Home
>
Honeywell
>
Control panel
>
Honeywell control panel VISTA15P VISTA20P Security System User Manual
Honeywell control panel VISTA15P VISTA20P Security System User Manual
Have a look at the manual Honeywell control panel VISTA15P VISTA20P Security System User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
– 41 – Testing the System About Testing the System Using the Test mode allows each protection point to be checked for proper operation. Testing should be conducted weekly to ensure proper operation . The keypad sounds a single beep about every 30 sec onds as a reminder that the system is in the Test mode. Alarm messages are not sent to your Central Statio n while Test mode is on. 1. Disarm the system and close all protected windows, doors, etc. The READY indicator light should come o n if all zones are intact (i.e., all protected window s, doors, etc. are closed. Alpha Displays: DISARMED READY TO ARM 2. + 5 TEST then [0] (walk) (Master Code) The Dial test (option “1”) is intended for the inst aller and should not be used unless directed to do so by your Security System Representative. 1 = DIAL, 0 = WALK 3. Listen. The external sounder should sound for about 1 second then turn off. If the sounder does not sound , CALL FOR SERVICE. The “Test in Progress” display appears only on the keypad that started the test. TEST IN PROGRESS 4. Fault zones. Open each protected door and window in turn and listen for three beeps from the keypad. Identification (zone number or zone description) of each faulted protection point should appear on the displ ay. The display clears when the door or window is closed. 5. Walk in front of any interior motion detectors ( if used) and listen for three beeps. The identification of the detector should appear on the display when it is activated. The display clears when no motion is detected. Note that if wireless motion detectors are used, there is a 3-minute delay between activati ons. This conserves battery life. 6. Test all smoke detectors, following the manufact urers instructions. The identification of each detector should appear on th e display when each is activated. If a problem is experienced with any protection po int (no confirming sounds, no display), call for service immediately. When all protection points have been checked and a re intact (closed), there should be no zone identification numbers displayed on the keypad. 7. Exit test mode: + 1 OFF (Security Code) If the test mode is inadvertently left active, it a utomatically turns off after 4 hours. During the final five minutes, the keypad will emit a double beep every 30 seconds.
– 42 – Trouble Conditions Check and Battery Displays The word CHECK on the keypads display, accompanied by a beeping at the keypad, indicates a trouble condit ion in the system. To silence the beeping for these conditions, press a ny key. 1. A display of CHECK and one or more zone numbers indicates that a problem exists with the displayed zone(s) and requires your attention. Determine if the zone(s) d isplayed are intact and make them so if they are not. If the pro blem has been corrected, the display can be cleared if you enter the OFF sequence (security code plus OFF key) twice. If the display persists, CALL FOR SERVICE . Note: A display of CHECK 70 on Alpha Display keypads indicates that the wiring connection to the externa l sounder is at fault (opened or shorted), and you should CALL F OR SERVICE. See “BELL FAILURE” on next page. A display of CHECK 90 indicates that RF interference may be impeding the operation of wireless sensors* in the system. See “ Rcvr Jam” on next page. 2. If there are wireless sensors* in your system, the CHECK condition may also be caused by some change in the environment that prevents the wireless receiver fro m receiving messages from a particular sensor. CALL FOR SERVIC E if this occurs. * Not all systems use wireless sensors. IF YOU CANNOT CORRECT A CHECK DISPLAY, CALL FOR SERVICE . TYPICAL CHECK DISPLAYS 06 CHECK AC FIXED-WORD DISPLAY KEYPAD C H E C K 0 6 B E D R O O M W I N D O W ALPHA DISPLAY KEYPAD
– 43 – Trouble Conditions (cont’d) Words or letters in parentheses ( ) are those that are displayed on Fixed-Word Display keypads. Other Trouble Displays * Any “beeping” that accompanies a trouble display can be stopped by depressing any key on the keypad or by entering an OFF sequence (code + OFF) ** Not all systems use wireless sensors. COMM. FAILURE Indicates that a failure has occurred in (or FC) the telephone communication portion of your system. CALL FOR SERVICE. SYSTEM LO BAT Indicates that a low system battery (or BAT with no condition exists. Display is zone No.) accompanied by beeping* at the keypad. If this condition persists for more than one day (with AC present), CALL FOR SERVICE. LO BAT Indicates that there is a low battery + zone descriptor condition in the wireless transmitt er** (or BAT with number displayed (00 is RF keypad). zone No.) Accompanied by a single beep * (about once every 30 seconds) at the keypad. Either replace the battery yourself, or CALL FOR SERVICE. If the battery is not replaced within 30 days, a CHECK display may occur. Rcvr Jam Wireless part of the system is experiencing (or CHECK 90 ) RF interference which may impede reception from wireless sensors.** ALARM 1xx FAULT 1xx CHECK 1xx (or 91) Indicates a communication problem between the control and a connected device (e.g., RF receiver, zone expander) where the “xx” indicates the device address. CALL FOR SERVICE. MODEM COMM (or CC) Indicates that the control is on-line with the Central Monitoring Stations remote computer. The control will not report system activity while on-line. Wait a few minutes — the display should disappear. BELL FAILURE Indicates that the wiring connection to (or CHECK 70 ) the external sounder is at fault (open or shorted). Accompanied by “beeping” at the keypad. CALL FOR SERVICE.
