Honeywell L8124a C Manual
Have a look at the manual Honeywell L8124a C Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
® U.S. Registered Trademark Copyright © 2001 Honeywell • All Rights Reserved INSTALLATION INSTRUCTIONS 60- 0786- 7 L8124B,E,G,L Aquastat ® Relays APPLICATION These immersion type controllers provide high limit, low limit, and circulator control in forced hydronic heating systems that include domestic hot water. Table 1 lists the various TRADELINE ® models and applications. SPECIFICATIONS Low Limit: Setting: 110°F to 220°F (43°C to 104°C), adjustable. Differential: 10°F to 25°F (6°C to 14°C), adjustable. High Limit: Setting: 130°F to 240°F (54°C to 116°C), adjustable. Differential: 10°F (6°C), fixed. Table 1. L8124 Models and Applications. a Multizone control can be provided using a separate circulator and R845 Relay for each zone.b Contacts are not powered; rated for switching of millivoltage loads. These Aquastat ® Relays have a diaphragm powerhead and Micro Switch Assembly that respond to temperature changes in the boiler water. L8124B has contacts rated for millivoltage loads. L8124E and G have large transformers and extra terminals for supplying power to low voltage valves. L8124L includes ZC-ZR terminals for multizone control, using a separate circulator and R845 Relay for each zone, and a large transformer and extra terminals for low voltage zone valves. All models have a case that allows vertical or horizontal mounting and include a tube of heat-conductive compound and limit stops. Do not use these Aquastat ® Relays where the pressure can exceed 100 psi (689.5 kPa) on the bulb when inserted directly or 200 psi (1379 kPa) when using an immersion well, or where the ambient temperature can exceed 150°F (66°C) at the case or 265°F (129°C) at the sensing element INSTALLATION When Installing This Product… 1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2.Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. 3.Installer must be a trained, experienced service technician. 4.After installation is complete, check out product operation as provided in these instructions. Model NumberBurner Control CircuitCan Be used For Multizone With Circulators a Number of V8043 Zone Valves Powered Without Additional TransformerElectrical Ratings Burner Circuit Circulator Circuit L8124B b— — 0.25A at 1/4 to 12 Vdc 120 Vac: 7.4A (full load), 44.4A (locked rotor). 240 Vac: 3.7A (full load), 22.2A (locked rotor). L8124E 24V Yes 2 1.25A at 24 Vac; 30 VA (total load) B 1-B2, TV-Z L8124G 120V — 2 Same as circulator rating. L8124L 120V Yes 2 60-0786-7.fm Page 1 Friday, March 11, 2005 3:19 PM
L8124B,E,G,L AQUASTAT® RELAYS 60-0786—7 2 . Fig. 1. Internal view of L8124G,L. WARNINGExplosion Hazard. Can cause serious injury, death or property damage. Use this product only in systems with a pressure relief valve. WARNINGElectrical Shock Hazard. Can cause serious injury or death. Disconnect power supply before beginning installation to prevent electrical shock or equipment damage. IMPORTANT: 1. Terminals on these Aquastat ® Relays are approved for copper wire only. 2. Immersion well must snugly fit sensing element and bulb must rest against bottom of well. Bend the tubing, if necessary, to hold bulb against bottom of well. Do not make a sharp bend in the tubing. A sharp bend may produce a break in the tubing and cause loss of fill. This condition causes the high and low limit controllers to be continuously made. 3. Use the heat-conductive compound furnished with these TRADELINE ® L8124 models to obtain best thermal response. Fold the plastic bag of compound lengthwise and twist it gently. Snip off the end and work open end of bag all the way into the well. Slowly pull the bag out while squeezing it firmly to evenly distribute the compound. MountingPosition mounting bracket properly on back of case for mounting case horizontally or vertically, as desired. See Fig. 2.Fig. 2. Convertible case is designed for horizontal or vertical mounting. 