    Specification
    Overview
    The UDC100 Universal Digital Controller
    is a microprocessor-based 1/4 DIN low
    cost temperature controller. It combines
    the highest operating simplicity with the
    benefits of digital technology. Its large dial
    allows easy parameter set-up. This micro-
    processor-based device provides a high
    degree of flexibility, repeatability,
    accuracy and temperature stability. Its
    simple ON-OFF/PID control algorithm with
    alarm and timer option capability make
    the UDC100 ideal for such applications as
    food processing (e.g. bakery ovens),
    small industrial furnaces and ceramics
    kilns. The UDC120 version has 2-loop
    control for excellent space integration and
    cost saving capabilities.
    Features
    High functionality at low cost
    The UDC100 offers the benefits of
    microprocessor technology at a very
    competitive price.
    Easy to use
    Thanks to analog-feel ergonomics the
    UDC100 is very simple to use. The
    interface has been selected to provide
    the most intuitive way to set-up
    parameters.  The UDC100 is the ideal
    replacement for the well-known and
    popular AL/CL analog controller family.
    Custom built for OEMs
    The UDC100 has been designed to
    meet OEM requirements. Product over-
    lay, labels, input ranges and firmware
    can be tailored to your particular
    specification. The integrated solution of
    the timer and 2-loop model is a perfect
    example of how the UDC100 is adapt-
    able to meet specific market segment
    needs.
    High level of integration
    Several functions have been integrated
    to provide cost and space savings as
    well as to reduce wiring and set-up time.
    The UDC110T offers control and dura-
    tion of the process thanks to its integral
    timer function. The UDC120 integrates 2
    loops in one DIN format to provide a
    high level of integration.
    Features, continued
    Rugged design for optimum
    repeatability and reliability
    The unit’s digital technology gives it
    extremely good stability in case of
    ambient temperature variation. This
    drift-free capability allows process
    control in the most severe industrial
    environments. All functional parts are
    mounted on a rugged chassis for easy
    replacement without disturbing field
    wiring. A rugged 10 Amp output relay
    is provided as standard for direct
    control application.
    Universal isolated input
    Input 1 can be configured for any input
    type and is isolated from relay output.
    In the dual loop model, input 2 type is
    identical to input 1 and is not isolated
    from input 1.
    Dual loop model
    This model offers two independent
    loops with two separate 3- or 4-digit
    displays. Control parameters and set-
    points are independent of each loop.
    The possibility exists of one single SP
    for both loops.
    Single or dual displays
    According to the version, the displays
    will have 3 or 4 digits. The UDC100
    basic model has one display. Models
    Features, continued
    UDC110 and UDC120 provide dual
    displays for PV and SP reading or PV1
    and PV2.
    Moisture-resistant front panel
    The front panel has IP54 front face
    protection against dust and water
    (hosedown).
    PC configuration editor
    Current parameters such as setpoints,
    alarm value and duration are config-
    urable from the instrument’s front face.
    All other parameters can be easily
    modified via a PC configurator pack-
    age. Specific configuration can be
    saved, uploaded or downloaded for
    maintenance management.
    Timer
    The UDC110T provides a configurable
    time period from 0 to 9 hours. The timer
    is initiated by a key on the front face.
    An electromechanical relay and a front
    face LED are activated at the end of the
    timeout period. The relay is latched and
    requires manual acknowledgement
    from the operator.
    Alarm selection
    One alarm is available with a remote
    electromechanical relay action. The
    alarm type can be set on PV high or
    low, Deviation high or low, Band. 
    						
    							51-52-03-29
    Page 2
    Specifications
    Technical data
    InputAccuracy
    0.5 % of span ± 1 LSD
    Tº Stability 0.01 % of span per ºC for T/C, mA and mV input
    0.04 % per ºC for RTD input
    0.05 % per ºC for cold junction
    Sampling Rate Four samples per second (two samples per second for 2 loops
    Model)
    Input Filter Digital filter configurable via PC software.
    0.0 (OFF), from 0.1 s to 120.0 seconds.
    Input Resolution 13 bits; always four times better than display resolution
    Input Isolation Universal input isolated (type test at 3250 Vdc) from all outputs and
    from power supply with exception of SSR driver and second input
    Burnout current 1.5 µA
    Input Signal Failure
    · For thermocouple, detected by any lead break within 2 seconds,
    upscale burnout
    · 
    For RTD, detected by any lead break within 2 seconds, upscale
    burnout
    · 
    For DC linear: 0-50 mV detected within 2 seconds, upscale
    burnout
    Stray rejectionCommon Mode > 120 dB at 50/60 Hz giving negligible effect at up to 264 Vac 50/60
    Hz
    Serial Mode > 60 dB at 100 % of Span (at 50/60 Hz)
    ControlOutput typeType available:
    Output 1: Electromechanical relay or SSR drive (open collector)
    Output 2: Electromechanical relay or SSR drive (UDC120 only)
    (open collector)
    Electromechanical relay: SPDT contact
            Resistive load: 10 A at 120 V or 240 V
            Life time: > 600000 operations at 230 Vac / 5 amps
    SSR drive capability: SSR > 11 Vdc into 500 ohms minimum
    Isolation: not isolated from input and other SSR output
    Output algorithmConfigurable via PC software only:
    ON/OFF with hysteresis: 0.0 % to 100.0 %
    Configurable via PC software or via front face:
    Proportional bands: 0.1% to 999.9 %
    Reset: Off or from 1 second to 5999 seconds
    Rate: From 0 seconds to 5999 seconds
    Two independent PID available for two loops model.
    Cycle times: Up to two independent cycle times available for
    two loops model
    Cycle times selection: From 0.1 seconds to 256.0 seconds
    Duration From 1 min to 9 hr 00 min
    Output Type 1 relay (SPDT) 10 A resistive load (115/230 Vac)
    Timer
    (Models 110T)
    Triggering cause End of preset time
    Number of Alarms 1 Alarm setpoint
    Output type 1 relay (SPDT) 10 A resistive load (115/230 Vac)
    Alarm
    (Model 110A)
    Alarm type PV High or Low, Deviation High or Low, Band 
    						
