Honeywell control panel LYNX Touch User Manual
Have a look at the manual Honeywell control panel LYNX Touch User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
– 61 – FIRE FIREFIRE FIRE/CO /CO/CO /CO ALARM SYSTEM ALARM SYSTEM ALARM SYSTEM ALARM SYSTEM National Fire Protection Association’s Smoke Detector Recommendations UL ULUL UL LYNX Touch is not intended for UL985 Household Fire applications unless a 24-hour backup battery (P/N LYNXRCHKIT-SHA) is installed. With regard to the number and placement of smoke and heat detectors, we subscribe to the recommendations contained in the National Fire Protection Associations (NFPA) Standard #72 noted below. Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household. The equipment should be installed as follows: A smoke detector installed outside of each separate sleeping area, in the immediate vicinity of the bedrooms and on each additional story of the family living unit, including basements and excluding crawl spaces and unfinished attics. In addition, the NFPA recommends that you install heat or smoke detectors in the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages. DINING KITCHENBEDROOM BEDROOM BEDROOM BEDROOM LIVING ROOMBEDROOM BDRM DINING LIVING ROOM TV ROOM KITCHEN BEDROOM BEDROOM TO BR LVNG RM BASEMENT KTCHN.CLOSED DOOR GARAGE Smoke Detectors for Minimum Protection Smoke Detectors for Additional Protection Heat-Activated Detectors BDRM floor_plan-001-V1
– 62 – FIRE FIREFIRE FIRE/CO /CO/CO /CO ALARM SYSTEM ALARM SYSTEM ALARM SYSTEM ALARM SYSTEM Emergency Evacuation UL ULUL UL LYNX Touch is not intended for UL985 Household Fire applications unless a 24-hour backup battery (P/N LYNXRCHKIT-SHA) is installed. Establish and regularly practice a plan of escape in the event of fire. The following steps are recommended by the National Fire Protection Association: 1. Position your detector or your interior and/or exterior sounders so that they can be heard by all occupants. 2. Determine two means of escape from each room. One path of escape should lead to the door that permits normal exit from the building. The other should be an alternative escape, such as a window, should your path to that door be unpassable. Station an escape ladder at such windows if there is a long drop to the ground. 3. Sketch a floor plan of the building. Show windows, doors, stairs and rooftops that can be used to escape. Indicate escape routes for each room. Keep these routes free from obstruction and post copies of the escape routes in every room. 4. Assure that all bedroom doors are shut while you are asleep. This will prevent deadly smoke from entering while you escape. 5. Try the door. If the door is hot, check your alternate escape route. If the door is cool, open it cautiously. Be prepared to slam the door if smoke or heat rushes in. 6. When smoke is present, crawl on the ground. Do not walk upright, since smoke rises and may overcome you. Clearer air is near the floor. 7. Escape quickly; dont panic. 8. Establish a place outdoors, away from your house, where everyone can meet and then take steps to contact the authorities and account for those missing. Choose someone to assure that nobody returns to the house — many die going back. FRONT BACK BATH BEDROOMKITCHEN BACK DOOR 1 FLOORST BEDROOM 2 FLOORND BATHBEDROOMPORCH CLOSET BEDROOM BEDR emerevac
– 63 – SYSTEM FUNCTIONS Testing the System (to be conducted weekly) Test Mode The Test mode allows each protection point to be checked for proper operation. When the Walk Test mode is active, the control sounds a single beep every 30 seconds as a reminder that the system is in the Test mode. NOTE: An alarm message will not be sent to your alarm monitoring company during these tests. Entering Test Mode Disarm the system and close all protected windows, doors, etc. The “READY ” indicator should be lit. Testing the System Arm Away Ready To Arm Arm Stay Back DelaySettings 10:18 AM June 8, 20105000-100-007-V0 Tools 1. With the system in the disarmed state, select the “ Tools” icon from the second page of the Home Screen. The system displays the Keypad screen. Ready To Arm Program the system Enter Code: Cancel 5000-100-009-V0 23 1 5 6 4 0 8 9 7 Clear 2. Enter your 4-digit Master User Code. The system displays the Master User programming screen. Slide ShowDate Time Ready To Arm Events BackReminders TestSchedulesDevicesUsers 5000-100-070-V0 3. Select the “Test ” icon. The system displays the Test screen.
