    							INSTALLATION INSTRUCTIONS
    69-1366-2
    ® U.S. Registered Trademark
    Copyright © 2002 Honeywell •  All Rights Reserved 
    TotalZone® Add-A-Zone™(TAZ-4)
     Zone Control Panel
    APPLICATION
    The TAZ-4 is a zone panel used to add zones to the TZ-4. See 
    Fig. 1. The TZ-4 provides up to four zones. Each TAZ-4 can 
    add up to four additional zones for a total of 32 zones. The 
    TAZ-4 is also compatible with the TZ-3, Rev 4.2.2, zone 
    control panel and with the TAZ-1, TAZ-2 and TAZ-3, Rev 4, 
    Add-A-Zone panels.
    Fig. 1. TAZ-4 Zone Control Panel.
    INSTALLATION 
    When Installing this Product . . .
    1.Read these instructions carefully. Failure to follow them 
    could damage the product or cause a hazardous condi-
    tion.
    2.Check the rating given in the instructions and on the 
    product to make sure the product is suitable for your 
    application.3.Installer must be a trained, experienced service techni-
    cian.
    4.After installation is complete, check out product opera-
    tion as provided in these instructions.
    5.Follow local codes for installation and application.
    CAUTION
    Voltage Hazard. 
    Can cause electrical shock or equipment damage.
    Disconnect power before beginning installation.
    Location
    Select a location for the TAZ-4 as close as possible to the 
    Total Zone panel.
    Mounting
    Mount the TotalZone Add-A-Zone Panel as close as possible 
    to the TotalZone Panel. See Fig. 1.
    WIRING
    CAUTION
    Electrical Interference Hazard. 
    Running cable near line voltage can interfere with 
    panel operation.
    Run cable connecting AZ terminals at least
    12 in. from line voltage wiring.
    IMPORTANT
    Be sure AZ1 and AZ2 wires do not cross and are a 
    minimum of 12 in. from any line voltage wiring. If not 
    possible, use shielded cable for AZ1 and AZ2 wires.
    NOTE: Only two wires are required to connect the TAZ-4 
    panels to the main TZ-4 panel. Each TAZ-4 is wired 
    in a daisy chain or parallel to each other, connecting 
    the AZ1 and AZ2 terminals between panels.
    Connect the AZ1 and AZ2 terminals on both panels using 
    standard 18-gauge thermostat wire:
    1.Connect AZ1 on the TotalZone panel to AZ1 on the   
    Add-A-Zone panel.
    2.Connect AZ2 on the TotalZone panel to AZ2 on the Add-
    A-Zone panel.
    M20362
    TotalZone Panel
    TotalZone
    Add-A-Zone Panel
    AZ1 DIP-SWITCHES
    AZ2AZ1
    AZ2
    AZ1
    AZ2TO NEXT
    ADD-A-ZONE
    PANEL
    54321O
    N 
    						
    							TOTALZONE® ADD-A-ZONE™(TAZ-4) ZONE CONTROL PANEL
    69-1366-2 2
    3.Connect a 24V, 40 VA transformer to terminals R and C. 
    R is Hot and C is 24 Vac (Common). See
     Fig. 2.
    4.If there are five to ten ARD or ZD dampers connected to 
    the TAZ-4, wire an additional 40 VA transformer to T1 
    and T2. See Fig. 2.
    5.Connect damper and thermostat wiring as shown
    in Fig. 2.SETUP
    Each TAZ-4 panel has a set of five DIP switches.  When using 
    a TZ-4 and one TAZ-4, set DIP switches 1, 2, and 4 to off and 
    switches 3 and 5 to on. Refer to Table 1 for other panel 
    configurations. Identify the zones that are controlled by the 
    TAZ-4 panel and set the DIP switches accordingly. 
    If the TAZ-4 is connected to a TZ-3 zone control panel, set 
    DIP switches 1, 2, and 4 to off, and switches 3 and 5 to on. 
    Set the switches on additional TAZ-1, TAZ-2, and TAZ-3, or 
    TAZ-4 panels to control the zones they are wired to; but be 
    careful that there is no duplication of zone numbers. See 
    Table 1. 
    Table 1. DIP Switch Settings.
    ZonesSwitch Positions
    Switch 1 Switch 2 Switch 3 Switch 4 Switch 5
    5-8 001 01
    6-9 001 10
    7-10 0 0 1 1 1
    8-11 0 1 0 0 0
    9-12 0 1 0 0 1
    10-13 010 10
    11-14 010 11
    12-15 011 00
    13-16 011 01
    14-17 011 10
    15-18 011 11
    16-19 100 00
    17-20 100 01
    18-21 100 10
    19-22 100 11
    20-23 101 00
    21-24 101 01
    22-25 101 10
    23-26 101 11
    24-27 110 00
    25-28 110 01
    26-29 110 10
    27-30 110 11
    28-31 111 00
    29-32 111 01 
    						
