Home > Honeywell > Control panel > Honeywell control panel VISTA Turbo Fire Series User Manual

Honeywell control panel VISTA Turbo Fire Series User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell control panel VISTA Turbo Fire Series User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Ê800-11045QG-2VŠ 800-11045QG-2  9/12  Rev A     Part 1
     
      
     TESTING THE SYSTEM The TEST key puts your system in Burglary Walk Test mode, which 
    allows each burglary protection point to be checked  for proper 
    operation.  Testing should be conducted weekly to ensure 
    proper operation .   The keypad sounds a single beep about every 30 sec onds as a 
    reminder that the system is in the Test mode.   Alarm messages are not sent to your Central Statio n while Test 
    mode is on. 
    If a problem is experienced with any detection poin t (no confirming 
    sounds, no display), call for service immediately.  1.   Disarm the system and close all protected windows,  doors, etc. 
    The READY indicator light should come on if all zon es are intact   2.  Enter your 4-digit Master code +   5    3.  Listen. The external sounder should sound for ab out 1 second 
    then turn off. If the sounder does not sound, CALL  FOR SERVICE.  
    The Burg Walk Test Reduced RF Sens. display appea rs only on 
    the keypad that started the test.  
    4.  Fault zones. Open each protected door and window  in turn and 
    listen for three beeps from the keypad. Each faulte d detection 
    point should appear on the display. The display cle ars when the 
    door or window is closed. 
    5.  Walk in front of any interior motion detectors ( if used) and listen 
    for three beeps. Each detector should appear on the  display when 
    it is activated. The display clears when no motion  is detected. 
    Note 
    that if wireless motion detectors are used, there is a 3-minute 
    delay between activations to conserve battery life.   
    6.  When all detection points have been checked and  are intact 
    (closed), there should be no zone numbers displayed . 
    7.  Exit test mode: 4-digit code +    1   
    TROUBLE CONDITIONS The word CHECK or TRBL on the keypads display, acc ompanied by a 
    rapid beeping at the keypad, indicates a trouble  condition in the 
    system.    
    To silence the beeping for these conditions, press  a valid code 
    +    1 .  Typical Trouble conditions include the following:  “Open Circuit Call for Service indicates a problem  exists with your keypad 
    connection to the Control panel. CALL FOR SERVICE I MMEDIATELY.  
     “CHECK”   or “TRBL   display  accompanied  by  a  display  of  one  or  more  z one 
    descriptors indicate that a problem exists with tho se zone(s). First, determine if 
    the  zone(s)  displayed  are  intact  (this  may  include  Fire  and  Waterflow  type 
    zones)  and  make  them  so  if  they  are  not.  If  the  pro blem  has  been  corrected, 
    key  an  OFF  sequence  (Code  plus  OFF)  to  clear  the  di splay.  If  the  display 
    persists, CALL FOR SERVICE IMMEDIATELY.  
    “CHECK”  or “TRBL”   display  accompanied  by  a  display  of  “6XX,”  where  X X  = 
    01-32,  indicates  a  trouble  on  a  supervised  relay  (c orresponding  relay  number 
    01-32).  
    “CHECK”  or “TRBL”   display  accompanied  by  a  display  of  “8XX,”  where  X X  = 
    00-30,  indicates  a  trouble  on  a  peripheral  device  ( connected  to  the  panel’s 
    keypad terminals). 
    “CHECK”  or “TRBL”   display  accompanied  by  a  display  of  “9XX,”  where  X X  = 
    00-99,  indicates  a  system  trouble  exists  (dialers,  Notification  Appliance 
    Circuits, ground fault, etc.).  These zones are as  follows: 
    970: Bell 1 Output    975: Dialer 2  
    971: Bell 2 Output  988: 2
    nd RF Receiver – not receiving signals 
    972: Earth Ground Fault  990: 1st RF Receiver – not receiving signals 
    973: J2 Trigger Output  997: Polling Loop Short 
    974: Dialer 1   
    “ SUPV”   display  accompanied  by  a  display  of  one  or  more  zo ne  descriptors 
    indicates  a  problem  on  fire supervisory  zone(s).  Th is means that  the  operation 
    of  the  fire  alarm  system  may  be  compromised.  First,   determine  if  the  zone(s) 
    displayed are intact and make them so if they are n ot. If the problem has been 
    corrected,  key  an  OFF  sequence  (Code  plus  OFF)  to  c lear  the “SUPV” 
    display. If the display persists, CALL FOR SERVICE  IMMEDIATELY. 
     
