Honeywell control panel LYNX Touch 5100 User Manual
Have a look at the manual Honeywell control panel LYNX Touch 5100 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
– 71 – FIRE FIREFIRE FIRE/CO /CO/CO /CO ALARM SYSTEM ALARM SYSTEM ALARM SYSTEM ALARM SYSTEM (If Installed) General Information UL ULUL UL LYNX Touch is not intended for UL985 Household Fire applications unless a 24-hour backup battery (P/N LYNXRCHKIT-SHA) is installed. General Your fire alarm system (if installed) is active 24 hours a day, providing continuous protection. In the event of an emergency, the installed smoke, heat and/or carbon monoxide detectors will automatically activate your security system, triggering a loud, intermittent sound from the touch screen. The sound will be interlaced with the voice descriptor, sounding every 15 seconds. A “FIRE” or “CO” message will appear at your touch screen and remain on until you silence and clear the alarm display. In Case of Fire 1. Should you become aware of a fire emergency before your detectors sense the problem, go to the LYNX Touch and press and hold the panic button and then select the Fire icon. The alarm will sound and an alarm will be transmitted to the central station. 2. Evacuate all occupants from the premises. 3. If flames and/or smoke are present, leave the premises and notify your local Fire Department immediately. 4. If no flames or smoke are apparent, investigate the cause of the alarm. The zone number of the zone(s) in an alarm condition will appear at the touch screen. In Case of Carbon Monoxide Alarm 1. If a high level of carbon monoxide is detected you should evacuate all occupants from the premises and immediately move to a spot where fresh air is available, preferably outdoors. 2. From a safe area, contact your security service provider for further instructions. Silencing a Fire/Carbon Monoxide Alarm 1. Silence the alarm by entering an OFF sequence. 2. To clear the alarm, enter a second OFF sequence. 3 If the touch screen indicates a trouble condition after the second OFF sequence, check that smoke detectors are not responding to smoke- or heat-producing objects in their vicinity. Should this be the case, eliminate the source of heat or smoke. 4. If this does not remedy the problem, there may still be smoke in the detector. Clear it by fanning the detector for about 30 seconds. 5. When the problem has been corrected, clear the display by entering another OFF sequence.
– 72 – FIRE FIREFIRE FIRE/CO /CO/CO /CO ALARM SYSTEM ALARM SYSTEM ALARM SYSTEM ALARM SYSTEM National Fire Protection Association’s Smoke Detector Recommendations UL ULUL UL LYNX Touch is not intended for UL985 Household Fire applications unless a 24-hour backup battery (P/N LYNXRCHKIT-SHA) is installed. With regard to the number and placement of smoke and heat detectors, we subscribe to the recommendations contained in the National Fire Protection Associations (NFPA) Standard #72 noted below. Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household. The equipment should be installed as follows: A smoke detector installed outside of each separate sleeping area, in the immediate vicinity of the bedrooms and on each additional story of the family living unit, including basements and excluding crawl spaces and unfinished attics. In addition, the NFPA recommends that you install heat or smoke detectors in the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages. DINING KITCHENBEDROOM BEDROOM BEDROOM BEDROOM LIVING ROOMBEDROOM BDRM DINING LIVING ROOM TV ROOM KITCHEN BEDROOM BEDROOM TO BR LVNG RM BASEMENT KTCHN.CLOSED DOOR GARAGE Smoke Detectors for Minimum Protection Smoke Detectors for Additional Protection Heat-Activated Detectors BDRM floor_plan-001-V1