– 44 – Trouble Conditions (cont’d) Other Trouble Displays (Continued ) AC LOSS The system is operating on battery power (or NO AC ) only due to an AC power failure. If only some lights are out on the premises, check circuit breakers and fuses and reset or replace as necessary. If AC power cannot be restored and a “low system battery” message appears (see previous page), CALL FOR SERVICE . Busy-Standby (or dI) If this message remains displayed for more than 1 minute, system is disabled. CALL FOR SERVICE . OPEN CIRCUIT The keypad is not receiving signals from (or OC ) the control. CALL FOR SERVICE. Long Rng Trbl If part of your system, back-up (or bF) communication device has failed. CALL FOR SERVICE. TELCO FAULT The telephone line has a problem. (or CHECK 94 ) CALL FOR SERVICE. Total Power Failure If there is no keypad display at all, and the READY indicator is not lit, operating power (from AC and back-up battery) for the system has been interrupted and the system is inoperative. CALL FOR SERVICE. In The Event Of Telephone Operational Problems In the event of telephone operational problems, dis connect the control from the phone line by removing the plug from the phone wall jack. We reco mmend that your installer demonstrate this disconnection on installation of the system. Do not attempt to disconnect the phone connection inside the control. Doing so will result in the loss of your phone lines. If the regular phones work correctly after the control has been disconnected from the phone wall jack, the control has a problem and you should immediately call for service . If upon disconnection of the control, there is still a problem on the phone line, notify the Telephone Company that they have a problem and request prompt phone repair service. The user may n ot under any circumstances attempt any service or repairs to the security system. Repairs must be made only by authorized service (see the LIMITED WARRANTY statement for information on ho w to obtain service).
– 45 – Maintaining Your System Taking Care of Your System The components of your security system are designed to be as maintenance-free as possible. However, to make sure that your system is in reliable working condition, do the fol lowing: 1. Test your system weekly . 2. Test your system after any alarm occurs. Silencing Low Battery Warning Tones at the Keypad You can silence the keypad’s warning tones by press ing the OFF key, but the keypads low battery message display will r emain on as a reminder that you have a low battery condition in o ne or more of your wireless sensors. When you replace the weak battery with a fresh one, the sensor sends a good battery signal to the con trol as soon as the sensor is activated (opening/closing of door, windo w, etc.), causing the low battery display to turn off. If the sensor is n ot activated, the display will automatically clear within approximate ly 1 hour. Replacing Batteries in Wireless Sensors Wireless sensors may not have been used in your security system IMPORTANT: Use only batteries recommended by your installer as replacement. Each wireless sensor in your system has a 9-volt or 3-volt battery. The system detects a low battery in wireless sensor s, including smoke detectors, the personal emergency transmitter, and the portable wireless keypad and displays a low battery message* . (A low battery in a portable wireless keypad is detected as soon a s one of its keys is pressed, and displayed as 00.). Battery-operated smoke detectors with a low battery also emit a single chirp sound appr oximately once every 20–30 seconds. Alkaline batteries provide a minimum of 1 year of o peration, and in most units and applications, provide 2–4 years of s ervice. 3-volt lithium batteries provide up to 4 or more years of operation. Actual battery life will depend on the environment in whic h the sensor is used, the number of signals that the transmitter in the sensor has had to send, and the specific type of sensor. Factors such as humidity, high or low temperatures or large swings in temperature, may all lead to the reduction of actual battery life in an installa tion. * The low battery message comes on as a warning that battery replacement in indicated sensor(s) is due within 30 days. In th e meantime, a sensor causing a low battery indication is still fully ope rational. Routine Care Treat the components of your security system as you would any other electrical equipment. Do not slam sensor-prot ected doors or windows. Keep dust from accumulating on the keypad and all protective sensors, particularly on motion sensors and smoke d etectors. The keypad and sensors should be cleaned carefully with a dry soft cloth. Do not spray water or any other fluid on the units.
