Sensing and Control, 11 West Spring Street, Freeport, Illinois 61032 Printed in U.S.A. n © Copyright 1999—Honeywell Inc. UDC100 Universal Digital Controller 51-52-03-29 11/99 Page 1 of 4 Specification Overview The UDC100 Universal Digital Controller is a microprocessor-based 1/4 DIN low cost temperature controller. It combines the highest operating simplicity with the benefits of digital technology. Its large dial allows easy parameter set-up. This micro- processor-based device provides a high degree of flexibility, repeatability, accuracy and temperature stability. Its simple ON-OFF/PID control algorithm with alarm and timer option capability make the UDC100 ideal for such applications as food processing (e.g. bakery ovens), small industrial furnaces and ceramics kilns. The UDC120 version has 2-loop control for excellent space integration and cost saving capabilities. Features High functionality at low cost The UDC100 offers the benefits of microprocessor technology at a very competitive price. Easy to use Thanks to analog-feel ergonomics the UDC100 is very simple to use. The interface has been selected to provide the most intuitive way to set-up parameters. The UDC100 is the ideal replacement for the well-known and popular AL/CL analog controller family. Custom built for OEMs The UDC100 has been designed to meet OEM requirements. Product over- lay, labels, input ranges and firmware can be tailored to your particular specification. The integrated solution of the timer and 2-loop model is a perfect example of how the UDC100 is adapt- able to meet specific market segment needs. High level of integration Several functions have been integrated to provide cost and space savings as well as to reduce wiring and set-up time. The UDC110T offers control and dura- tion of the process thanks to its integral timer function. The UDC120 integrates 2 loops in one DIN format to provide a high level of integration. Features, continued Rugged design for optimum repeatability and reliability The unit’s digital technology gives it extremely good stability in case of ambient temperature variation. This drift-free capability allows process control in the most severe industrial environments. All functional parts are mounted on a rugged chassis for easy replacement without disturbing field wiring. A rugged 10 Amp output relay is provided as standard for direct control application. Universal isolated input Input 1 can be configured for any input type and is isolated from relay output. In the dual loop model, input 2 type is identical to input 1 and is not isolated from input 1. Dual loop model This model offers two independent loops with two separate 3- or 4-digit displays. Control parameters and set- points are independent of each loop. The possibility exists of one single SP for both loops. Single or dual displays According to the version, the displays will have 3 or 4 digits. The UDC100 basic model has one display. Models Features, continued UDC110 and UDC120 provide dual displays for PV and SP reading or PV1 and PV2. Moisture-resistant front panel The front panel has IP54 front face protection against dust and water (hosedown). PC configuration editor Current parameters such as setpoints, alarm value and duration are config- urable from the instrument’s front face. All other parameters can be easily modified via a PC configurator pack- age. Specific configuration can be saved, uploaded or downloaded for maintenance management. Timer The UDC110T provides a configurable time period from 0 to 9 hours. The timer is initiated by a key on the front face. An electromechanical relay and a front face LED are activated at the end of the timeout period. The relay is latched and requires manual acknowledgement from the operator. Alarm selection One alarm is available with a remote electromechanical relay action. The alarm type can be set on PV high or low, Deviation high or low, Band.