    A  display  of  COMM.  FAILURE   at  the  Keypad  indicates  that  a  failure  has 
    occurred  in  the  telephone  communication  portion  of  your  system.  CALL  FOR 
    SERVICE IMMEDIATELY.   
    A  display  of   SYSTEM LO  BAT ,  accompanied  by  a  rapid  beeping  at  the 
    Keypad  indicates  that  a  low  system  battery  conditio n  exists.  CALL  FOR 
    SERVICE IMMEDIATELY.  
    A  display  of   LO  BAT  and  a  zone  descriptor,  accompanied  by  a  once  per 
    minute  beeping  at  the  Keypad  indicates  that  a  low   battery  condition  exists  in 
    the wireless transmitter displayed. CALL FOR SERVIC E IMMEDIATELY.  
    A  display  of   MODEM  COMM   indicates  that  the  control  is  on-line  with  the 
    central stations remote computer. The control will  not operate while on-line. 
    A  display  of  “HSENS”  and  a  zone  number  indicates  a  smoke  detector  with  a 
    high  sensitivity  level,  which  may  cause  false  alarm s.  CALL  FOR  SERVICE 
    IMMEDIATELY.  
    A  display  of  “LSENS”  and  a  zone  number  indicates  a  smoke  detector  with  a 
    low  sensitivity  level.  Detectors  with  a  low  sensiti vity  might  not  detect  a  smoke 
    condition. CALL FOR SERVICE IMMEDIATELY.  
    Power Failure  
    If  the  message   AC  LOSS  is  displayed,  the  Keypad  is  operating  on  battery 
    power  only.  If  only  some  lights  are  out  on  the  prem ises, check  circuit  breakers 
    and  fuses  and  reset  or  replace  as  necessary.  CALL  F OR  SERVICE 
    IMMEDIATELY if AC power cannot be restored.
     
    SETTING THE DATE AND TIME NOTE: All partitions must be disarmed before date/t ime can be set. 
    You can set the time and date by doing the followin g: 
     
    1.    
        
        
        
     +[#] + [6] [3] 
     
    (Master Code) 
     2.  Press [
    ] when the time/date is displayed.  
      A cursor appears under the first digit of the hour . 
      To move cursor to the right, press [
    ]. To move the cursor to the 
    left, press [#]. 
     
     Enter the correct hour setting, then press [
    ]. 
     
     Enter the correct minute setting, then press [
    ]. 
     
     Press any key [0] – [9] to change AM to PM, or PM  to AM, then 
    press [
    ]. 
     
     Enter the correct month using a 2-digit setting, t hen press [
    ]. 
     
     Enter the correct day using a 2-digit setting, the n press [
    ]. 
     
     Enter the current year, then press [
    ]. 
      
    3.  Press [
    ] to exit the Real Time Clock Edit Mode. 
     SERVICING INFORMATION  Your  local  Honeywell  dealer  is  the  person  best  qual ified  to  service 
    your  alarm  system.  Arranging  some  kind  of  regular  s ervice 
    program with him is advisable. Your local Honeywell  dealer is:  Name:   
     
    Address:    
        
    Phone: 
     
     
           
    2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747Copyright © 2012 Honeywell International Inc. www.honeywell.com/security
     
     
     
    VISTA TURBO FIRE SERIES 
    Vista-32FBPT/Vista-128FBPT/Vista-250FBPT 
     
    Quick Guide
    Quick Guide Quick Guide
    Quick Guide to User Functions
     to User Functions to User Functions
     to User Functions 
      
     
     Full User Guide Available Online:
     This Quick Guide describes the most frequently use d features and functions of your system. For full details of all user functions, please see the system’s User Guide located online at:
     
    http://www.security.honeywell.com/hsc/products . The full version User Guide is also available from your installer upon request.  Congratulations on your ownership of a Honeywell Secur ity System. This system provides:  
       Three forms of detection: burglary, fire and emergen cy (see your installer for which forms of detection are i nstalled) 
       At least one keypad which provides control of system and  displays system status 
       Various sensors for perimeter and interior burglary de tection 
       Smoke and/or combustion detectors designed to provide  early warning in case of fire. 
    Your system may also be programmed to automatically send  alarm and status messages to a Central Monitoring Station. 
     