    							51-52-03-29
    Page 3
    Technical data (continued)
    PhysicalDimensionDepth: 55 mm (2.16 in)
    Front Face: 96 mm x 96 mm (3.78 in x 3.78 in)
    W eight 400 grams maximum
    Cut out 92 mm x 92 mm (3.62 in x 3.62 in)
    Plug in with panel mounting lock
    Terminals Screw type (combination head)
    Panel thickness 3 mm (0.118 in) maximum
    Front PanelSealing IP54
    Parameters Set-upDial button For Process, Alarm SP and Timer duration
    Parameter set-up speed proportional to the angle speed.
    PowerType 115/230 Vac  50/60 Hz
    24/48 Vac  50/60 Hz
    Consumption 5 W atts
    EnvironmentalEMI Susceptibility Designed to meet EN50082-1: 1992 and EN50082-2: 1995
    EMI Emissions Designed to meet EN50081-1: 1992 and EN50081-2: 1994
    Safety Designed to comply with EN61010-1: 1993
    ApprovalEuropeCE Mark:Conformity with 72/23/EEC Low voltage directive
    Conformity with 89/336/EEC EMC directive
    United States / Canada Designed to meet UL and CSA certified C22.2 N1010-1 / 95
    standard (certified) (for altitude < 2000 m).
    Input Actuations
    Ranges
    Thermocouple types°F °C
    J32-572;  32-752;  32-999 0-300; 0-400;  0-537;  0-870
    K32-999;  32-2372 0-537; 0-999;  0-1300
    L32-932 0-500
    S32-2912 0-1600
    R32-2912 0-1600
    T32-752 0-400
    RTD: (3 wires connection)
    PT100 (IEC) a = 0.00385–40-140
    32-212
    32-392
    32-752–40-60
    0-100
    0-200
    0-400
    DC linear:10-50 mV
    4-20 mA*0-50 mV
    0-20 mA*
    * with 2.5 ohms resistance
    Operating Conditions
    Reference
    ConditionsOperative
    LimitsTransportation and
    Storage
    Ambient temperature23 °C ± 2 °C
    (73 °F ± 4 °F)0 °C to 60 °C
    (32 °F to 140 °F)–20 °C to 80 °C
    (–4 °F to 176 °F)
    Relative Humidity60-70 % 20-95 % non -condensing
    Voltage
    230 Vac ± 1 %
    115 Vac ± 1 %264/200 Vac
    132/100 Vac55/42 Vac
    27.5/21 Vac
    Frequency
    50/60 Hz ± 1 %47-63 Hz
    Source resistance< 5 ohms for
    thermocouple1000 ohms max for
    thermocouple
    Lead resistance for RTD< 0.1 ohm/lead (PT100) 50 ohms per lead 
    						
    							51-52-03-29
    Page 4
    External Dimensions, Panel Cutout
    92+0.8
    0 55 24
    96
    0.4 kg
    3 mm max.
    (in millimeter)
    Wiring Diagram
    3 21
    6 5 4
    9 8
    7
    13
    14
    15 10
    11
    12
    1817
    16
    N
    230 Vac115 Vac
    UDC110
    UDC120
    UDC120
    N
    48 Vac
    24 Vac
    +
    -
    +
    -
    N
    230 Vac
    24 Vac
    For more information, contact Honeywell sales at (800) 343-0228.Specifications are subject to change without notice.
    Distributor :
    Sensing and Control
    Honeywell Inc.
    11 West Spring Street
    Freeport, IL 61032
    www.honeywell.com/sensing
    51-52-03-29   1199   Printed in USA 
    						
    All Honeywell manuals Comments (0)

    Related Manuals for Honeywell Udc 100 L Manual