– 73 – FIRE FIREFIRE FIRE/CO /CO/CO /CO ALARM SYSTEM ALARM SYSTEM ALARM SYSTEM ALARM SYSTEM Emergency Evacuation UL ULUL UL LYNX Touch is not intended for UL985 Household Fire applications unless a 24-hour backup battery (P/N LYNXRCHKIT-SHA) is installed. Establish and regularly practice a plan of escape in the event of fire. The following steps are recommended by the National Fire Protection Association: 1. Position your detector or your interior and/or exterior sounders so that they can be heard by all occupants. 2. Determine two means of escape from each room. One path of escape should lead to the door that permits normal exit from the building. The other should be an alternative escape, such as a window, should your path to that door be unpassable. Station an escape ladder at such windows if there is a long drop to the ground. 3. Sketch a floor plan of the building. Show windows, doors, stairs and rooftops that can be used to escape. Indicate escape routes for each room. Keep these routes free from obstruction and post copies of the escape routes in every room. 4. Assure that all bedroom doors are shut while you are asleep. This will prevent deadly smoke from entering while you escape. 5. Try the door. If the door is hot, check your alternate escape route. If the door is cool, open it cautiously. Be prepared to slam the door if smoke or heat rushes in. 6. When smoke is present, crawl on the ground. Do not walk upright, since smoke rises and may overcome you. Clearer air is near the floor. 7. Escape quickly; dont panic. 8. Establish a place outdoors, away from your house, where everyone can meet and then take steps to contact the authorities and account for those missing. Choose someone to assure that nobody returns to the house — many die going back. • FRONT BACK BATH BEDROOMKITCHEN BACK DOOR 1 FLOORST BEDROOM 2 FLOORND BATHBEDROOMPORCH CLOSET BEDROOM BEDR emerevac
– 74 – SYSTEM FUNCTIONS Testing the System (to be conducted weekly) Test Modes The Test icon provides access to the Walk Test, Dialer Test and Reboot functions. The Walk Test mode allows each protection point to be checked for proper operation. When the Walk Test mode is active, the control sounds a single beep every 30 seconds as a reminder that the system is in the Test mode. The Dialer Test performs a check of the system dialer. The Reboot feature allows you to reboot the system if required. NOTE: An alarm message will not be sent to your alarm monitoring company during these tests. Entering Test Mode Disarm the system and close all protected windows, doors, etc. The “Ready” indicator should be lit. Testing or Rebooting the System Arm Away Ready To Arm Dashboard Arm Stay Back DelaySettings 10:18 AM June 8, 20105100-100-003-V0 Tools 1. With the system in the disarmed state, select the “ Tools” icon from the second page of the Home Screen. The system displays the Keypad screen. Ready To Arm Program the system Enter Code: Cancel 5000-100-009-V0 23 1 5 6 4 0 8 9 7 Clear 2. Enter your 4-digit Master User Code. The system displays the Master User programming screen.
– 75 – SYSTEM FUNCTIONS Testing the System (to be conducted weekly) WiFi Config Date Time Ready To Arm Events Back Reminders KeypadUsers 5100-100-006-V0 Slide Show Test 3. Select the “Test ” icon. The system displays the Test screen. Ready To Arm Back5100-100-087-V0 Prod. Id. : DE Sw. Rev.: 05.00 CRC Number: 0X**** Walk TestDialer TestReboot 4. Select the “Walk Test ”, “Dialer Test ” or “ Reboot ” icon. If Walk Test is selected proceed to Step 5. If Dialer Test is selected proceed to Step 6. If Reboot is selected proceed to Step 7. 5. “Walk Test …” is displayed on the system status bar and the control sounds a single beep every 30 seconds. Fault each zone as described below. 6. If the dialer test is unsuccessful the system will display a Reporter Failure message. Contact your security service provider. 7. The system will reboot itself. 8. After the reboot sequence is completed, conduct a W alk Test to verify that all transmitters are operational in the system . Walk Test FAULT ZONES. Open each protected door and window in turn and listen for three beeps from the control, followed by the zone’s Voice Descriptor, if it is programmed. Identification of each faulted protection point should appear on the display. The display will clear when the door or window is closed. Walk in front of any interior motion detectors (if used) and listen for three beeps and/or voice descriptors, if programmed. The identification of the detector should appear on the display when it is activated, and its voice descriptor will be announced (if programmed). The display will clear when no motion is detected. Note that if wireless motion detectors are used, in order to conserve battery life, there is a 3-minute delay between activations. To test all smoke detectors, follow the manufacturers instructions. The identification of each detector should appear on the display when each is activated.
