Home > Honeywell > Control panel > Honeywell control panel VISTA128B User Manual

Honeywell control panel VISTA128B User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell control panel VISTA128B User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							 
    ±±
    Fire Alarm System 
    General 
    Your fire alarm system (if installed) is on 24 hours a day, providing 
    continuous protection.  In the event of an emergency, the smoke and heat 
    detectors automatically send signals to your Control, triggering a loud 
    interrupting sound from the keypad and the optional exterior sounders.  
    FIRE appears at your keypad and remains on until you silence the alarm. 
    In Case Of Fire Alarm 
    1.  Should you become aware of a fire emergency before your detectors sense 
    the problem, go to your nearest keypad and manually initiate an alarm 
    by pressing the panic key assigned as FIRE emergency (if programmed 
    by the installer) and hold down for at least 2 seconds. 
    2.  Evacuate all occupants from the premises. 
    3.  If flames and/or smoke are present, leave the premises and notify your 
    local Fire Department immediately. 
    4.  If no flames or smoke are apparent, investigate the cause of the alarm.  
    The descriptor of the zone(s) in alarm appears at the keypad. 
    Silencing A Fire Alarm 
    1.  Silence the alarm by entering your code and pressing the OFF key.  To 
    clear the display, enter your code and press the OFF key again. 
    2.  If the keypad does not indicate a READY condition after the second OFF 
    sequence, press the READY key to display the zone(s) that are faulted.  
    Be sure to check that smoke detectors are not responding to smoke or 
    heat producing objects in their vicinity.  Should this be the case, 
    eliminate the source of heat or smoke. 
    3.  If this does not remedy the problem, there may still be smoke in the 
    detector.  Clear it by fanning the detector for about 30 seconds. 
    4.  You can clear the display by entering your code + OFF key. 
    Fire Display Lock 
    If several zones produce an alarm before any are silenced, the system can be 
    programmed to lock the keypad display with the first zone that produced an 
    alarm. Ask your installer if your system has been activated with this feature. 
    To display the other zone(s), press the [
    ✴] key for each zone.  Also the “A”, 
    ‘’B’, or “C” keys can be programmed to scroll the keypad display to view the 
    previous or subsequent fire alarms.
      
    						
    							 
     
    – 52 –
     
    Trouble Conditions 
    Typical Trouble Displays 
    The word CHECK or TRBL on the Keypads display, accompanied by a rapid 
    beeping at the Keypad, indicates that there is a trouble condition in the 
    system.  
    To silence the beeping sound for trouble conditions, press any key. 
    x
    A display of “CHECK” or “TRBL” accompanied by a display of CALL 
    SERVICE indicates that a problem exists with the system that 
    eliminates some of the protection.  CALL FOR SERVICE 
    IMMEDIATELY.  
    x
    A display of “CHECK” or “TRBL accompanied by a display of one or 
    more zone descriptors indicates that a problem exists with those zone(s). 
    First, determine if the zones displayed are intact and make them so if 
    they are not. If the problem has been corrected, the display of the zone 
    descriptor(s) and “CHECK” or “TRBL” should disappear. If not, key an 
    OFF sequence (Code plus OFF) to clear the display. If the display 
    persists, CALL FOR SERVICE IMMEDIATELY. 
    x
    A display of “CHECK” or “TRBL” accompanied by a numeric display of 
    “6XX,” where XX = 01-32, indicates a trouble on a supervised relay 
    (corresponding relay number 01-32). 
    x
    A display of “CHECK” or “TRBL” accompanied by a numeric display of 
    “8XX,” where XX = 00-30, indicates a trouble on a peripheral device 
    (connected to the panel’s keypad terminals) of a corresponding device 
    address (00-30). 
    x
    A display of “CHECK” or “TRBL” accompanied by a numeric display of 
    “9XX,” where XX = 00-99, indicates a system trouble exists (dialers, bell 
    outputs, ground fault, etc.).  These zones are as follows: 
    988: 2nd RF Receiver – not receiving signals 
    990: 1st RF Receiver – not receiving signals 
    997: Polling Loop Short 
    x
    A display of COMM. FAILURE at the Keypad indicates that a failure 
    has occurred in the telephone communication portion of your system. 
    CALL FOR SERVICE IMMEDIATELY.   
    						