1.Shut off the electric power and remove the old control. Leave the old immersion well in place if it is suitable for use with the L8124. A 124904 Well Adapter (purchased separately) can be used to convert some old wells to be compatible with the L8124 mounting. See form 68-0040 for ordering information. 2.If the old well is unsuitable, drain the system, remove the old well, install a new immersion well, then refill the system. Refer to form 68-0040, Wells and Fittings for Temperature Controllers, to order well. Make sure the well is screwed in tightly enough to prevent leakage. NOTE: Do not attempt to tighten well using the case as a handle. 3.Loosen, but do not remove, the immersion well clamp screw. 4.If the immersion well fits the L8124 Immersion Well Clamp, proceed as follows: a. Partially fill the immersion well with heat-conductive compound. Fold the plastic bag of compound lengthwise and twist it gently. Snip off the end and work open end of bag all the way into the well. Slowly pull out the bag while squeezing it firmly to evenly distribute the compound in the well. Wipe excess compound from outer end of the well. b. Insert the bulb into the well, assuring the bulb bottoms in the well. c. Make sure the well fits into the hole in the case. Position the clamp properly on the well flange, then tighten the clamp screw. d. Center the loop of excess capillary tubing in front of the immersion well so it cannot touch any electrical parts. NOTE: Some models have a tubing length adjustable to 3 in. (76 mm). In these models, pull out extra tubing from inside the case if needed. M8853 DIFFERENTIAL SETTING LOW LIMIT SETTING GROUND SCREW HIGH LIMIT SETTING TRANSFORMER FOR THERMOSTATCIRCUIT CIRCULATOR RELAY BRACKET POSITION FOR VERTICAL MOUNTING BRACKET POSITION FOR HORIZONTAL MOUNTINGM1798 60-0786-7.fm Page 2 Friday, March 11, 2005 3:19 PM
L8124B,E,G,L AQUASTAT® RELAYS 3 60-0786—7 5.5.If the old immersion well is otherwise suitable but does not fit the L8124 Clamp, the124904 Well Adapter (ordered separately) must be used as follows:a. After loosening the immersion well clamp screw, fit the adapter onto the capillary tube (Fig. 3). b. Make sure the adapter fits into the hole in the case. Position the clamp properly on the adapter flange, then tighten the clamp screw. c. Return to step 4a. above, and complete the installation. Fig. 3. Position of bulb in immersion well and use of well adapter. Wiring IMPORTANT: Terminals on the L8124 Aquastat® Relay are approved for use with copper wire only. The terminals allow wraparound wiring only. 1.Strip 7/16 in. of insulation from the wire end. 2.Wrap the wire at least three fourths of the distance around the screw as shown. 3.Using a standard, flat-headed screwdriver, tighten the screw until the wire is snugly in contact with the screw and contact plate. 