– 76 – SYSTEM FUNCTIONS Testing the System (to be conducted weekly) If a problem is experienced with any protection point (no confirming sounds, no display), notify your service company. When all protection points have been checked and are intact (closed), there should be no zone identification numbers displayed on the touch screen. Exiting Test Mode When testing is completed, exit the Walk Test or Dialer Test mode by entering an Off sequence. NOTE: If the Walk Test mode is inadvertently left active, it automatically turns off after 4 hours. The Dialer Test mode will remain active until exited via an Off sequence. LYNX Touch SIA Exit/Entry Delay Times The LYNX Touch SIA will send an event code to the Central Station after entering and after exiting from Test mode.
– 77 – SYSTEM FUNCTIONS Maintaining your system The components of your security system are designed to be as maintenance-free as possible. To make sure that your system is in working condition, do the following: 1. Test your system weekly (see the TESTING THE SYSTEM section). 2. Test your system after any alarm occurs (see the TESTING THE SYSTEM section). 3. Clean the touch screen weekly. Routine Care Treat the components of your security system as you would any other electrical equipment. Do not slam sensor-protected doors or windows. Keep dust from accumulating on the touch screen and all protective sensors, particularly on motion sensors and smoke detectors. The touch screen and sensors should be cleaned carefully with a dry soft cloth. Do not spray water or any other fluid on the units. Cleaning the Touch screen Ready To Arm 5000-100-006-V1 Arm Away Delay Phone More Automation Message Zones Arm Stay 72 10:18 AM June 8, 2010 1. With the system in the disarmed or armed state, select the “ Settings” icon from the second page of the Home Screen. The system displays the Settings ” screen. Ready To Arm Ringer Chime Voice Brightness ContrastVolume 5100-100-088-V0 Save Clean 2. Select the “Clean ” icon. The touch screen become inactive for a period of 15 seconds. A box displays “Please Use A Damp, Soft Cloth Touch Screen Will Be Disabled For 15 Seconds ” and the time will count down. 3. After 15 seconds the screen returns to the settings screen and becomes active. Note: If any user notification events occur while the screen cleaning mode is active and the system is armed, the mode will be canceled and the system will operate normally. If certain user notification events occur (i.e.; motion or silent alarm) while the screen cleaning mode is active and the system is disarmed the mode will not be canceled.
– 78 – SYSTEM FUNCTIONS Maintaining your system Low Battery Conditions in Wireless Sensors Each wireless sensor in your system has an internal battery. The system detects low battery conditions in wireless sensors, including smoke detectors, personal emergency transmitter, and the portable wireless keypad, and displays a “Battery Low” message on the touch screen, which also beeps. A low battery in a wireless keypad is detected as soon as one of its keys is pressed. In addition, a wireless smoke detector with a low battery also emits a chirp sound approximately once every 20–30 seconds, identifying itself as the smoke detector with the weak battery. NOTE: A low battery message means that battery replacement in the indicated sensor(s) is due within 30 days. In the meantime, a sensor with a low battery is still operational. To silence Low Battery Warning Tones, enter an Off sequence. The low battery message display will remain on as a reminder. When you replace the weak battery with a fresh one, the sensor will send a good battery signal to the control when the sensor is activated (opening/closing of door, window, etc.). To clear the “Low Battery” message, enter an Off sequence. When replacing batteries, use only those recommended by your installer. Alkaline batteries provide a minimum of 1 year of operation, and in most units and applications, provide 2 –4 years of service. 3-volt lithium batteries may provide from 4-7 years of operation. Actual battery life will depend on the environment in which the sensor is used, the number of signals that the transmitter in the sensor has had to send, and the specific type of sensor. Factors such as humidity, high or low temperatures, and large swings in temperature may all lead to the reduction of actual battery life in an installation. Changing the LYNX Touch Series System Battery In the event of an AC power loss, the LYNX Touch Series is powered by a rechargeable, nickel-metal hydride battery pack. The battery pack should be replaced when a “Battery Low” message with no zone number is displayed. NOTE: The battery pack (P/N LYNXRCHKIT-SC or LYNXRCHKIT-SHA) should be changed every four years and must be replaced by a qualified service technician. Following battery pack replacement, rechargeable batteries may take up to 48 hours to charge. The “Battery Low” message may be displayed after one minute, however it should clear within 4 hours or by entering Test Mode.