     
    SYSTEM BASICS
     
    The following is a list of some of the most common  features and 
    functions of your system:   Several modes of burglary detection: Away, Stay, I nstant, 
    Maximum.   Bypass feature lets authorized persons to bypass s elected zones 
    while leaving the rest of the system armed.    Chime mode alerts you to the opening of protected  doors and 
    windows while the system is disarmed, if enabled.   Fire and carbon monoxide detection are always acti ve (if 
    installed) and an alarm sounds if a fire or carbon  monoxide 
    condition is detected.   Panic keys (if programmed) let you manually initia te a fire and 
    personal alarms using the keypad.    4-digit security codes are used in conjunction wit h keypad 
    command to perform system functions.    Each user can be assigned a different security cod e, each with 
    different authority levels.   The system sensing devices have been assigned to v arious 
    “zones,” which are specific areas of detection (e.g ., front door, 
    storage room window, etc.).   Zone numbers (points of detection) are displayed a t the keypad 
    when an alarm or trouble condition occurs.   Partitions provide two independent areas of detect ion with each 
    partition containing a group of zones that can be a rmed and 
    disarmed without affecting other zones.   Function keys may have been programmed to perform  various 
    functions. Ask your installer if these keys are act ive.   A Scheduling feature can be programmed to automati cally 
    perform certain functions (e.g., arm the system) at  a 
    predetermined time each day. See the full User Guid e for details.  ENTRY/EXIT DELAYS  Entry Delays  give you time to disarm the system when you 
    enter through the designated entrance door.    You must disarm the system before the entry delay  period ends, 
    or an alarm will occur (keypad beeps during the ent ry delay 
    period, reminding you to disarm the system).    Exit delay  gives you time after arming the system to leave 
    through the designated exit door(s) without setting  off an alarm. 
    If programmed, a slow beeping will sound during the  exit delay 
    period until the last 10 seconds, which then change s to fast 
    beeping (alerting you to the end of exit delay). If  you cannot 
    leave within this delay time period, you should sto p, disarm the 
    system, and start over to avoid a false alarm.  
    
     
    See your installer for your delay times. See the fu ll User Guide 
    for details on Exit Error alarms. 
    NOTES on BURGLARY DETECTION    The system must be armed before the burglary detec tion can 
    sense intrusions.   To arm your system, enter your security code follo wed by the 
    desired arming key.   To disarm the system, enter your security code the n press the 
    OFF key.   When an alarm occurs, the keypad sounds and displa ys the 
    zone(s) causing the alarm. The external sounder may  also 
    sound.   If your system is connected to a Central Monitorin g Station, an 
    alarm message is also sent (may be delayed 30 secon ds to 
    reduce false alarms).   To stop the alarm sounding, simply disarm the syst em.  Memory of Alarm:  When an alarm condition occurs, the 
    keypad displays the number(s) of the zone(s) that c aused the 
    problem, and displays the type of alarm. Clear the  Memory of 
    Alarm display by entering another “off” sequence. 
     
    IMPORTANT:  If you return to the premises and the main burglary sounder is on, or the keypad beeps rapidly upon entering the premises, it indicates that an alarm has occurred during your absence and an intruder may still be on the premises. LEAVE IMMEDIATELY and CONTACT THE POLICE from a nearby safe location.   NOTES on FIRE and CO DETECTION    Your fire alarm system (if installed) is on 24 hou rs a day, for 
    continuous detection. In the event of an emergency,  the 
    smoke and heat detectors sound their alarms, trigge ring a 
    loud, interrupted pulsed sound from the Keypad(s) a nd any 
    external sounders.    You can silence the alarm at any time by pressing  a valid code 
    + OFF.   Carbon monoxide (CO) detectors, if installed, prov ide 
    continuous detection. If a high level of carbon mon oxide is 
    detected, an interrupted pulsed alarm sound occurs  at the 
    keypads and the detector(s). Immediately move to a  spot 
    where fresh air is available, preferably outdoors.  From a safe 
    area, call your security service provider for furth er 
    instructions. To silence the keypad sounding, press  a valid 
    code + OFF. To silence the detector, see its instru ctions.  
     
     
      
    						
    							 
     
     4-digit code +     #    Enter 71 or 72.  Activate output device as programmed. 4-digit code +     
    #    Enter 70.  Activate output device manually 
    CONTROL  
    OUTPUT  
    DEVICE
     
    4-digit code +      #    
    Enter 77.  Activate output device or system event instantly 4-digit code +     
    #    Enter 41  Randomize output devices set for random  
    schedules 4-digit code +     
    #    Enter 42.  Randomize output devices set for random  
    schedules with activation times between 6 PM and 
    5 AM 
    RANDOMIZE  
    OUTPUT 
    DEVICE
     
    Enter the sequence  
    used to activate 
    randomization.  De-activate randomization 
     DISARMING THE SYSTEM and SILENCING ALARMS  The   
    1   OFF key is used to disarm the system, silence ala rm and trouble sounds, and clear memory of alarm displays.
     