    							 
    ±±
    Trouble Conditions (cont’d) 
    x
    A display of SYSTEM LO BAT, accompanied by a once-per-minute 
    beeping at the Keypad indicates that a low system battery condition 
    exists. CALL FOR SERVICE IMMEDIATELY. 
    x
    A display of LO BAT and a zone descriptor, accompanied by a once-per-
    minute beeping at the Keypad indicates that a low battery condition 
    exists in the wireless transmitter displayed. CALL FOR SERVICE 
    IMMEDIATELY.  
    x
    A display of MODEM COMM indicates that the control is on-line with 
    the central stations remote computer. The control will not operate while 
    on-line. 
    Power Failure 
    If the POWER indicator is off, operating power for the system has stopped 
    and is inoperative. CALL FOR SERVICE IMMEDIATELY. If the POWER 
    indicator is on, but the message AC LOSS is displayed, the Keypad is 
    operating on battery power only. If only some lights are out on the premises, 
    check circuit breakers and fuses and reset or replace as necessary. CALL 
    FOR SERVICE IMMEDIATELY if AC power cannot be restored. 
     
    SERVICING INFORMATION 
    Your local ADEMCO dealer is the person best qualified to service your alarm 
    system. Arranging some kind of regular service program with him is 
    advisable. 
     
    Your local ADEMCO dealer is: 
    Name:  
    Address:  
      
    Phone: 
     
     
      
    						
    							 
     
    – 54 –
     
    Recommendations For Proper Protection 
    THE FOLLOWING RECOMMENDATIONS FOR THE LOCATION OF FIRE AND 
    BURGLARY DETECTION DEVICES HELP PROVIDE PROPER COVERAGE FOR 
    THE PROTECTED PREMISES. 
     
    Recommendations For Smoke And Heat Detectors 
    With regard to the number and placement of smoke/heat detectors, we subscribe to the 
    recommendations contained in the National Fire Protection Associations (NFPA) Standard 
    #72 noted below. 
    Early warning fire detection is best achieved by the installation of fire detection 
    equipment in all rooms and areas of the household as follows: For minimum protection 
    a smoke detector should be installed outside of each separate sleeping area, and on each 
    additional floor of a multi-floor family living unit, including basements. The installation 
    of smoke detectors
     in kitchens, attics (finished or unfinished), or in garages is not 
    normally recommended.  
    For additional protection the NFPA recommends that you install heat
     or smoke detectors in 
    the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and 
    storage rooms, basements and attached garages. 
      
    						
    							 
    ±±
    Recommendations For Proper Protection (cont’d) 
     
    DININGKITCHENBEDROOM
    BEDROOM
    BEDROOM
    BEDROOM
    LIVING ROOMBEDROOMBDRM
    BDRM DINING 
    LIVING ROOM TV ROOMKITCHEN
    BEDROOM
    BEDROOM TO
    BR
    LVNG RM
    BASEMENTKTCHN.CLOSED
    DOORGARAGE
    Smoke Detectors for Minimum Protection
    Smoke Detectors for Additional Protection
    Heat-Activated Detectors
    floor_plan-001-V0 
     
    In addition, we recommend the following: 
    ƒInstall a smoke detector inside every bedroom where a smoker sleeps. 
    ƒInstall a smoke detector inside bedrooms where electrical appliances (such as portable 
    heaters, air conditioners or humidifiers) are used. 
    ƒInstall a smoke detector inside every bedroom where someone sleeps with the door partly 
    or completely closed. Smoke could be blocked by the closed door. Also, an alarm in the 
    hallway outside may not wake up the sleeper if the door is closed. 
    ƒInstall a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 
    meters) long. 
    ƒInstall smoke detectors in any room where an alarm control is located, or in any room 
    where alarm control connections to an AC source or phone lines are made. If detectors are 
    not so located, a fire within the room could prevent the control from reporting a fire or an 
    intrusion.  
    						
