Appearance, Dimension and Interface 1------------ Reset Port 2------------ Signal Ground Wire of Unit B 3------------ Signal Line of Unit B 4------------ Signal Ground Wire of Unit A 5------------ Signal Line of Unit A 6------------ Central Control Interface — B 7------------ Central Control Interface — A 8------------ Communication Line for RS-232 Linking Control Computer or Communication Line of MODEM (We only offer agreement of deteetor for programming control software ) 9------------ Power Cord. If damaged, to avoid dangers, the power cord must be replaced by manufacturer or its maintenance department or similar professional staff. Performance Parameters and Accessories Power Supply 1PH, 220~230VAC, 50Hz Consumed Power 3W The Maximum Dimension 139 × 142 × 55 mm Weight 0.53 kg Accessories 2 pieces of communication line to air conditioner (UL2547, AWG24 2C) (Core: red/white) \b \b \f \b\b\f - 51 -
Installation and Debugging Installation Methods Fix detector by means of two screw s hanging methods, and distance between screws see (right figure). 1. Realization, installatio n, wiring and power distribution of a system only using two-unit swit chover function are much more easier, after finishing installation of two units, connect detector to the remote control interface of the air conditioner computer board, set detector as two-unit switchover working mode and set two-unit switchover time as required. 2. It must form a complete set of documents (project la yout for group control network, installation and construction records for group control network, debugging records for group control net, maintenance and repair records for group control network) for group control network of Haier commercial air conditioner long distan ce system (hereinafter for short as: group c ontrol network) from layout design, installation, debugging to after service, and file all for future refere\ nce. 3. Layout design of group control net woek shall be finished in advance, including: (1) compositions of group control network system and qu antities controlled; (2) selection type of air conditioner, installation place, power distribution and wiring manner and connection to detector; (3) installation place of detector, allocation of unit address code, power distribution and wiring manner and connection to group control bus; (4) in stallation and wiring of group control bus, length limitation of bus, resistance matching of two en ds of bus, and single point earth of bus shielding layer; (5) installation place of central controller, allocation of unit address code, power distribution and wiring manner. 4. Principles of layout design of group control net : (1) detector is essential part, to keep proper responding speed and co mmunication reliability, d etector quantities carried by one central controller shall not more than 64; (2) air conditioner must be a net air conditioner, installation must strictly follow the installation and operat ion instructions shipped with the unit, and confirm that power blackout compensation fun ction of local air conditioner has bee n cancelled when debugging; (3) suggest that do not use two-unit switchover function of detector in the case of high load, i.e. suggest that do not use one detector to load two air conditioners when detector forming group control net, otherwise temperature difference control may be affected. If it is necessary to install two-unit switchover function for group cont rol net, air conditioners with same type and half installation distance of that of normal installation are required; (4) installation place of detector shall not too far away from air conditioner, not ex ceed the wiring length; (5) unit address code of detector shall be strictly allocated in a seq uence from small one to big one, and set continuous unit number; (6) for power distribution of detector, the power distributi on line and communication line shall not be too close from each other or in the same wiring chan nel, and no other special requirements; (7) for connection between detector and group control bus, not allowed to connect branch line from the group control