– 64 – SYSTEM FUNCTIONS Testing the System (to be conducted weekly) Ready To Arm Back5000-100-076-V0 Version Number: CA01.00EXX CRC Number: 0X877D RF Version Number: 0.44 Walk TestDialer Test 4. Select the “Walk Test ” or “Dialer Test ” icon. If Walk Test is selected proceed to Step 5. If Dialer Test is selected proceed to Step 6 5. “Walk Test …” is displayed on the system status bar. Fault each zone as described below. 6. If the dialer test is unsuccessful the system will display a Reporter Failure message. Contact your security service provider. Walk Test FAULT ZONES. Open each protected door and window in turn and listen for three beeps from the control, followed by the zone ’s Voice Descriptor, if it is programmed. Identification of each faulted protection point should appear on the display. The display will clear when the door or window is closed. Walk in front of any interior motion detectors (if used) and listen for three beeps and/or voice descriptors, if programmed. The identification of the detector should appear on the display when it is activated, and its voice descriptor will be announced (if programmed). The display will clear when no motion is detected. Note that if wireless motion detectors are used, in order to conserve battery life, there is a 3-minute delay between activations. To test all smoke detectors, follow the manufacturers instructions. The identification of each detector should appear on the display when each is activated. If a problem is experienced with any protection point (no confirming sounds, no display), notify your service company. When all protection points have been checked and are intact (closed), there should be no zone identification numbers displayed on the touchscreen. Exiting Test Mode When testing is completed, exit the Walk Test or Dialer Test mode by entering an Off sequence. NOTE: If the Walk Test mode is inadvertently left active, it automatically turns off after 4 hours. The Dialer Test mode will remain active until exited via an Off sequence. LYNX Touch SIA Exit/Entry Delay Times The LYNX Touch SIA will send an event code to the Central Station after entering and after exiting from Test mode.
– 65 – SYSTEM FUNCTIONS Maintaining your system The components of your security system are designed to be as maintenance-free as possible. To make sure that your system is in working condition, do the following: 1. Test your system weekly. 2. Test your system after any alarm occurs (see the TESTING THE SYSTEM section). Routine Care Treat the components of your security system as you would any other electrical equipment. Do not slam sensor-protected doors or windows. Keep dust from accumulating on the touchscreen and all protective sensors, particularly on motion sensors and smoke detectors. The touchscreen and sensors should be cleaned carefully with a dry soft cloth. Do not spray water or any other fluid on the units. Low Battery Conditions in Wireless Sensors Each wireless sensor in your system has an internal battery. The system detects low battery conditions in wireless sensors, including smoke detectors, personal emergency transmitter, and the portable wireless keypad, and displays a “Battery Low ” message on the touchscreen, which also beeps. A low battery in a wireless keypad is detected as soon as one of its keys is pressed. In addition, a wireless smoke detector with a low battery also emits a chirp sound approximately once every 20 –30 seconds, identifying itself as the smoke detector with the weak battery. NOTE: A low battery message means that battery replacement in the indicated sensor(s) is due within 30 days. In the meantime, a sensor with a low battery is still operational. To silence Low Battery Warning Tones, enter an Off sequence. The low battery message display will remain on as a reminder. When you replace the weak battery with a fresh one, the sensor will send a good battery signal to the control when the sensor is activated (opening/closing of door, window, etc.). To clear the “Low Battery ” message, enter an Off sequence. When replacing batteries, use only those recommended by your installer. Alkaline batteries provide a minimum of 1 year of operation, and in most units and applications, provide 2 –4 years of service. 3-volt lithium batteries may provide from 4-7 years of operation. Actual battery life will depend on the environment in which the sensor is used, the number of signals that the transmitter in the sensor has had to send, and the specific type of sensor. Factors such as humidity, high or low temperatures, and large swings in temperature may all lead to the reduction of actual battery life in an installation.
– 66 – SYSTEM FUNCTIONS Maintaining your system Changing the LYNX Touch Series System Battery In the event of an AC power loss, the LYNX Touch Series is powered by a rechargeable, nickel-metal hydride battery pack. The battery pack should be replaced when a “Battery Low ” message with no zone number is displayed. NOTE: The battery pack (P/N LYNXRCHKIT-SC or LYNXRCHKIT-SHA) should be changed every four years and must be replaced by a qualified service technician. Following battery pack replacement, rechargeable batteries may take up to 48 hours to charge. The “Battery Low ” message may be displayed after one minute, however it should clear within 4 hours or by entering Test Mode.
