Honeywell control panel VISTA15 Security System User Manual
Have a look at the manual Honeywell control panel VISTA15 Security System User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Security Codes (contd) - 31 - To Delete a User 1. + 8 (Master Code) Enter 4-digit Master code, then press the 8 key. Example: Press 2 0 5 9 then 8 2. (User Number) Enter user number. Enter the 2-digit user number (03-16) for the user whose code you are deleting. 3.-----------Stop. Wait (about 3 seconds) until the keypad beeps once before pressing any other key. The code is automatically deleted.
- 32 - Testing the System (To be conducted weekly) Using the 5 Key TEST The TEST key puts your system into a TEST mode, which allows each protection point to be checked for proper operation. The keypad sounds a single beep every 30 seconds as a reminder that the system is in this TEST mode. NOTE: An alarm message will not be sent to your alarm monitoring company during the following tests. 1.**** DISARMED**** READY TO ARMDisarm the system. Disarm the system and close all protected windows, doors, etc. The READY message should be displayed and the green READY indicator (if present on the keypad) should also be lit. 2. + 5 (Security Code)TEST Enter 4-digit security code, then press TEST key. Example: Press 7 2 9 6 then 5 3.Listen. The external sounder should sound for 2 seconds and then turn off. If the sounder does not sound, CALL FOR SERVICE IMMEDIATELY. 4.Fault zones. Open each protected door and window in turn and listen for three beeps from the keypad. Identification of each faulted protection point should appear on the display. The display will clear when the door or window is closed.
Testing the System (contd) - 33 - Walk in front of any interior motion detectors (if used) and listen for three beeps. The keypad should display the identification of the detector when the detector is activated. The display will clear when no motion is detected. Note that if you are using wireless motion detectors, there is a 3-minute delay between activations. This is to conserve battery life. To test all smoke detectors, follow the manufacturers instructions. The keypad should display the identification of each detector when each is activated. If you experience a problem with any protection point (no confirming sounds, no display), CALL FOR SERVICE IMMEDIATELY. When you have checked (and closed, where necessary) all protection points, no zone identification numbers should be displayed on the keypad. When you complete testing, exit the TEST mode by continuing with step 5. 5. + 1 (Security Code)OFF Exit TEST mode. Enter your security code and press the OFF key. If you inadvertently leave the test mode active, it automatically turns off after approximately 4 hours.
- 34 - Trouble Conditions Typical Check Displays The word CHECK on the keypads display, accompanied by a rapid beeping at the keypad, indicates a trouble condition in the system. The displays in parentheses in the left column below may appear on non-alpha keypads when the associated trouble condition is present. To silence the beeping sound for “check” conditions, press any key. CHECK + Zone Descriptors Indicates that a problem exists with those zone(s)*. First, determine why the zone(s) displayed are faulted (open window or door; open or shorted zone terminals; etc.) and correct the problem. If the zone(s) contain a wireless detector, check that changes in the room (moving furniture, televisions, etc.) are not blocking wireless signals to/from the detector. If the problem has been corrected, the zone descriptor(s) and CHECK should dis- appear from the keypad display. If not, key an OFF sequence (enter the 4-digit security code, then press the OFF key) to clear the display. A “Check” condition can also indicate a wiring problem (opens or shorts, for instance). If the CHECK display persists, CALL FOR SERVICE IMMEDIATELY. Note that the system will not allow arming if a “Check” condition exists. To arm the system with a “Check” condition present, you must first bypass the zone(s) having the “Check” condition. NOTE: Zone 9 represents a problem with wireless receivers or other system devices, which are not user-serviceable. CALL FOR SERVICE IMMEDIATELY.
Trouble Conditions (contd) - 35 - Telco Fault (or CHECK and zone 94)If the telephone line monitor feature has been programmed for your system, this display indicates that the telephone line has been disconnected or cut. In some systems, this display is accompanied by a trouble sound from the keypad and an external sounder. CONTACT YOUR SERVICE COMPANY IMMEDIATELY. To silence the trouble sound, enter your security code plus OFF. COMM. FAILURE (or FC) Indicates that a failure has occurred in the telephone communication portion of your system. CALL FOR SERVICE IMMEDI- ATELY. SYSTEM LO BAT (or BAT with no zone no.) Indicates that a low system battery condition exists, and is accompanied by a once-per- minute beeping* at the keypad. CALL FOR SERVICE IMMEDIATELY. * You can stop the beeping that accompanies a low- battery display by entering an OFF sequence (security code + OFF). LO BAT + zone descriptor (or BAT with zone no.)Indicates that a low-battery condition exists in the wireless transmitter** displayed, and is accompanied by a once-per-minute beeping at the keypad. CALL FOR SERVICE IMMEDIATELY. ** Not all systems use wireless transmitters. MODEM COMM (or CC)Indicates that the control is on-line with the central stations remote computer. The control will not operate while on-line. Wait a few minutes. The display should disappear.