bus; (8) shie lding line of communication line betwee n detector and air conditioner and the shielding line of commu nication bus between detector and central controller shall be shorted; (9) wiring and power distribution line of the group control bus shall not be too close from each other or in the same wiring channel, and others may refer to wiring requirements of building autocontrol system; (10) limit the total leng th of group control bus to 1000 meters; (11) at both ends between Bus A and Bus B connect a metallic membrane precision resistance of 100 or 120 ohm respectively; if needed (12) single point earth for bus shielding l ine, suggest to be arranged in the middle of communication bus, close to central controller; \b \b \f \b\b\f - 52 -
Installation and Debugging (13) in principle, installation place of central controller shall be arranged in the middle of communication bus, close to shielding earth line of communication bus; (14) unit address codes of central controller adopt the defaul t settings; (15) central controller has its own power distribution line, the power distribution line and communicati on line shall not be too close from each other or in the same wiring channel, and no other special requirements. 5. Installation and construction of wiring of group control network shall be processed together with installation and debugging of net air conditioner, pay attention to commissioning before installation. 6. Connection between detector and air conditioner: detector working mode and unit address code shall be strictly set according to planned layout; detector makes wire communication with at most two air conditioners (A, B) through 4-poles screw-fixing terminal at air conditioner interface (A +,A-, B+, B-); connection between detect or and air conditioner use un iform wiring; use uniform wiring for connection between detector and air conditioner, one plug in type terminal of wiring connected to Remote control interface on the computer board of air conditioner, and cores of another terminal respectively connected to A + and A- (B+ and B-); connection has polarity, and generally white wire connected to A +/B+ and black/red wire connected to A-/B-; if detector cannot work normally when debugging, then can check and remove malfunctio n by changing positive and negative polarity. During debugging also can judge wheth er communication interface to air conditioner is normal according to the running status indicated by operation indicator (green\ LED). 7. Connect detector and communication bus after finish the wiring of communication bus: connect several detectors to communicati on bus in parallel, all terminal port A (including central controller) on one bus, and all terminal port B (including centra l controller) on another bus, at both ends of the communication bus - A terminal port line and B terminal port line shall paralleling connect a metal membrane precision resistance of 100 or 120 ohm respectively if needed. Earth one point of the shielding line of communication bus, which is at th e middle position of the communication bus, and the total length of communication bus shall be limited within 1000m. 8. Connect central controller and communication bu s after finish installation and connection of detector: central controller is connected to communication bus through the 2-post screw-fixing terminal (A and B) of interface RS-485, locating in the middle of the communication bus, with position close to the earth point of the shielding line of communication bus. 9. Power on and debugging : after power on, central controller periodically monitors the detector and air conditioner groups on the communication bus, a nd after inquiring for a period of time the unit number shall display as expected, check and debug if having any difference. 