    							 
     
    – 56 – 
    Recommendations For Proper Protection (cont’d) 
    Recommendations For Proper Intrusion Protection 
    For proper intrusion coverage, sensors should be located at every possible point of entry to a 
    home or commercial premises. This would include any skylights that may be present, and 
    the upper windows in a multi-level building. 
    In addition, we recommend that radio backup be used in a security system so that alarm 
    signals can still be sent to the alarm monitoring station in the event that the telephone lines 
    are out of order (alarm signals are normally sent over the phone lines, if connected to an 
    alarm monitoring station).  
    						
    							 
    ±±
    Emergency Evacuation 
    Establish and regularly practice a plan of escape in the event of fire. The following steps are 
    recommended by the National Fire Protection Association: 
     
    1.  Position your detector or your interior and/or exterior sounders so that 
    they can be heard by all occupants. 
    2.  Determine two means of escape from each room. One path of escape 
    should lead to the door that permits normal exit from the building. The 
    other may be a window, should your path be impassable. Station an 
    escape ladder at such windows if there is a long drop to the ground. 
    3.  Sketch a floor plan of the building. Show windows, doors, stairs and 
    rooftops that can be used to escape. Indicate escape routes for each room. 
    Keep these routes free from obstruction and post copies of the escape 
    routes in every room. 
    4.  Assure that all bedroom doors are shut while you are asleep. This will 
    prevent deadly smoke from entering while you escape. 
    5.  Try the door. If the door is hot, check your alternate escape route. If the 
    door is cool, open it cautiously. Be prepared to slam the door if smoke or 
    heat rushes in. 
    6.  Where smoke is present, crawl on the ground; do not walk upright. 
    Smoke rises and may overcome you. Clearer air is near the floor. 
    7.  Escape quickly; dont panic. 
    8.  Establish a common meeting place outdoors, away from your house, 
    where everyone can meet and then take steps to contact the authorities 
    and account for those missing. Choose someone to assure that nobody 
    returns to the house — many die going back. 
     
     
     
     
     
     
     
     
     
      
    						
    							 
     
    – 58 –
     
    Maintaining Your System 
    Taking Care of Your System 
    The components of your security system are designed to be as free of 
    maintenance as possible. However, there are some things you can do to make 
    sure that your system is in reliable working condition. 
    1.  Test your system weekly. 
    2.  Test the system after any alarm occurs (see TESTING THE SYSTEM). 
    Replacing Batteries in Wireless Sensors 
    Wireless sensors may not have been used in your security system
    Each wireless sensor in your system has a 9-volt or 3-volt battery. The system 
    detects a low battery in any wireless sensor, including smoke detectors, the 
    optional personal emergency transmitter, and the optional portable wireless 
    keypad. (A low battery in a portable wireless keypad is detected as soon as 
    one of its keys is pressed, and the keypad will display 00.) 
    Alkaline batteries provide a minimum of 1 year of operation, and in most 
    units and applications, provide 2–4 years of service. Actual battery life will 
    depend on the environment in which the sensor is used, the number of signals 
    that the transmitter in the sensor has had to send, and the specific type of 
    sensor.  Factors such as humidity, high or low temperatures or large swings 
    in temperature, may all lead to the reduction of actual battery life in an 
    installation.
      