4. Tighten the screw an additional one-half turn. NOTE: Do not use a push-type ratchet screwdriver.Be sure all wiring complies with local electrical codes and ordinances. Do not exceed the limits in the Application section when applying this control. Disconnect power before wiring to prevent electrical shock or equipment damage. Refer to insert inside of Aquastat Relay cover or to Table 1 for electrical ratings and maximum load information. Use manufacturer instructions when wiring controlled equipment or refer to typical hookups in Fig. 4 through 11 . When the B1 terminal on the device being replaced is a 1/4 in. tab terminal, use the existing wiring harness terminals to install the replacement device. When B1 on the device being replaced is a screw terminal, insert the provided tab terminal to screw terminal adapter on the 1/4 in. tab terminals of the replacement device. After the adapter is installed, the existing wrap-around wire end can be reused to make an electrical connection to the B1 terminal. CONTROLLER CASE IMMERSION WELL CLAMP ADAPTERIMMERSION WELL SPUDBOILER OLD IMMERSION WELL ASSEMBLY BACK OF CONTROLLER CASE IMMERSION WELL CLAMP SCREWADAPTER SENSING BULB HEAT-CONDUCTIVE COMPOUND SETSCREW CAPILLARY TUBE (C)IMMERSION WELL CLAMP IMMERSION WELL CLAMP SCREWSHORT TUBE FITS IN CENTRAL RECESS OF ADAPTER BEND THE CAPILLARY TUBE TO HOLD THE SENSING BULB IN GOOD THERMAL CONTACT WITH THE IMMERSION WELL AT POINTS (A) AND (B). ASSURE THAT CAPILLARY TUBE FITS FREELY IN THE ADAPTER SO THE TENSION OF THE CAPILLARY TUBE AT POINT (C) HOLDS THE SENSING BULB IN GOOD THERMAL CONTACT WITH THE IMMERSION WELL AT POINT (D). M8830 1 1 2 2(D) (B)(A) M8843 60-0786-7.fm Page 3 Friday, March 11, 2005 3:19 PM
L8124B,E,G,L AQUASTAT® RELAYS 60-0786—7 4 Fig. 4. L8124B in gas-fired, millivolt, forced hot water, tankless, zoned pump system. Fig. 5. L8124B single zone connections and internal schematic.Fig. 6. L8124Esingle zone connections and internal schematic. L1 (HOT) L2 1 2 3 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED. B1 IS 1/4 IN. TAB TERMINAL. TT 1 23 456 M8841 THPP 1 2 3TRPP MILLIVOLTAGE GAS VALVE (eg, VS820)Q313A PILOT GENERATOR L8124E G L2 L1 C1 C2TT B2 B1 T87F R845 RELAY TT 1 23 456 T87F R845 RELAY TT 1 23 456 T87F R845 RELAY PUMP PUMP PUMP M8842 L1 (HOT) L2 1 3 1 2 2 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED. B1 IS 1/4 IN. TAB TERMINAL. MILLIVOLTAGEGAS VALVE LINE VOLTAGE CIRCULATOR C2C1 B2 B1 TH TH PP PP R BHIGH LIMIT1K1 B R W LOW LIMIT/ CIRCULATOR1K21 G T TL8124B LOW VOLTAGE THERMOSTAT 1K3 1K2 POWERPILE® 3M8803 L1 (HOT) L2 1 3 1 2 3 2 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED. B1 IS 1/4 IN. TAB TERMINAL. LOW VOLTAGE GAS VALVE (eg, VR8300)LINE VOLTAG ECIRCULATOR C2C1 B2 B1 R B HIGH LIMIT Z 1K1 B R W LOW LIMIT/ CIRCULATOR 1K 21 G T TVL8124E LOW VOLTAGE THERMOSTAT 1K2 TR TH 60-0786-7.fm Page 4 Friday, March 11, 2005 3:19 PM
L8124B,E,G,L AQUASTAT® RELAYS 5 60-0786—7 Fig. 7. L8124E in 24V, gas-fired, forced hot water, tankless, zoned, pump system. Fig. 8. L8124E in 24V, gas-fired forced hot water, tankless system. Fig. 9. L8124G,L multizone system with zone valve connections and internal schematic. L1 (HOT) L2 1 2 3 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED. B1 IS 1/4 IN. TAB TERMINAL. TT 1 23 456 M1794A TH 123TRLOW VOLTAGE GAS VALVE (eg, VR8300) L8124E AQUASTAT® RELAY G L2 L1 C1 C2TT B2 B1 T87F R845 RELAY TT 1 23 456 T87F R845 RELAY TT 1 23 456 T87F R845 RELAY PUMP PUMP PUMP L1 (HOT) L21 2 3 2 3 1 TH TR LOW VOLTAGE GAS VALVE (eg, VR8300)L8124E G L2 L1 C1 C2TT B2 B1 T87F POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. CONTROL CASE