     Mode  Press these keys…  What happens DISARM  
    and  
    SILENCE  
    ALARMS 4-digit code +   
    1    
      System is disarmed and alarm sounding is silenced.    To clear the memory of alarm display (if present), 
    enter your 4-digit code +    1   again.    
     BYPASSING ZONES  Use the    6   BYPASS key when you want to arm your system with  one or more zones intentionally unprotected.  
    Mode  Press these keys…
     What happens 
    BYPASS  
    ZONES  4-digit code +   
    6   + 
    3-digit zone numbers  
    to be bypassed   
      When finished, the keypad will momentarily display  a 
    Bypass message for each bypassed zone number.  
    Wait for all bypassed zones to be displayed.   Arm the system as usual. When armed, the arming  message is displayed with “ZONE BYPASSED.”   Bypassed zones are unprotected and will not cause an alarm if violated.   The system may not allow fire zones to be bypassed .   Zones may be automatically unbypassed when the 
    system is disarmed. 
     PANIC KEYS Your system may have been programmed to use special  keys or key pairs to manually 
    activate emergency (panic) functions as follows: 
    This Function  Key(s)*  Sends This Signal**  With This Sounding…  Silent Alarm    silent alarm  no change to the keypad.  Audible Alarm    audible alarm  a loud, steady alarm at keypad(s) and 
    at any external sounders that may be  
    connected. Personal Alarm    auxiliary alarm  steady alarm sound  at keypad(s), but 
    not at external bells or sirens. Fire Alarm    fire alarm  temporal (pulsing) sound at  external 
    bells and sirens. * Enter the appropriate keys programmed by your ins taller for each function (see installer). 
    ** All panic functions send signals to the Central  Monitoring Station, if connected. 
    To activate a Panic Function:  
    Press and hold down for at least 2 seconds 
    the programmed lettered key or key pair 
    for the desired emergency function (or 
    press both keys of the assigned key pair at 
     Keys  Pairs  Displayed as Zone [A]   
    (
    
    
    /1)   995 [B] 
     
    (
    
    
    /#)   999 [C]  
    (3/#)  996 
     
    CHECKING OPEN ZONES Checking Zones: Before arming your system, all prot
    ected doors, windows and other 
    detection zones must be closed or bypassed; otherwi se the keypad displays Not Ready.  GOTO: If the user is authorized, a keypad in one partition can be used to perform system 
    functions in the other partition by using the GOTO  command. 
     
    Mode  Press these keys…  What happens CHECK  
    ZONES 
     
    
    
        
      Displays all faulted zones. 
    GOTO  4-digit code + 
    
    
       + partition no.:
     
    1 or 2 (Vista-32FBPT);  
    1 through 8 (Vista-128FBPT/Vista-
    250FBPT) = go to partition;  
    0 = return to home part  
      The keypad beeps to confirm the partition 
    change.   Keypads automatically return to their original partition after 2 minutes with no  
    keypad activity.  
    ARMING THE SYSTEM, CHIME MODE, and CONTROLLING DEVI CES Before arming, close all perimeter doors and windows and make sure the Ready to Arm 
    message is shown.  
    After arming, leave the premises through an entry/e xit door during the exit delay period and 
    be sure the door is reclosed to avoid causing an al arm. 
    Mode  Press these keys…   When to use an arming mode and what happens STAY 4-digit code +   3 
      +   1 
     for STAY 
    Mode 1.    
    4-digit code +    3 
      