    If you have a low battery in a wireless sensor, a low battery message 
    is displayed on the keypad.  
    In addition, a battery-operated smoke detector with a low battery also emits 
    a single chirp sound once approximately every 20-30 seconds, identifying 
    itself as the smoke detector with the weak battery.  If you do not replace a 
    smoke detectors low battery, the smoke detector may sound continuously, as 
    if there were a fire alarm. 
    Note: The low battery message comes on as a warning that battery 
    replacement in indicated sensor(s) is due within 30 days. In the meantime, 
    the sensor(s) causing the low battery indication is still fully operational. 
    Important:  Use only batteries recommended by your installer as 
    replacement. 
      
    						
    							 
    ±±
    Maintaining Your System (cont’d) 
    Silencing Low Battery Warning Tones at the Keypad 
    The keypad’s warning tones can be silenced by performing an OFF sequence 
    (code plus OFF key), but the Keypads low battery message display will 
    remain on as a reminder that you have a low battery condition in one or more 
    of your sensors. When you replace the weak battery with a fresh one, the 
    sensor will send a good battery signal to the control as soon as the sensor is 
    activated (opening/closing of door, window, etc.), causing the low battery 
    display to turn off. If the sensor is not activated, the display will 
    automatically clear within approximately 1 hour. 
    Routine Care 
    x
    Treat the components of your security system as you would any other 
    electrical equipment. Do not slam sensor-protected doors or windows. 
    x
    Keep dust from accumulating on the keypad and all protective sensors, 
    particularly on motion sensors and smoke detectors. 
    x
    The keypad and sensors should be cleaned carefully with a dry soft cloth. 
    Do not spray water or any other fluid on the units. 
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
      
    						
    							 
     
    – 60 –
     
    Quick Guide To System Functions 
    FUNCTION 
    PROCEDURE 
    COMMENTS 
    Check Zones 
    Press [
    ✱]. To view faulted zones when is system not ready 
    Display All 
    Descriptors Press and hold [
    ✱] for 5 seconds. Displays all alpha descriptors programmed by 
    installer. 
    Arm System  Enter code. 
    Press arming key desired (AWAY, 
    STAY, INSTANT, MAXIMUM). Arms system in mode selected. 
     
    Disarm System  Enter code.   
    Press OFF [1]. Disarms system and silences alarms. 
    Bypass Zones  Enter code.  Press BYPASS [6]. 
    Enter zone numbers to be 
    bypassed (use 3-digit entries). Bypassed zones are unprotected and will not 
    cause an alarm if violated. 
    Quick Bypass  Enter code.   
    Press BYPASS [6]. 
    Press [#]. Bypasses all faulted zones automatically. 
    Chime Mode  Enter code.   
    Press CHIME [9]. Keypad will sound if doors or windows are 
    violated while system disarmed. 
    Test Mode  Enter code.   
    Press TEST [5] Activates alarm sounder and allows sensors to 
    be tested. 
    View Messages  Press and hold [0] for at least 5 
    seconds. Message from central station will appear. 
    View User 
    Capabilities Enter users code.   
    Press [
    ✱] + [
    ✱]. Displays partitions & authority levels assigned 
    to the user. 
    GOTO Partition  Enter security code.   
    Press [
    ✱]. 
    Enter partition number (1-8). 
    0 returns to default partition. Allows a user at one keypad to perform 
    functions in another partition, if that user is 
    authorized to do so. 
    Add a User  Enter master/manager code. 
    Press CODE [8]. 
    Enter new users user number. 
    Enter code for that user. 
    Enter authority for that user in this 
    partition (1-5). 
    Follow prompts, 1=Yes, 0=No. Master & Manager level users can add users to 
    the system, each with its own code and 
    authority level. 
    Change a Users 
    Code Enter master/manager code. 
    Press CODE [8]. 
    Enter users 3-digit number. 
    Enter new code for that user. 
    Press 0 (No) at prompt. Master & Manager level users can change their 
    own or other users codes. 
     
     
      
    						
    All Honeywell manuals Comments (6)

    Related Manuals for Honeywell control panel VISTA128B User Manual