MUST BE CONNECTED TO EARTH GROUND . USE GROUNDING SCREW PROVIDED. B1 IS 1/4 IN. TAB TERMINAL.CIRCULATOR M1796A M1795B L1 (HOT) L2 1 1 2 3 4 3 2 4 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. UP TO TWO V8043F ZONE VALVES CAN BE POWERED WITH L8124G,L. ADD ADDITIONAL TRANSFORMER FOR EVERY TWO OR LESS VALVES. CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED. B1 IS 1/4 IN. TAB TERMINAL. LINE VOLTAGEOIL BURNER RELAY OR GAS VALVE LINE VOLTAG ECIRCULATOR B2 C2 C1 ZR B1 RB HIGH LIMIT Z 1K1 B R W LOW LIMIT/ CIRCULATOR 1K 21 G T TVL8124G,L ZONE 1 THERMOSTAT 1K2 V8043F TH TRTHTR ZONE 2 THERMOSTAT V8043F TH TRTHTR ZC 60-0786-7.fm Page 5 Friday, March 11, 2005 3:19 PM
L8124B,E,G,L AQUASTAT® RELAYS 60-0786—7 6 Fig. 10. L8124E multizone system with circulator connections and internal schematic. Fig. 11. L8124L multizone system with circulator connections and internal schematic. M8828 L1 (HOT) L21 1 2 3POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED. B1 IS 1/4 IN. TAB TERMINAL. 2 1 4 3 5 6 ZONE 1 LOW VOLTAGETHERMOSTAT R845A RELAY ZONE 1 ZONE 1 CIRCULATOR TO ADDITIONAL R845A RELAYS FOR OTHER ZONES 2 3 LOW VOLTAGE GAS VALVE (eg, VR8300) C2C1 B2 B1 R B HIGH LIMIT Z 1K1 B R W LOW LIMIT/ CIRCULATOR 1K 21 G T TVL8124E 1K2 TR TH THTR M8829 L1 (HOT)L21 3 1 2 3 2 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED. B1 IS 1/4 IN. TAB TERMINAL. 2 1 4 3 5 6 LOW VOLTAGE THERMOSTAT ZONE 1 ZONE 2 LOW VOLTAGE THERMOSTAT R845A RELAY ZONE 2 ZONE 2 CIRCULATO R TO ADDITIONAL R845A RELAYS FOR OTHER ZONES LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE LINE VOLTAGE CIRCULATOR ZONE 1 B2 C2 C1 ZR B1 RB HIGH LIMIT Z 1K1 B R W LOW LIMIT/ CIRCULATOR 1K 21 G T TVL8124L 1K2 ZC 60-0786-7.fm Page 6 Friday, March 11, 2005 3:19 PM
L8124B,E,G,L AQUASTAT® RELAYS 7 60-0786—7 Fig. 12. Relationship of setpoints and differential adjustments. Fig. 13. Setting stop in position to limit the high limit setting to 180°F (82°C). OPERATION (FIG. 12) High LimitThe high limit opens and turns off the burner when the water temperature reaches the set point. The high limit automatically resets after the water temperature drops past the set point and through the 10°F (6°C) differential. WARNINGExplosion Hazard. Can cause serious injury, death or property damage. Use this product only in systems with a pressure relief valve. Low Limit and CirculatorOn a temperature rise, with the adjustable differential at the minimum setting of 10°F (6°C), the burner circuit (R-B) breaks and the circulator circuit (R-W) makes at the control set point. On a temperature drop of 10°F (6°C) below the set point, the R-B circuit makes and the R-W circuit breaks. At any differential setting greater than 10°F (6°C), the R-B make temperature and R-W break temperature remains the same control setting minus 10°F (6°C). The R-B break and R-W make temperature are the setpoint temperature plus the difference between the differential setting and 10°F (6°C). EXAMPLE: The set point is set at 140°F (60°C); the differential is set at 25°F (14°C). On a temperature rise, R-B breaks and R-W makes at 155°F (68°C). On a temperature fall, R-B makes and R-W breaks at 130°F (54°C). SETTING Follow the boiler manufacturer recommendations when making the L8124 settings. The high limit setting must be at least 20°F (11°C) higher than the low limit setting. Place the indicators over the selected temperature marks. Set the low limit differential by turning the differential adjustment knob to the desired amount of differential. Set the thermostat heat anticipator at 0.2A. Setting StopA setting stop (Honeywell part no. 126580, ordered separately) can be installed on the adjusting knob to prevent turning the knob beyond a predetermined point. Fig. 13 shows it installed on high limit switch knob to prevent setting higher than 200°F (93°C). To install the setting stop, proceed as follows: 1.Turn knob to the established setting limit. 