51-52-03-29 Page 2 Specifications Technical data InputAccuracy 0.5 % of span ± 1 LSD Tº Stability 0.01 % of span per ºC for T/C, mA and mV input 0.04 % per ºC for RTD input 0.05 % per ºC for cold junction Sampling Rate Four samples per second (two samples per second for 2 loops Model) Input Filter Digital filter configurable via PC software. 0.0 (OFF), from 0.1 s to 120.0 seconds. Input Resolution 13 bits; always four times better than display resolution Input Isolation Universal input isolated (type test at 3250 Vdc) from all outputs and from power supply with exception of SSR driver and second input Burnout current 1.5 µA Input Signal Failure · For thermocouple, detected by any lead break within 2 seconds, upscale burnout · For RTD, detected by any lead break within 2 seconds, upscale burnout · For DC linear: 0-50 mV detected within 2 seconds, upscale burnout Stray rejectionCommon Mode > 120 dB at 50/60 Hz giving negligible effect at up to 264 Vac 50/60 Hz Serial Mode > 60 dB at 100 % of Span (at 50/60 Hz) ControlOutput typeType available: Output 1: Electromechanical relay or SSR drive (open collector) Output 2: Electromechanical relay or SSR drive (UDC120 only) (open collector) Electromechanical relay: SPDT contact Resistive load: 10 A at 120 V or 240 V Life time: > 600000 operations at 230 Vac / 5 amps SSR drive capability: SSR > 11 Vdc into 500 ohms minimum Isolation: not isolated from input and other SSR output Output algorithmConfigurable via PC software only: ON/OFF with hysteresis: 0.0 % to 100.0 % Configurable via PC software or via front face: Proportional bands: 0.1% to 999.9 % Reset: Off or from 1 second to 5999 seconds Rate: From 0 seconds to 5999 seconds Two independent PID available for two loops model. Cycle times: Up to two independent cycle times available for two loops model Cycle times selection: From 0.1 seconds to 256.0 seconds Duration From 1 min to 9 hr 00 min Output Type 1 relay (SPDT) 10 A resistive load (115/230 Vac) Timer (Models 110T) Triggering cause End of preset time Number of Alarms 1 Alarm setpoint Output type 1 relay (SPDT) 10 A resistive load (115/230 Vac) Alarm (Model 110A) Alarm type PV High or Low, Deviation High or Low, Band
51-52-03-29 Page 3 Technical data (continued) PhysicalDimensionDepth: 55 mm (2.16 in) Front Face: 96 mm x 96 mm (3.78 in x 3.78 in) W eight 400 grams maximum Cut out 92 mm x 92 mm (3.62 in x 3.62 in) Plug in with panel mounting lock Terminals Screw type (combination head) Panel thickness 3 mm (0.118 in) maximum Front PanelSealing IP54 Parameters Set-upDial button For Process, Alarm SP and Timer duration Parameter set-up speed proportional to the angle speed. PowerType 115/230 Vac 50/60 Hz 24/48 Vac 50/60 Hz Consumption 5 W atts EnvironmentalEMI Susceptibility Designed to meet EN50082-1: 1992 and EN50082-2: 1995 EMI Emissions Designed to meet EN50081-1: 1992 and EN50081-2: 1994 Safety Designed to comply with EN61010-1: 1993 ApprovalEuropeCE Mark:Conformity with 72/23/EEC Low voltage directive Conformity with 89/336/EEC EMC directive United States / Canada Designed to meet UL and CSA certified C22.2 N1010-1 / 95 standard (certified) (for altitude < 2000 m). Input Actuations Ranges Thermocouple types°F °C J32-572; 32-752; 32-999 0-300; 0-400; 0-537; 0-870 K32-999; 32-2372 0-537; 0-999; 0-1300 L32-932 0-500 S32-2912 0-1600 R32-2912 0-1600 T32-752 0-400 RTD: (3 wires connection) PT100 (IEC) a = 0.00385–40-140 32-212 32-392 32-752–40-60 0-100 0-200 0-400 DC linear:10-50 mV 4-20 mA*0-50 mV 0-20 mA* * with 2.5 ohms resistance Operating Conditions Reference ConditionsOperative LimitsTransportation and Storage Ambient temperature23 °C ± 2 °C (73 °F ± 4 °F)0 °C to 60 °C (32 °F to 140 °F)–20 °C to 80 °C (–4 °F to 176 °F) Relative Humidity60-70 % 20-95 % non -condensing Voltage 230 Vac ± 1 % 115 Vac ± 1 %264/200 Vac 132/100 Vac55/42 Vac 27.5/21 Vac Frequency 50/60 Hz ± 1 %47-63 Hz Source resistance< 5 ohms for thermocouple1000 ohms max for thermocouple Lead resistance for RTD< 0.1 ohm/lead (PT100) 50 ohms per lead
51-52-03-29 Page 4 External Dimensions, Panel Cutout 92+0.8 0 55 24 96 0.4 kg 3 mm max. (in millimeter) Wiring Diagram 3 21 6 5 4 9 8 7 13 14 15 10 11 12 1817 16 N 230 Vac115 Vac UDC110 UDC120 UDC120 N 48 Vac 24 Vac + - + - N 230 Vac 24 Vac For more information, contact Honeywell sales at (800) 343-0228.Specifications are subject to change without notice. Distributor : Sensing and Control Honeywell Inc. 11 West Spring Street Freeport, IL 61032 www.honeywell.com/sensing 51-52-03-29 1199 Printed in USA