    							TOTALZONE® ADD-A-ZONE™(TAZ-4) ZONE CONTROL PANEL
    3 69-1366-2
    Fig. 2. Wiring Add-A-Zone panel.
    ZONE DAMPER MOTORS
    M1 - common
    M4 - power open
    M6 - power closed
    DIP SWITCH SETTINGS     1 = ON    0 = OFF
    12 345 N1N2N3N40 0 1 0 1 ZONES 5 6 7 8
    0 0 1 1 0 ZONES 6 7 8 9
    0 0 1 1 1 ZONES 7 8 9 10
    0 1 0 0 0 ZONES 8 9 10 11
    0 1 0 0 1 ZONES 9 10 11 12
    0 1 0 1 0 ZONES 10 11 12 13
    0 1 0 1 1 ZONES 11 12 13 14
    0 1 1 0 0 ZONES 12 13 14 15
    0 1 1 0 1 ZONES 13 14 15 16
    0 1 1 1 0 ZONES 14 15 16 17
    0 1 1 1 1 ZONES 15 16 17 18
    1 0 0 0 0 ZONES 16 17 18 19
    1 0 0 0 1 ZONES 17 18 19 20
    1 0 0 1 0 ZONES 18 19 20 21
    1 0 0 1 1 ZONES 19 20 21 22
    1 0 1 0 0 ZONES 20 21 22 23
    1 0 1 0 1 ZONES 21 22 23 24
    1 0 1 1 0 ZONES 22 23 24 25
    1 0 1 1 1 ZONES 23 24 25 26
    1 1 0 0 0 ZONES 24 25 26 27
    1 1 0 0 1 ZONES 25 26 27 28
    1 1 0 1 0 ZONES 26 27 28 29
    1 1 0 1 1 ZONES 27 28 29 30
    1 1 1 0 0 ZONES 28 29 30 31
    1 1 1 0 1 ZONES 29 30 31 32
    ZONE LEDsON Damper open or opening
    OFF Damper closed or closing
    MOMENTARY PUSH BUTTONBoot — Clears microprocessor
    BOOT
    1 “C” terminal connection is not required on battery powered, power stealing, or some electromechanical thermostats.
    2 Leave jumper disconnected for “B” type or conventional thermostats. Connect jumper for “O” type thermostats.
    R
    C
    T1
    T2
    AZ2 AZ1
    This diagram shows the typical thermostat and damper motor connections. For specific wiring
    for other thermostats and damper motors, refer to the Installation Instructions.
    M6 M4 M1
    1
    Zone 4 Thermostat
    CR
    C R
    Power-closed
    Spring-open
    (Model ZBD, ZDS,
    or ARD-PC)Power-open
    Spring-closed
    (Model ARD-PO)Power-open
    Spring-closed
    (Model ARD-PO)
    24VAC, 40VA 
    Transformer
    (Required if
    more than
    four dampers) 24VAC, 40VA 
    Transformer
    AZ1
    AZ2Add-A-Zone
    Panel(s)
    Add-A-Zone
    or TZ Panel(s)
    DAMPER
    XFRMPANEL
    XFRM
    Minneapolis, MN  55422
    www.honeywell.com/yourhome
    ZONE N1ZONE N2COMMZONE N3ZONE N4
    DIP SWITCH
    1 O
    N2345
    M6 M4 M1
    1
    Zone 3 Thermostat
    M6 M4 M1
    1
    Zone 2 Thermostat
    456Z
    123X
    Power-open
    Power-closed
    (Opposed Blade
    Damper Motors)
    O/B Y2 GW2M6M4M1W3/
    AUXY1W1/
    ERC
    Y1 W3/
    AUX W2 W1/
    E R CY2GLO/B Y1 W3/
    AUX W2 W1/
    E R CY2GLO/B Y1 W3/
    AUX W2 W1/
    E R CY2GLO/B Y1 W3/
    AUX W2 W1/
    E R CY2GLO/B LO/B Y2 GW2W3/
    AUX Y1 W1/
    E R C
    LO/B Y2 GW2W3/
    AUX Y1 W1/
    E R C
    LO/B Y2 GW2W3/
    AUX Y1 W1/
    E R C
    L
    1
    Zone 1 Thermostat
    ZONE 12ThermostatDamperZONE 22ThermostatDamperZONE 32ThermostatDamperZONE 42ThermostatDamper
    M20363 
    						
    							69-1366-2    G.H.  Rev. 02-02 www.honeywell.com/yourhome
    TOTALZONE® ADD-A-ZONE™(TAZ-4) ZONE CONTROL PANEL
    Automation and Control SolutionsHoneywell Honeywell Limited-Honeywell Limitée
    1985 Douglas Drive North 35 Dynamic Drive
    Golden Valley, MN  55422 Scarborough, Ontario
    M1V 4Z9
    Printed in U.S.A. on recycled 
    paper containing at least 10% 
    post-consumer paper fibers.
    TECHNICAL SUPPORT
    For Internet access: www.trolatemp.com  or
    www.honeywell.com/yourhome/zoning/zoning_home.htm
    Call 1-800-828-8367 for zoning technical support line.
    To download Zoning literature: http://hbctechlit.honeywell.com 
    						