Trouble Conditions (cont’d) - 36 - POWER indicator (if present) is off. AC LOSS is displayed.The system is operating on battery power only. If only some lights are out on the premises, check circuit breakers and fuses and reset or replace as necessary. CALL FOR SERVICE IMMEDIATELY if AC power cannot be restored to the system. Busy-Standby (or dI) If this remains displayed for more than 1 minute, system is disabled. CALL FOR SERVICE AT ONCE. OPEN CIRCUIT (or OC) The keypad is not receiving signals from the control. CALL FOR SERVICE AT ONCE. Long Rng Trbl (or bF) If programmed, backup Long Range Radio communication has failed. CALL FOR SERVICE AT ONCE. Bell failure (or CHECK 70) Bell/Siren supervision failure. CALL FOR SERVICE AT ONCE. RF Jam (or Check 90) If enabled and a Receiver Jam is detected, a report will be sent to the monitoring station and at the same time a Rcvr Jam message will toggle with the present display on the alpha keypad. When the jam condition is cleared, a Restore message is sent to the monitoring station. To clear the keypad display, enter your 4-digit code and 1 key. OFF
- 37 - Fire Alarm System (If Installed) General Information Your fire alarm system (if installed) is active 24 hours a day, providing continuous protection. In the event of an emergency, the installed smoke and heat detectors will automatically activate your security system, triggering a loud, interrupted sound from the keypad. Optional exterior sounders will also produce an interrupted sound. Your keypad will display a FIRE message (with zone location) until you silence and clear the alarm display. In Case of Fire 1. Should you become aware of a fire emergency before your detectors sense the problem, go to your nearest keypad and press the single panic key (or panic key pair) assigned as FIRE emergency (if programmed by the installer) and hold it down for at least 2 seconds. The alarm will sound. 2. Evacuate all occupants from the premises. 3. If flames and/or smoke are present, leave the premises and notify your local fire department immediately. 4. If no flames or smoke are apparent, investigate the cause of the alarm. The keypad will display the zone descriptor of the zone(s) in an alarm condition. Silencing a Fire Alarm 1. Silence the alarm by pressing the 1 key. OFF To clear the alarm display, enter your security code and press the 1 key again. OFF
Fire Alarm System (cont’d) - 38 - 2. If the keypad indicates a trouble condition after the second OFF sequence, check smoke detectors to see if they are responding to smoke or heat-producing objects in their vicinity. Should this be the case, eliminate the source of heat or smoke. 3. If this does not remedy the problem, there may still be smoke in the detector. Clear it by fanning the detector for about 30 seconds. 4. When the problem has been corrected, clear the display by entering your code and pressing the 1 key. OFF
- 39 - Recommendations for Proper Protection THE FOLLOWING RECOMMENDATIONS FOR THE LOCATION OF FIRE AND BURGLARY DETECTION DEVICES HELP PROVIDE PROPER COVERAGE FOR THE PROTECTED PREMISES. Recommendations for Smoke and Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Associations (NFPA) Standard #72, noted below. Early-warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: For minimum protection, a smoke detector should be installed outside of each separate sleeping area, and on each additional floor of a multi-floor family living unit, including basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not normally recommended. For additional protection, the NFPA recommends that you install heat or smoke detectors in the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements, and attached garages.
Recommendations for Proper Protection (cont’d) - 40 - DININGKITCHENBEDROOM BEDROOM BEDROOM BEDROOM LIVING ROOM J JJJ Js s BEDROOMBDRM BDRM DINING LIVING ROOM TV ROOMKITCHEN nnn J JJ JJ Js JJ J BEDROOM BEDROOM TO BR n n nn n LVNG RM BASEMENTKTCHN ss .CLOSED DOORGARAGE s Smoke Detectors for Minimum Protection Smoke Detectors for Additional Protection Heat-Activated Detectors In addition, we recommend the following: • Install a smoke detector inside every bedroom where a smoker sleeps. • Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the sleeper if the door is closed. • Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air conditioners, or humidifiers) are used. • Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long. • Install smoke detectors in any room where an alarm control is located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire or an intrusion.