– 46 – Fire Alarm System THIS SECTION APPLIES ONLY TO RESIDENTIAL SYSTEMS General Your fire alarm system (if installed) is on 24 hours a day, for continuous protection. In the event of an emergency , the strategically located smoke and heat detectors will sound their alarms and automatically send signals to your syste m, triggering a loud, interrupted pulsed sound* from the Keypad(s) and any external sounders. A FIRE message will appear at yo ur Keypad and remain on until you silence the alarm (see below fo r silencing fire alarms). * Temporal pulse sounding is produced for Fire alarms , as follows: 3 pulses–pause–3 pulses–pause–3 pulses–pause. . . , repeated. TYPICAL FIRE EMERGENCY DISPLAYS F I R E 0 1 M A S T E R B E D R O O M 01 0101 01 ALARM FIRE AC ALPHA DISPLAY KEYPAD FIXED-WORD DISPLAY KEYPAD Silencing Fire Alarms and Clearing Memory of Alarm 1. You can silence the alarm at any time by pressin g the OFF key (the security code is not needed to silence fire al arms). To clear the display, enter your code and press the OFF key again (to clear Memory of Alarm). 2. If the Keypads FIRE display does not clear afte r the second OFF sequence, smoke detectors may still be responding t o smoke or heat producing objects in their vicinity. Investiga te, and should this be the case, eliminate the source of heat or s moke. 3. If this does not remedy the problem, there may s till be smoke in the detector. Clear it by fanning the detector for about 30 seconds. When the problem has been corrected, clear the disp lay by entering your code and pressing the OFF key. Smoke Detector Reset Depending on the type of smoke detectors in your sy stem, it may be necessary to reset the smoke detectors after a fi re alarm has been turned off. Check with your installer. This reset is accomplished at a keypad, as follows: Enter security code ( except “arm only” user), then press the [1] key. NOTE: During smoke detector reset, “FAULT xx” appears (a bout six seconds) and should disappear if the detector is cl ear.
– 47 – Fire Alarm System (cont’d) THIS SECTION APPLIES ONLY TO RESIDENTIAL SYSTEMS Manually Initiating a Fire Alarm 1. Should you become aware of a fire emergency before your smoke or heat detectors sense the problem, go to your neares t keypad and manually initiate an alarm by pressing the panic ke y assigned for FIRE emergency for 2 seconds (see below). If a key pair has been assigned for fire, press both keys at the same time . See the Using the Panic Keys section below for further details. 2. Evacuate all occupants from the premises. 3. If flames and/or smoke are present, leave the pr emises and notify your local Fire Department immediately. 4. If no flames or smoke are apparent, investigate the cause of the alarm. The zone number(s) of the zone(s) in an alar m condition will be displayed at the keypad. Using the Panic Key(s) Assigned for FIRE Emergency A key or key pair may have been assigned for manual ly initiating a FIRE alarm. See the Panic Keys section for key assignments. For convenience, indicate the key or key pair assig ned for fire below. I n d i v i d u a l K e y s A B C Press the individual key assigned for fire for 2 se conds. O R K e y P a i r s 1 OFF and READY (zone 95) READY and # (zone 99) 3 STAY and # (zone 96) DISPLAYS FOLLOWING MANUAL INITIATION OF A FIRE ALARM F I R E 9 5 95 9595 95 ALARM FIRE AC ALPHA DISPLAY KEYPAD FIXED-WORD KEYPAD Carbon Monoxide Alarms If installed, carbon monoxide detectors provide con tinuous protection. If a high level of carbon monoxide is detected, an interrupted pulsed alarm sound occurs at the keypads and the detector( s). Immediately move to a spot where fresh air is available, prefer ably outdoors. From a safe area, call your security service provider fo r further instructions. To silence the keypad sounding, press the OFF key. To silence the detector, see its instructions. Press both keys of the key pair assigned for fire at the same time.
