water heater.
                             
    FIGURE 13.
    2. The convertible element is located behind the lower
    access panel of the water heater. Remove the two screws
    securing the access panel, and remove panel.
                                 
    FIGURE 14.
    3. Remove the insulation cap with handle to expose the
    terminal cover.
                                     
    FIGURE 15.
    4. Lower Element: Lift out the tab as shown to unclip the
    terminal cover from the thermostat. The terminal cover can
    now be removed from the thermostat. 
    						
    							13
    FIGURE 16.
    5. Remove the screws from terminal 2 of the element, and
    move the looped end of the wire aside.
                         
    FIGURE 17.
    6. The buss bar is labeled 5500 W. Place the buss bar over
    terminals 2 and 3 with the 5500 W visible. Install the extra
    screw provided into terminal 3.
                   
    FIGURE 18.
    7. The wire removed from terminal 2 has a looped end. It
    must remain looped and now be placed (as shown) on
    top of the buss bar, over the opening of terminal 2, and
    secured using the remaining screw.
                                             
    FIGURE 19.
    8. Tighten terminals 2 and 3 to ensure proper electrical
    connection.
    Failure to tighten terminal screws can cause a fire which can
    result in DEATH, SERIOUS BODILY INJURY, OR PROPERTY
    DAMAGE.
    9. Replace terminal cover on thermostat making sure that
    the locking tabs on the terminal cover are in place.
    Make sure the thermostat is flush against the tank, the terminal
    cover is in place, and the insulation is replaced. Failure to do
    so can result in DEATH, SERIOUS BODILY INJURY, OR
    PROPERTY DAMAGE.
    10. Replace the insulation cap with handle so that it completely
    covers the thermostat and element.
                                     
    FIGURE 20. 
    						
    							14
    11. Replace the access panel.
                                   
    FIGURE 21.
    12. Complete wiring to the water heater, or if completed, turn
    “ON” electric power to the water heater 
    after filling the tank
    with water.
                         
    FIGURE 22.
    Never use this water heater unless it is completely full of water.
    To prevent damage to the tank and heating element, the tank
    must be filled with water. Water must flow from the hot water
    faucet before turning “ON” power.
    Wiring
    You must provide all wiring of the proper size outside of the
    water heater. You must obey local codes and electric company
    requirements when you install this wiring.
    If you are not familiar with electric codes and practices, or if you
    have any doubt, even the slightest doubt, in your ability to connect
    the wiring to this water heater, obtain the service of a competent
    electrician. Contact your Sears salesperson to arrange for a
    professional electrician.
    WATER HEATERS EQUIPPED FOR ONE VOLTAGE ONLY: This
    water heater is equipped for one type voltage only. Check the
    rating plate near the bottom access panel for the correct voltage.
    DO NOT use this water heater with any voltage other than the
    one shown on the model rating plate. Failure to use the correct
    voltage can cause problems which can result in DEATH,
    SERIOUS BODILY INJURY, OR PROPERTY DAMAGE. If you
    have any questions or doubts consult your electric company.
    If wiring from your fuse box or circuit breaker box was aluminum
    for your old water heater, replace it with copper wire. If you wish
    to reuse the existing aluminum wire, have the connection at
    the water heater made by a competent electrician. Contact your
    Sears salesperson to arrange for a professional electrician.
    1. Provide a way to easily shut off the electric power when
    working on the water heater. This could be with a circuit
    breaker or fuse block in the entrance box or a separate
    disconnect switch.
    2. Install and connect a circuit directly from the main fuse or
    circuit breaker box. This circuit must be the right size and
    have its own fuse or circuit breaker. Refer to the chart in the
    “Product Specifications” section for the correct size wire and
    fuse or circuit breaker.
    3. If metal conduit is used for the grounding conductor:
    a. The grounding electrode conductor shall be of copper,
    aluminum, or copperclad aluminum. The material
    shall be of one continuous length without a splice or
    joint.
    b. Rigid metal conduit, intermediate metal conduit, or
    electrical metallic tubing may be used for the grounding
    means if conduit or tubing is terminated in fittings
    approved for grounding.
    c. Flexible metal conduit or flexible metallic tubing shall
    be permitted for grounding if all the following
    conditions are met:
    • The length in any ground return path does not exceed
    6 feet.
    • The circuit conductors contained therein are protected
    by overcurrent devices rated at 20 amperes or less.
    • The conduit or tubing is terminated in fittings approved
    for grounding.
    For complete grounding details and all allowable exceptions,
    refer to the current edition of the NEC - National Electrical Code
    NFPA 70.
    4. A standard 1/2 conduit opening has been made in the water
    heater junction box for the conduit connection. 
    						