2.Place setting stop over knob in position so arm of setting stop strikes (after stop is pressed into place) projection A and prevents turning the knob beyond the desired limit setting. IMPORTANT: The setting stop cannot be reset once it is in place. If the stop must be removed, snip it off with cutters—do not twist it off. 3.Press setting stop tightly onto knob so its inner teeth securely engage knob. 4.Turn knob back and forth several times to make sure stop functions properly. 5.When all settings are made, replace the cover. CHECKOUT Put the system into operation and observe each function through at least one complete cycle. Be sure the control operates as intended. LOW LIMIT AND CIRCULATOR SETTING HIGH LIMITSETTINGSWITCH BREAKS ON TEMPERATURE RISE. BURNER TURNS OFF. CIRCULATOR OPERATES ON A CALL FOR HEAT. SWITCH MAKES ON TEMPERATURE FALL. BURNER OPERATES ON A CALL FOR HEAT. SWITCH MAKES R-W AND BREAKS R-B ON TEMPERATURE RISE. SWITCH MAKES R-B AND BREAKS R-W ON TEMPERATURE FALL. BURNER IS ON TO MAINTAIN MINIMUM WATER TEMPERATURE. CIRCULATOR IS OFF. 110°F (43°C) 240°F (116°C) M1523 SWITCH MAKES R-W AND BREAKS R-B ON TEMPERATURE RISE. WHEN WATER REACHES PROPER TEMPERATURE, THE BURNER SHUTS OFF OR THE CIRCULATOR PUMP STARTS (WHEN CALLING FOR HEAT). 1 1 10°F (6°C) DIFFERENTIAL 25°F (14°C) DIFFERENTIAL 10°F (6°C) DIFFERENTIAL 220200 160 140 180 SETTING STOP SETTING STOP ARM PROJECTION AKNOB SET AT 180°F (82°C) M28441 1 SCALE MARKINGS IN FAHRENHEIT ONLY. 60-0786-7.fm Page 7 Friday, March 11, 2005 3:19 PM
L8124B,E,G,L AQUASTAT® RELAYS 60-0786—7 8 MATERIAL SAFETY DATA SHEET Section 1. Product And Company Identification Product Name: Heat Conductive Compound MSDS ID: DS9021 Synonyms: MS1699 Product Use: Heat conductive material used to enhance contact and heat transfer in temperature sensor applications. Manufacturer: Honeywell Inc., 1985 Douglas Drive North, Minneapolis, MN 55422.Date Released: October 8, 1999 Customer Response Center: 800-328-5111 Emergency Telephone Information: 888-809-3787 NFPA Ratings: Health 0; Flammability 1; Reactivity 0; Personal Protection B Section 2. Composition, Information on Ingredients Additional Information: Part No. 120650 (0.5 oz tube); Part No. 107408 (4 oz can); Part No. 197007 (5 gallon container). May also contain minute amounts of lithium and molybdenum lubricant compounds. Section 3. Hazard Identification Acute Health Effects:Skin: Excessive contact may cause skin irritation and dermatitis. Eye: Direct contact with eye will cause irritation. Inhalation: No adverse effects are expected. Ingestion: Ingestion of product may cause nausea, vomiting and diarrhea. Chronic Health Effects:Existing skin rash or dermatitis may be aggravated by repeated contact. OSHA Hazard Classifications: None. Carcinogenicity: Not considered to be a carcinogen by either OSHA, NTP, IARC, or ACGIH. Section 4. First Aid MeasuresEye Contact: Flush eyes with water for 15 minutes. Remove any contact lenses and continue to flush. Obtain medical attention if irritation develops and persists.Skin Contact: Remove