– 79 – SUMMARY OF AUDIBLE & VISUAL NOTIFICATIONS SOUND CAUSE ANNOUNCEMENT* INTERRUPTED FIRE ALARM (3 beeps) OR CARBON MONOXIDE ALARM (4 beeps) fire alarm + zone voice descriptor OR Carbon monoxide alarm + zone voice descriptor (Voice descriptor is interlaced with the sounder and sounds every 45 seconds) CONTINUOUS BURGLARY/AUDIBLE EMERGENCY ALARM alarm + zone voice descriptor (Voice descriptor is interlaced with the sounder and sounds every 45 seconds) ONE SHORT BEEP (not repeated) a. SYSTEM DISARM b. SYSTEM ARMING ATTEMPT WITH AN OPEN ZONE. c. BYPASS VERIFY a. disarmed– ready to arm b. disarmed– not ready to arm c. zones bypassed ONE SHORT BEEP (once every 45 secs) a. SYSTEM IS IN TEST MODE b. LOW BATTERY AT A TRANSMITTER c. SYSTEM LOW BATTERY d. FAIL TO COMMUNICATE a. no announcement b. low battery + zone voice descriptor c. system low battery d. check system TWO SHORT BEEPS ARM AWAY armed away [instant] – exit now THREE SHORT BEEPS a. ARM STAY OR INSTANT b. ZONE OPENED WHILE SYSTEM IS IN CHIME MODE. a. armed stay [instant] – exit now b. zone voice descriptor RAPID BEEPING a. TROUBLE b. MEMORY OF ALARM a. fault + zone voice descriptor b. fire alarm or alarm + zone voice descriptor SLOW BEEPING a. ENTRY DELAY WARNING b. EXIT DELAY WARNING a. disarm system now b. armed [away] [instant] – exit now Additional Announcements: The system will announce the following primary messages, depending on the system’s status at the time: • Disarmed –Ready to Arm [check system] • Disarmed [not ready to arm] • Armed [away] [stay] [instant] [check system] [exit now] The system will announce the following secondary messages, depending on the system’s status at the time: • Fire Alarm + zone voice descriptor • Alarm + zone voice descriptor • Carbon Monoxide Alarm + zone voice descriptor • Carbon Monoxide Fault + zone voice descriptor • Fire Fault + zone voice descriptor • Fault + zone voice descriptor Alarm + zone voice descriptor • Low Battery + zone voice descriptor Fire Fault + zone voice descriptor • System Low Battery • Check System • Check Zone • Activity Detected + zone type • AC Loss • Zones Bypassed • Chime Note: If there are no secondary messages, the primary status messages will be announced.
– 80 – SUMMARY OF AUDIBLE & VISUAL NOTIFICATIONS System Displays The following icons will be displayed on the Home screen along with specific zone status information (if applicable) to indicate system status. DISPLAY DEFINITION DISPLAY DEFINITION AC Loss Door Open Alarm (intrusion) Window Open Armed Away Exit Active Armed Stay Fire OR Heat Sensor Battery Low Flood Check Zones Glass Break CO Alarm Medical Alarm Disarmed Not Ready to Arm Motion Disarmed Ready to Arm Temperature Reporter Failure 90 RF Jam Cover Tamper 94 Phone Line Cut Trouble 103 Comm. Trouble 72 Automation (Z-Wave Node Failed)