    							15
    5. Wiring Diagrams (see “Wiring Diagrams” section) have been
    supplied showing the two most common types of
    connections between the water heater and the power supply.
    You can easily see which type connection you have by
    removing the junction box cover on top of the water heater.
    •Two Wire Connection Diagrams: is the most common
    requiring you to simply connect red to red, black to
    black, and the ground wire to the green ground screw
    in the junction box of the water heater.
    •Three Wire Connection Diagram: is used when you
    are connecting the water heater to a power supply
    that has a “Time Clock” or “Off Peak” meter. To make
    these connections refer to block 1 or 2 in this wiring
    diagram for the type of system you have.
    NOTE: If you have purchased a three wire connection water
    heater but you are not on a “Time Clock” or “Off Peak” meter
    and have a standard two wire connection power supply,
    simply follow the connection diagram in block 3 of the three
    wire connection diagram.6. Use wire nuts and connect the power supply wiring to the
    wires inside the water heater’s junction box.
    7. The water heater must be electrically “grounded” by the
    installer. A green ground screw has been provided on the
    water heater’s junction box. Connect ground wire to this
    location.
    8. Replace the wiring junction cover using the screw provided.
    FIGURE 23. 
    						
    							16
    Wiring Diagrams
    FIGURE 25.
    STANDARD WIRING FOR 2 WIRE LEAD WATER HEATERS
    NON-SIMULTANEOUS OPERATION 240 VOLT DOUBLE ELEMENT
    WIRING FOR 3 WIRE LEAD WATER HEATERS NON-SIMULTANEOUS OPERATION 240 VOLT DOUBLE ELEMENT
    *NOTE: Some lower Hi-Temp Limit Switches
     may have 4 terminals. Use only the
    2 terminals on left.FIGURE 24.
    A6
    A9 
    						
    							17
    Temperature Regulation
    HOTTER WATER CAN SCALD: Water heaters are intended to
    produce hot water. Water heated to a temperature which will
    satisfy clothes washing, dish washing, and other sanitizing
    needs can scald and permanently injure you upon contact.
    Some people are more likely to be permanently injured by hot
    water than others. These include the elderly, children, the infirm,
    or physically/mentally handicapped. If anyone using hot water
    in your home fits into one of these groups or if there is a local
    code or state law requiring a certain temperature water at the
    hot water tap, then you must take special precautions. In
    addition to using the lowest possible temperature setting that
    satisfies your hot water needs, some type of tempering device,
    such as a mixing valve, should be used at the hot water taps
    used by these people or at the water heater. Mixing valves are
    available at plumbing supply or hardware stores. Follow
    manufacturers instructions for installation of the valves, Before
    changing the factory setting of the thermostat see Temperature
    Settings table at right.
    Never allow small children to use a hot water tap, or to draw
    their own bath water. Never leave a child or handicapped person
    unattended in a bathtub or shower.
    Thermostats
    The thermostats of this water heater have been factory set at a
    position which approximates 120°F (49°C), to reduce the risk
    of scald injury.
    The upper thermostat is factory set at a position which
    approximates 120°F (49°C), and is adjustable if a different
    water temperature is desired. Read all warnings in this manual
    and on the water heating before proceeding.
    FIGURE 26.
    The lower thermostat is factory set at a position which
    approximates 120°F (49°C), and is adjustable if a different
    water temperature is desired. Read all warnings in this manual
    and on the water heating before proceeding.
    FIGURE 27.
    Temperature Settings
    NOTE: Water temperature range of 120°—140°F (49°-60°C)
    recommended by most dishwasher manufacturers.
    Upper and Lower Thermostat Adjustments
    (Refer to thermostat illustrations under “Thermostats” section)
     
    NOTE: It is not necessary to adjust the upper thermostat.
    However, if it is adjusted above the factory set point of 120°F
    (49°C), it is recommended that it not be set higher than the
    lower thermostat setting.
    SERVICE AND ADJUSTMENT 
    						
    							18
    The upper and lower thermostats are adjustable if a different
    water temperature is desired. Read all warnings in the
    “Temperature-Regulation” section before proceeding.
    1. Turn “OFF” the electric power to the water heater at the
    junction box.
    2. Take off the upper and/or lower access panel, insulation
    cap with handle.
    3. The slotted adjustment (using a screwdriver) can be turned
    clockwise ( 
     ) to increase the temperature setting or
    counter clockwise ( 
     ) to decrease the temperature setting.
    4. Replace the insulation cap with handle and access panel.
    5. Turn “ON” the power supply.
    Anode Rod Inspection
    The anode rod is used to protect the tank from corrosion. Most
    hot water tanks are equipped with an anode rod. The
    submerged rod sacrifices itself to protect the tank. Instead of
    corroding the tank, water ions attack and eat away the anode
    rod. This does not affect the water’s taste or color. The rod
    must be maintained to keep the tank in operating condition.
    Anode deterioration depends on the water conductivity, not
    necessarily water condition. A corroded or pitted anode rod
    indicates high water conductivity and should be checked and/
    or replaced more often than an anode rod that appears to be
    intact. Replacement of a depleted anode rod can extend the
    life of your water heater. Inspection should be conducted by
    calling Sears Service Center. At  a minimum the anode(s)
    should be checked annually after the warranty period.
    Temperature-Pressure Relief Valve Operation
    The temperature-pressure relief valve must be manually
    operated at least once a year.
    The temperature-pressure relief valve must be manually
    operated at least once a year. Caution should be taken to ensure
    that (1) no one is in front of or around the outlet of the
    temperature-pressure relief valve discharge line, and (2) the
    water manually discharged will not cause any property damage
    or bodily injury. The water may be extremely hot.
                        
