INSTALLATION INSTRUCTIONS 69-1366-2 ® U.S. Registered Trademark Copyright © 2002 Honeywell • All Rights Reserved TotalZone® Add-A-Zone™(TAZ-4) Zone Control Panel APPLICATION The TAZ-4 is a zone panel used to add zones to the TZ-4. See Fig. 1. The TZ-4 provides up to four zones. Each TAZ-4 can add up to four additional zones for a total of 32 zones. The TAZ-4 is also compatible with the TZ-3, Rev 4.2.2, zone control panel and with the TAZ-1, TAZ-2 and TAZ-3, Rev 4, Add-A-Zone panels. Fig. 1. TAZ-4 Zone Control Panel. INSTALLATION When Installing this Product . . . 1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condi- tion. 2.Check the rating given in the instructions and on the product to make sure the product is suitable for your application.3.Installer must be a trained, experienced service techni- cian. 4.After installation is complete, check out product opera- tion as provided in these instructions. 5.Follow local codes for installation and application. CAUTION Voltage Hazard. Can cause electrical shock or equipment damage. Disconnect power before beginning installation. Location Select a location for the TAZ-4 as close as possible to the Total Zone panel. Mounting Mount the TotalZone Add-A-Zone Panel as close as possible to the TotalZone Panel. See Fig. 1. WIRING CAUTION Electrical Interference Hazard. Running cable near line voltage can interfere with panel operation. Run cable connecting AZ terminals at least 12 in. from line voltage wiring. IMPORTANT Be sure AZ1 and AZ2 wires do not cross and are a minimum of 12 in. from any line voltage wiring. If not possible, use shielded cable for AZ1 and AZ2 wires. NOTE: Only two wires are required to connect the TAZ-4 panels to the main TZ-4 panel. Each TAZ-4 is wired in a daisy chain or parallel to each other, connecting the AZ1 and AZ2 terminals between panels. Connect the AZ1 and AZ2 terminals on both panels using standard 18-gauge thermostat wire: 1.Connect AZ1 on the TotalZone panel to AZ1 on the Add-A-Zone panel. 2.Connect AZ2 on the TotalZone panel to AZ2 on the Add- A-Zone panel. M20362 TotalZone Panel TotalZone Add-A-Zone Panel AZ1 DIP-SWITCHES AZ2AZ1 AZ2 AZ1 AZ2TO NEXT ADD-A-ZONE PANEL 54321O N
TOTALZONE® ADD-A-ZONE™(TAZ-4) ZONE CONTROL PANEL 69-1366-2 2 3.Connect a 24V, 40 VA transformer to terminals R and C. R is Hot and C is 24 Vac (Common). See Fig. 2. 4.If there are five to ten ARD or ZD dampers connected to the TAZ-4, wire an additional 40 VA transformer to T1 and T2. See Fig. 2. 5.Connect damper and thermostat wiring as shown in Fig. 2.SETUP Each TAZ-4 panel has a set of five DIP switches. When using a TZ-4 and one TAZ-4, set DIP switches 1, 2, and 4 to off and switches 3 and 5 to on. Refer to Table 1 for other panel configurations. Identify the zones that are controlled by the TAZ-4 panel and set the DIP switches accordingly. If the TAZ-4 is connected to a TZ-3 zone control panel, set DIP switches 1, 2, and 4 to off, and switches 3 and 5 to on. Set the switches on additional TAZ-1, TAZ-2, and TAZ-3, or TAZ-4 panels to control the zones they are wired to; but be careful that there is no duplication of zone numbers. See Table 1. Table 1. DIP Switch Settings. ZonesSwitch Positions Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 5-8 001 01 6-9 001 10 7-10 0 0 1 1 1 8-11 0 1 0 0 0 9-12 0 1 0 0 1 10-13 010 10 11-14 010 11 12-15 011 00 13-16 011 01 14-17 011 10 15-18 011 11 16-19 100 00 17-20 100 01 18-21 100 10 19-22 100 11 20-23 101 00 21-24 101 01 22-25 101 10 23-26 101 11 24-27 110 00 25-28 110 01 26-29 110 10 27-30 110 11 28-31 111 00 29-32 111 01