– 48 – Fire Alarm System (cont’d) THIS SECTION APPLIES ONLY TO RESIDENTIAL SYSTEMS National Fire Protection Association Recommendations on Smoke Detectors With regard to the number and placement of smoke/he at detectors, we subscribe to the recommendations contained in the N ational Fire Protection Associations National Fire Alarm Code (NFPA 72) no ted below. Early warning fire detection is best achieved by th e installation of fire detection equipment in all rooms and areas of the h ousehold as follows: A smoke detector installed outside of each separate s leeping area, in the immediate vicinity of the bedrooms and on each addi tional story of the family living unit, including basements and excludi ng crawl spaces and unfinished attics. In addition, the NFPA recommends that you install h eat or smoke detectors in the living room, dining room, bedroom(s), kitche n, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages. DININGKITCHEN BEDROOM BEDROOM BEDROOM BEDROOM LIVING ROOM BEDROOM BDRM DINING LIVING ROOM TV ROOM KITCHEN BEDROOM BEDROOM TO BR LVNG RM BASEMENT KTCHN.CLOSED DOOR GARAGE Smoke Detectors for Minimum Protection Smoke Detectors for Additional Protection Heat-Activated Detectors BDRM floor_plan-001-V1
– 49 – Fire Alarm System (cont’d) THIS SECTION APPLIES ONLY TO RESIDENTIAL SYSTEMS Emergency Evacuation • FRONT • BA CK • BA TH BEDR OOMKITCHEN BACK DOOR 1 FLOORST BEDR OOM 2 FLOORND BATHBEDR OOMPORCH CLOSET BEDR OOM BEDR OOM Establish and regularly practice a plan of escape i n the event of fire. The following steps are recommended by the National Fire Protection Association: 1. Position your detector or your interior and/or exterior sounders so that they can be heard by all occupants. 2. Determine two means of escape from each room. One path of escape should lead to the door that permits normal exit from the building. The other may be a window, should your path be impassable. Station an escape ladder at such windows if there is a long drop to the ground. 3. Sketch a floor plan of the building. Show window s, doors, stairs and rooftops that can be used to escape. Indicate escape routes for each room. Keep these routes free from obstruction and post copies of the escape routes in every room. 4. Assure that all bedroom doors are shut while you are asleep. This will prevent deadly smoke from entering while you escape. 5. Try the door. If the door is hot, check your alternate escape route. If the door is cool, open i t cautiously. Be prepared to slam the door if smoke or heat rushes in. 6. When smoke is present, crawl on the ground. Do not walk upright, since smoke rises and may overcome you. Clearer air is near the floor. 7. Escape quickly; dont panic. 8. Establish a common meeting place outdoors, away from your house, where everyone can meet and then take steps to contact the authorities and account for those missing. Choose someone to assure that nobody returns to the house — many die going back.
– 50 – Quick Guide to Basic System Functions FUNCTION PROCEDURE COMMENTS Check Zones Press READY key. View faulted zones when system not ready. Arm System Enter code. Press arming key desired: (AWAY, STAY, NIGHT-STAY, MAXIMUM, INSTANT) Arms system in mode selected. Quick Arm (if programmed) Press #. Press arming key desired: (AWAY, STAY, MAXIMUM, INSTANT) Arms system in mode selected, quickly and without use of a code. Bypass Zone(s) Enter code. Press BYPASS [6] key. Enter zone number(s) to be bypassed (use 2-digit entries). Bypassed zones are unprotected and will not cause an alarm if violated. Quick Bypass (if programmed) Enter code. Press BYPASS [6] key + [#]. Bypasses al l faulted zones automatically. Silence Sounders Burglary: Fire or CO: Check: Enter code. Press OFF [1] key. Press OFF [1] key. Press any key. Also disarms system. Memory of alarm remains until cleared. Memory of Alarm remains unt il cleared. Determine cause. Disarm System Enter code. Press OFF [1] key. (OFF need not be pressed if entry delay or an alarm is active) Also silences sounders. Memory of alarm remains until cleared. Clear Alarm Memory After disarming, enter code again. Press OFF [1] key again. Keypad beeps rapidly on entry if alarm has occurred while absent. Alarm display will remain upon disarming until cleared. Duress (if active and connected to Central Station) Arm or disarm normally, but use your 4- digit Duress code to do so. Performs desired action and sends silent alarm to Central Station. Panic Alarms (as programmed) Press key [A], [B], or [C] for at least 2 seconds, or key pairs 1 + ; + #, or 3 + # respectively. See the Panic Keys section for emergency functions programmed for your system. Note: Keys “A”, “B”, and “C” may have been programmed for other functions. Chime Mode To turn ON or OFF: Enter code. Press CHIME key. The keypad will sound if doors or windows are violated while system is disarmed and chime mode is ON. Test Mode To turn ON: Enter code. Press TEST key, then [0]. To turn OFF: Enter code. Press OFF key. Tests alarm sounder and allows sensors to be tested. Phone Access if applicable Consult Phone Access Users Guide that accompanies the Phone Module. Permits system access remotely, via Touch-tone phone.