– 67 – SUMMARY OF AUDIBLE & VISUAL NOTIFICATIONS SOUND CAUSE ANNOUNCEMENT* INTERRUPTED FIRE ALARM (3 beeps) OR CARBON MONOXIDE ALARM (4 beeps) fire alarm + zone voice descriptor OR Carbon monoxide alarm + zone voice descriptor (Voice descriptor is interlaced with the sounder and sounds every 45 seconds) CONTINUOUS BURGLARY/AUDIBLE EMERGENCY ALARM alarm + zone voice descriptor (Voice descriptor is interlaced with the sounder and sounds every 45 seconds) ONE SHORT BEEP (not repeated) a. SYSTEM DISARM b. SYSTEM ARMING ATTEMPT WITH AN OPEN ZONE. c. BYPASS VERIFY a. disarmed–ready to arm b. disarmed–not ready to arm c. zones bypassed ONE SHORT BEEP (once every 45 secs) a. SYSTEM IS IN TEST MODE b. LOW BATTERY AT A TRANSMITTER c. SYSTEM LOW BATTERY d. FAIL TO COMMUNICATE a. no announcement b. low battery + zone voice descriptor c. system low battery d. check system TWO SHORT BEEPS ARM AWAY armed away [instant] – exit now THREE SHORT BEEPS a. ARM STAY OR INSTANT b. ZONE OPENED WHILE SYSTEM IS IN CHIME MODE. a. armed stay [instant] – exit now b. zone voice descriptor RAPID BEEPING a. TROUBLE b. MEMORY OF ALARM a. fault + zone voice descriptor b. fire alarm or alarm + zone voice descriptor SLOW BEEPING a. ENTRY DELAY WARNING b. EXIT DELAY WARNING a. disarm system now b. armed [away] [instant] – exit now Additional Announcements: The system will announce the following primary messages, depending on the system ’s status at the time: • Disarmed –Ready to Arm [check system] • Disarmed [not ready to arm] • Armed [away] [stay] [instant] [check system] [exit now] The system will announce the following secondary messages, depending on the system ’s status at the time: • Fire Alarm + zone voice descriptor • Alarm + zone voice descriptor • Carbon Monoxide Alarm + zone voice descriptor • Carbon Monoxide Fault + zone voice descriptor • Fire Fault + zone voice descriptor • Fault + zone voice descriptor Alarm + zone voice descriptor • Low Battery + zone voice descriptor Fire Fault + zone voice descriptor • System Low Battery • Check System • AC Loss • Zones Bypassed • Chime Note: If there are no secondary messages, the primary status messages will be announced.
– 68 – SUMMARY OF AUDIBLE & VISUAL NOTIFICATIONS System Displays The following icons will be displayed on the Home screen along with specific zone status information (if applicable) to indicate system status. DISPLAY DEFINITION DISPLAY DEFINITION AC Loss Door Open Alarm (intrusion) Window Open Armed Away Exit Active Armed Stay Fire Battery Low Flood Check Zones Glass Break CO Alarm Medical Alarm Disarmed Not Ready to Arm Motion Disarmed Ready to Arm Temperature Reporter Failure 90 RF Jam Cover Tamper 94 Phone Line Cut Trouble 103 Comm. Trouble
– 69 – SUMMARY OF AUDIBLE & VISUAL NOTIFICATIONS Zone Status Icons The following icons may be displayed on the Zone Status screen. ICON DEFINITION ICON DEFINITION Alarm Trouble (red) Fault (Yellow) Bypass Ready LED Meanings ARMED LED (Red): ON = System armed OFF = System disarmed Blinking = System armed, but a fault exists or alternating with READY LED when AVM (VOX or Talk) or speaker phone mode is active. READY LED (Green): ON = System disarmed, ready to arm Blinking = System disarmed, not ready to arm (a fault exists) or alternating with ARMED LED when AVM (VOX or Talk) or speakerphone mode is active. Note: When the system is armed, the READY LED turns off.
– 70 – Regulatory Agency Statements Federal Communications Commission (FCC) Part 15 The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or Use rs Manual. Unauthorized changes or modifications could void the users authority to operate the equipment. CLASS B DIGITAL DEVICE STATEMENT NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installatio n. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: • Reorient or relocate the receiving antenna. • Increase the separation between the equipment and receiver. • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. • Consult the dealer or an experienced radio/TV technician for help. This Class B digital apparatus complies with Canadian ICES-003. Cet appareil num érique de la classe B est conforme à la norme NMB-003 du Canada. Industry Canada (IC) This device complies with RSS210 of Industry Canada. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may caus e undesired operation. Cet appareil est conforme à la partie 15 des règles de la FCC & de RSS 210 des Industries Canada. Son fonctionnement est soumis aux conditions suivantes: (1) Cet appareil ne doit pas causer d interferences nuisibles. (2) Cet appareil doit accepter toute interference reçue y compris les interferences causant une reception ind ésirable.