    FIGURE 28.
    If after manually operating the valve, it fails to completely reset
    and continues to release water, immediately close the cold
    water inlet to the water heater, follow the draining instructions,
    and replace the temperature-pressure relief valve with a new
    one.
    Failure to install and maintain a new properly listed temperature-
    pressure relief valve will release the manufacturer from any
    claim which might result from excessive temperature or
    pressure.
    If the temperature-pressure relief valve on the appliance weeps
    or discharges periodically, this may be due to thermal
    expansion. Your water heater may have a check valve installed
    in the water line or a water meter with a check valve. Consult
    your local Sears Service Center for further information. Do not
    plug the temperature-pressure relief valve.
    Draining 
    						
    							19
    The water heater should be drained if being shut down during
    freezing temperatures. Also, periodic draining and cleaning of
    sediment from the tank may be necessary.
    1. Before beginning turn “OFF” the electric power supply to the
    water heater.
    2. CLOSE the cold water inlet valve to the water heater.
    3. OPEN a nearby hot water faucet and leave open to allow for
    draining.
    4. Connect a hose to the drain valve and terminate to an
    adequate drain or outdoors.
    5. OPEN the water heater drain valve to allow for tank draining.
    NOTE: If the water heater is going to be shut down and
    drained for an extended period, the drain valve should be left
    open with hose connected allowing water to terminate to an
    adequate drain.
    6. Close the drain valve.
    7. Follow “Filling the Water Heater” instructions in the
    “Installation Instructions” section.
    8. Turn “ON” power to the water heater.
    Never use this water heater unless it is completely full of water.
    To prevent damage to the tank and heating element, the tank
    must be filled with water. Water must flow from the hot water
    faucet before turning “ON” power.
    Thermostat Removal/Replacement
    1. Turn “OFF” the electrical power to the water heater at the
    junction box.
    2. Remove the access panel and the insulation cap with
    handle.
    3. Lift out the tab as shown below to unclip the terminal cover
    from the thermostat. The terminal cover can now be removed
    from the thermostat.
          
    FIGURE 29.
    4. Disconnect wires from the thermostat.
    5. Remove the thermostat from behind the thermostat
    bracket.
    6. Place the new thermostat in the bracket making sure it fits
    firmly against the tank.
    7. Attach the wires to the new thermostat.
    NOTE: Some of the terminals may require straight-in wiring
    through an eye-opening. If wires are now looped, recut and
    strip wire 3/8” to a straight length and insert.
    8. Put plastic terminal cover back in place.
    9. Replace the insulation cap with handle to cover the
    thermostat.
    10. Replace access panel, then turn the electric power on.
    Element Cleaning/Replacement
    NOTE: These instructions are written for element cleaning and
    element replacement for the lower element. If it is necessary to
    clean or replace the upper element, then repeat these
    instructions.
    To remove the element from your tank in order to clean or
    replace it. 
    						
    							20
    1. Before beginning turn “OFF” the electric power supply to
    the water heater.
                      
    FIGURE 30.
    2. Turn off the water supply to the water heater at the water
    Shut-off valve or water meter.
                         
    FIGURE 31.
    3. Attach a hose to the water heater drain valve and put the
    other end in a floor drain or outdoors. Open the water heater
    drain valve. Open a nearby hot water faucet which will relieve
    pressure in the water heater and speed draining.
                        
    FIGURE 32.
    The water passing out of the drain valve may be extremely hot.
    To avoid being scalded, make sure all connections are tight
    and that the water flow is directed away from any person.4. Remove the two screws securing the access panel, and
    remove panel.
                                  
    FIGURE 33.
    5. Remove the insulation cap with handle.
                                       
    FIGURE 34.
    6. Lift out the tab as shown to unclip the terminal cover from
    the thermostat. The terminal cover can now be removed
    from the thermostat.
            
    FIGURE 35.
    7. Disconnect the two wires on the element and unscrew the
    old element from the tank.
    FIGURE 36. 
    						
    All Kenmore manuals Comments (0)

    Related Manuals for Kenmore Power Miser 6 Owners Manual