excess with cloth or paper. Wash thoroughly with mild soap and water. Obtain medical attention if irritation develops and persists. Ingestion: Contact physician or local poison control center immediately. Inhalation: Remove patient to fresh air and obtain medical attention if symptoms develop. Section 5. Fire Fighting MeasuresMaterial Flash Point: > 383°F (195°C). Will burn if exposed to flame. Extinguishing Media: Carbon dioxide, dry chemical or foam. Special Fire Fighting Procedures: None. Explosion Hazards: None. Aluminum powder can react with water to release flammable hydrogen gas. In the form of this product, this reaction is not expected. Section 6. Accidental Release MeasuresScrape up and dispose of as solid waste in accordance with state and federal regulations. Ingredient CAS Number Percent PEL TVL #2 Lithium Complex Grease (70%): Mineral Oil 64742-65-0 35-50 5 mg/m 35 mg/m3 Mineral Oil 64742-62-7 20-25 5 mg/m35 mg/m3 Lithium Hydrostearate/Sebacate Complex68815-49-6 4-9 — — Zinc Alkyldithiophosphate 68649-42-3 0-2 — — Aluminum Paste (30%): Aluminum, as Al 7429-90-5 20-25 15 mg/m 310 mg/m3 Aliphatic Petroleum Distillates 8052-41-3 10-15 2900 mg/m3525 mg/m3 Stearic Acid 57-11-4 1-2 — — Aromatic Petroleum Distillates 64742-95-6 1-2 5 mg/m35 mg/m3 60-0786-7.fm Page 8 Friday, March 11, 2005 3:19 PM
L8124B,E,G,L AQUASTAT® RELAYS 9 60-0786—7 Section 7. Handling and StorageStore in dry place. Keep container closed when not in use. Section 8. Exposure Controls and Personal Protection. Ventilation: No special ventilation is required when working with this product. Respiratory Protection: None required. Eye Protection: Not normally required. However, use chemical safety goggles or faceshield if potential for eye contact exists, especially if material is heated. Hand/Clothing Protection: Not normally required. Protective gloves and clothing are recommended, as material is difficult to remove from skin and clothing. Other Protective Equipment: None required. Section 9. Physical and Chemical Properties Appearance/Odor: Aluminum color, semi-solid material, pleasant odor. Solubility in Water: Negligible. Specific Gravity: 0.86. Section 10. Stability and ReactivityStability: Stable. Reactivity: Hazardous polymerization will not occur.Incompatibilities: Strong oxidizing agents and halogens. Hazardous Decomposition Products: Carbon dioxide, carbon monoxide. Section 11. Toxicology Information.No data available. Section 12. Ecological InformationChemical Fate Information: Hydrocarbon compo- nents will biodegrade in soil; relatively persistent in water. Section 13. Disposal ConsiderationDispose of as solid waste in accordance with local, state and federal regulations. Section 14. Transportation InformationDOT Classification: Not classified as hazardous. Section 15. Regulatory InformationSARA Title III Supplier Notification: Include in Section 311/312 inventory reports if amounts exceed 10,000 pounds. Aluminum compounds are subject to the reporting requirements under Section 313 of Emergency Planning and Community Right-To-Know Act of 1986 (40 CFR 372). Ingredients listed in TSCA Inventory. Section 16. Other InformationThis information is furnished without warranty, expressed or implied, except that is is accurate to the best of our knowledge. Prepared by: PROSAR, 1295 Bandana Boulevard, Suite 335, St. Paul, MN 55108 (651-917-6100). 60-0786-7.fm Page 9 Friday, March 11, 2005 3:19 PM
60-0786—7 10 60-0786-7.fm Page 10 Friday, March 11, 2005 3:19 PM