TOTALZONE® ADD-A-ZONE™(TAZ-4) ZONE CONTROL PANEL 3 69-1366-2 Fig. 2. Wiring Add-A-Zone panel. ZONE DAMPER MOTORS M1 - common M4 - power open M6 - power closed DIP SWITCH SETTINGS 1 = ON 0 = OFF 12 345 N1N2N3N40 0 1 0 1 ZONES 5 6 7 8 0 0 1 1 0 ZONES 6 7 8 9 0 0 1 1 1 ZONES 7 8 9 10 0 1 0 0 0 ZONES 8 9 10 11 0 1 0 0 1 ZONES 9 10 11 12 0 1 0 1 0 ZONES 10 11 12 13 0 1 0 1 1 ZONES 11 12 13 14 0 1 1 0 0 ZONES 12 13 14 15 0 1 1 0 1 ZONES 13 14 15 16 0 1 1 1 0 ZONES 14 15 16 17 0 1 1 1 1 ZONES 15 16 17 18 1 0 0 0 0 ZONES 16 17 18 19 1 0 0 0 1 ZONES 17 18 19 20 1 0 0 1 0 ZONES 18 19 20 21 1 0 0 1 1 ZONES 19 20 21 22 1 0 1 0 0 ZONES 20 21 22 23 1 0 1 0 1 ZONES 21 22 23 24 1 0 1 1 0 ZONES 22 23 24 25 1 0 1 1 1 ZONES 23 24 25 26 1 1 0 0 0 ZONES 24 25 26 27 1 1 0 0 1 ZONES 25 26 27 28 1 1 0 1 0 ZONES 26 27 28 29 1 1 0 1 1 ZONES 27 28 29 30 1 1 1 0 0 ZONES 28 29 30 31 1 1 1 0 1 ZONES 29 30 31 32 ZONE LEDsON Damper open or opening OFF Damper closed or closing MOMENTARY PUSH BUTTONBoot — Clears microprocessor BOOT 1 “C” terminal connection is not required on battery powered, power stealing, or some electromechanical thermostats. 2 Leave jumper disconnected for “B” type or conventional thermostats. Connect jumper for “O” type thermostats. R C T1 T2 AZ2 AZ1 This diagram shows the typical thermostat and damper motor connections. For specific wiring for other thermostats and damper motors, refer to the Installation Instructions. M6 M4 M1 1 Zone 4 Thermostat CR C R Power-closed Spring-open (Model ZBD, ZDS, or ARD-PC)Power-open Spring-closed (Model ARD-PO)Power-open Spring-closed (Model ARD-PO) 24VAC, 40VA Transformer (Required if more than four dampers) 24VAC, 40VA Transformer AZ1 AZ2Add-A-Zone Panel(s) Add-A-Zone or TZ Panel(s) DAMPER XFRMPANEL XFRM Minneapolis, MN 55422 www.honeywell.com/yourhome ZONE N1ZONE N2COMMZONE N3ZONE N4 DIP SWITCH 1 O N2345 M6 M4 M1 1 Zone 3 Thermostat M6 M4 M1 1 Zone 2 Thermostat 456Z 123X Power-open Power-closed (Opposed Blade Damper Motors) O/B Y2 GW2M6M4M1W3/ AUXY1W1/ ERC Y1 W3/ AUX W2 W1/ E R CY2GLO/B Y1 W3/ AUX W2 W1/ E R CY2GLO/B Y1 W3/ AUX W2 W1/ E R CY2GLO/B Y1 W3/ AUX W2 W1/ E R CY2GLO/B LO/B Y2 GW2W3/ AUX Y1 W1/ E R C LO/B Y2 GW2W3/ AUX Y1 W1/ E R C LO/B Y2 GW2W3/ AUX Y1 W1/ E R C L 1 Zone 1 Thermostat ZONE 12ThermostatDamperZONE 22ThermostatDamperZONE 32ThermostatDamperZONE 42ThermostatDamper M20363
69-1366-2 G.H. Rev. 02-02 www.honeywell.com/yourhome TOTALZONE® ADD-A-ZONE™(TAZ-4) ZONE CONTROL PANEL Automation and Control SolutionsHoneywell Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers. TECHNICAL SUPPORT For Internet access: www.trolatemp.com or www.honeywell.com/yourhome/zoning/zoning_home.htm Call 1-800-828-8367 for zoning technical support line. To download Zoning literature: http://hbctechlit.honeywell.com