    +   2 
     for STAY 
    Mode 2.    
    4-digit code +    3 
     
    +   3 
     for STAY 
    Mode 3. 
    Three beeps confirm. 
      Used  when  staying  on  premises,  but  someone 
    might use the entrance door later. 
       Arms the perimeter.   An alarm sounds if a protected window or any door  
    is opened.  
    When armed in STAY mode, the system will sound an  
    alarm  if  a  protected  door  or  window  is  opened,  but 
    you  may  otherwise  move  freely  throughout  the 
    premises.  Arrivals  can  enter  through  the  entrance 
    door  without  causing  an  alarm,  but  must  disarm  the 
    system  within  the  entry  delay  period  or  an  alarm  wi ll 
    occur.   
    The  system  provides  three  STAY  modes.  STAY  mode  
    1,  2,  and  3.  When  activated,  STAY  modes  1  and  2  
    automatically  bypass  specific  zones  assigned  by  you r 
    installer  to  each  of  the  STAY  modes.  STAY  mode  3, 
    when  activated,  automatically  bypasses  all  zones 
    assigned  to  STAY  modes  1  AND  2.  Check  with  your 
    installer  for  a  list  of  the  zones  that  are  bypassed  
    during each STAY mode.  
    NOTE:  If  none  of  the  zones  in  a  partition  are 
    assigned  to  Stay  mode  2,  then  when  the  user  enters  
    [User  Code]  + [3]   (STAY),  all  zones  assigned  to 
    Stay mode 1 are automatically bypassed.  
    The keypad beeps three times, displays the armed  
    message, and indicates which STAY mode (1, 2 or 3).  
    AWAY 4-digit code +    
    2   
      
    two beeps confirm 
      Used when nobody is staying inside.   Arms the entire system (interior and perimeter).   An alarm sounds if a protected window or any door 
    is opened, or if any movement is detected inside. 
    MAXIMUM
     4-digit code +     4       
    two beeps confirm 
      Used when leaving the premises for extended 
    periods (e.g., vacation).   Same as Away mode, except entry delay is off.   An alarm sounds same as Away mode, and sounds upon opening entry/exit doors. 
    QUICK  
    ARMING     
    #    + arming key 
      If programmed, you can press the [#] key in place 
    of your security code when arming the system  
    CHIME  
    MODE  4-digit code +    
    9     
      
    (enter again to turn 
    Chime mode off)
     
      Alerts you to the opening of a perimeter door or 
    window while the system is disarmed.    Three tones sound at the keypad whenever a perimeter door or window is opened (interior zones 
    do not produce a tone when they are faulted).    Pressing the READY key displays the open zones. 
          
     
      
     
    1 OFF
    4 MAX
    7INSTANTREADY
    2 AWAY
    5 TEST
    8 CODE
    0 3
    STAY
    6
    BYPASS9 CHIME#
    SILENCED
    TROUBLEALARMSUPV
    POWER
    6160CR2-001-V1
    ARMED
    READY
    (B)
    A
    DS
    ENTER
    SHIFT N / Y
    BS/ESC
    SPACE
    BE
    T C
    FX
    SHIFT
    FUNCTION
     WHEN LIT
    /
    (C)(D)(A)
     
        When entering codes and commands, sequential key de pressions must be made within 4-5 
    seconds of one another. If 4-5 seconds elapse witho ut a key depression, the entry will be 
    aborted and must be repeated from its beginning. 
      If you make a mistake while entering a security c ode, stop, press the   
    
    
       key, and then 
    start over.
     If you stop in the middle while entering a code, an d then immediately start the 
    entry over, an erroneous code might be entered. 
     SECURITY CODES Your installer assigned a master code that is used  to perform all system functions. 
    In addition, other security codes can be assigned f or use by other users.   Only the Master and Manager Codes can assign secur ity codes to users.   Users are identified by a 2-digit user number (Vista-32FBPT) or 3-digit user number 
    (Vista-128FBPT/Vista-250FBPT).      In addition to a security code, each user is assig ned an authority level and various system 
    attributes. See the full User Guide for definitions  of each Authority Level.   Security codes can be used interchangeably within  a partition when performing system 
    functions (a system armed with one security code ca n be disarmed by a different security 
    code), with the exception of the Guest codes.   Security code programming involves these steps:  
      1. Choose a user number from the set of users assi gned to the partition in which the user 
    will be operating, and assign a 4-digit security co de. 
      2. Assign an authority level to that user.  
      3. Assign other attributes as necessary. 
    Assigning Security Codes and User Attributes  
    The following lists the various command strings for  adding security codes and attributes.   Function  Commands Add Security Code 
     Master or Manager code +  8    + [user no.] + new user’s security code Follow the screen prompts to add the authority leve l and other attributes for 
    this user. The Keypad beeps once to confirm that ne w user was added.  
    Delete Security  
    Code 
     Master or Manager code +  8    + [user no.] + Master or Manager code first entered.   
    When prompted, press 1 (YES). 
    The security code set for this user number is erase d from the 
    system.  
    Change a User  
    Security Code 
     Master code +   8   + [user no.]. Enter the new code for that user. When prompted, press 0 (NO). The security code set for this user number is chang ed to the new 
    code. 
       
      
    						
    All Honeywell manuals Comments (0)

    Related Manuals for Honeywell control panel VISTA Turbo Fire Series User Manual