10. Set the dialing switch of detec tor: (1) there is a 8-bit (18) dialing switch inside the detector, OFF means 0 and ON means 1; (2) the eighth bit used for s etting single unit working mode or two-unit switchover working mode, OFF m eans single unit and ON means two-un it; (3) the lower seven bits (from the seventh to the first bit) have up to 128 selections when forming group control net, which are used for setting unit address code, see the table below for detail setting check list; (4) the lower seven bits have up to 128 selections when forming group control net and using two-unit switchover function, which are used for setting unit address code, see the ta ble below for detail setting check list, and the default two-unit switchover time is 24 hrs; (5) the lower seven bits have up to 128 selections when not forming group control net, wh ich are used for setting two-unit sw itchover time, see the table below for detail setting check list. \b \b \f \b\b\f - 53 -
Installation and Debugging Tw o Unit Dialing setting Ä 1 means dialing to ON È0 means dialing to OFF Å NO.8 NO.7 NO.6 NO.5 NO.4 NO.3 NO.2 NO.1 Low 7-bit value Air conditioner installation sequence Unit number of central controller Two-unit switchover time * 0 0 0 0 0 0 0 0 1 1-1 No limit * 0 0 0 0 0 0 1 1 2 1-2 1hr * 0 0 0 0 0 1 0 2 3 1-3 2hrs * 0 0 0 0 0 1 1 3 4 1-4 3hrs * 0 0 0 0 1 0 0 4 5 1-5 4hrs * 0 0 0 0 1 0 1 5 6 1-6 5hrs * 0 0 0 0 1 1 0 6 7 1-7 6hrs * 0 0 0 0 1 1 1 7 8 1-8 7hrs * 0 0 0 1 0 0 0 8 9 1-9 8hrs * 0 0 0 1 0 0 1 9 10 1-10 9hrs * 0 0 0 1 0 1 0 10 11 1-11 10hrs * 0 0 0 1 0 1 1 11 12 1-12 11hrs * 0 0 0 1 1 0 0 12 13 1-13 12hrs * 0 0 0 1 1 0 1 13 14 1-14 13hrs * 0 0 0 1 1 1 0 14 15 1-15 14hrs * 0 0 0 1 1 1 1 15 16 1-16 15hrs * 0 0 1 0 0 0 0 16 17 2-1 16hrs * 0 0 1 0 0 0 1 17 18 2-2 17hrs * 0 0 1 0 0 1 0 18 19 2-3 18hrs * 0 0 1 0 0 1 1 19 20 2-4 19hrs * 0 0 1 0 1 0 0 20 21 2-5 20hrs * 0 0 1 0 1 0 1 21 22 2-6 21hrs * 0 0 1 0 1 1 0 22 23 2-7 22hrs * 0 0 1 0 1 1 1 23 24 2-8 23hrs * 0 0 1 1 0 0 0 24 25 2-9 24hrs * 0 0 1 1 0 0 1 25 26 2-10 25hrs * 0 0 1 1 0 1 0 26 27 2-11 26hrs * 0 0 1 1 0 1 1 27 28 2-12 27hrs * 0 0 1 1 1 0 0 28 29 2-13 28hrs * 0 0 1 1 1 0 1 29 30 2-14 29hrs * 0 0 1 1 1 1 0 30 31 2-15 30hrs * 0 0 1 1 1 1 1 31 32 2-16 31hrs * 0 1 0 0 0 0 0 32 33 3-1 32hrs * 0 1 0 0 0 0 1 33 34 3-2 33hrs * 0 1 0 0 0 1 0 34 35 3-3 34hrs * 0 1 0 0 0 1 1 35 36 3-4 35hrs * 0 1 0 0 1 0 0 36 37 3-5 36hrs * 0 1 0 0 1 0 1 37 38 3-6 37hrs * 0 1 0 0 1 1 0 38 39 3-7 38hrs * 0 1 0 0 1 1 1 39 40 3-8 39hrs * 0 1 0 1 0 0 0 40 41 3-9 40hrs * 0 1 0 1 0 0 1 41 42 3-10 41hrs * 0 1 0 1 0 1 0 42 43 3-11 42hrs * 0 1 0 1 0 1 1 43 44 3-12 43hrs * 0 1 0 1 1 0 0 44 45 3-13 44hrs * 0 1 0 1 1 0 1 45 46 3-14 45hrs * 0 1 0 1 1 1 0 46 47 3-15 46hrs * 0 1 0 1 1 1 1 47 48 3-16 47hrs * 0 1 1 0 0 0 0 48 49 4-1 48hrs * 0 1 1 0 0 0 1 49 50 4-2 49hrs * 0 1 1 0 0 1 0 50 51 4-3 50hrs * 0 1 1 0 0 1 1 51 52 4-4 51hrs * 0 1 1 0 1 0 0 52 53 4-5 52hrs * 0 1 1 0 1 0 1 53 54 4-6 53hrs * 0 1 1 0 1 1 0 54 55 4-7 54hrs * 0 1 1 0 1 1 1 55 56 4-8 55hrs * 0 1 1 1 0 0 0 56 57 4-9 56hrs * 0 1 1 1 0 0 1 57 58 4-10 57hrs * 0 1 1 1 0 1 0 58 59 4-11 58hrs * 0 1 1 1 0 1 1 59 60 4-12 59hrs \b \b \f \b\b\f -54 -
Installation and Debugging Tw o Unit Dialing setting Ä 1 means dialing to ON È0 means dialing to OFF Å NO.8 NO.7 NO.6 NO.5 NO.4 NO.3 NO.2 NO.1 Low 7-bit value Air conditioner installation sequence Unit number of central controller Two-unit switchover time * 0 1 1 1 1 0 0 60 61 4-13 60hrs * 0 1 1 1 1 0 1 61 62 4-14 61hrs * 0 1 1 1 1 1 0 62 63 4-15 62hrs * 0 1 1 1 1 1 1 63 64 4-16 63hrs * 1 0 0 0 0 0 0 64 65 5-1 64hrs * 1 0 0 0 0 0 1 65 66 5-2 65hrs * 1 0 0 0 0 1 0 66 67 5-3 66hrs * 1 0 0 0 0 1 1 67 68 5-4 67hrs * 1 0 0 0 1 0 0 68 69 5-5 68hrs * 1 0 0 0 1 0 1 69 70 5-6 69hrs * 1 0 0 0 1 1 0 70 71 5-7 70hrs * 1 0 0 0 1 1 1 71 72 5-8 71hrs * 1 0 0 1 0 0 0 72 73 5-9 72hrs * 1 0 0 1 0 0 1 73 74 5-10 73hrs * 1 0 0 1 0 1 0 74 75 5-11 74hrs * 1 0 0 1 0 1 1 75 76 5-12 75hrs * 1 0 0 1 1 0 0 76 77 5-13 76hrs * 1 0 0 1 1 0 1 77 78 5-14 77hrs * 1 0 0 1 1 1 0 78 79 5-15 78hrs * 1 0 0 1 1 1 1 79 80 5-16 79hrs * 1 0 1 0 0 0 0 80 81 6-1 80hrs * 1 0 1 0 0 0 1 81 82 6-2 81hrs * 1 0 1 0 0 1 0 82 83 6-3 82hrs * 1 0 1 0 0 1 1 83 84 6-4 83hrs * 1 0 1 0 1 0 0 84 85 6-5 84hrs * 1 0 1 0 1 0 1 85 86 6-6 85hrs * 1 0 1 0 1 1 0 86 87 6-7 86hrs * 1 0 1 0 1 1 1 87 88 6-8 87hrs * 1 0 1 1 0 0 0 88 89 6-9 88hrs * 1 0 1 1 0 0 1 89 90 6-10 89hrs * 1 0 1 1 0 1 0 90 91 6-11 90hrs * 1 0 1 1 0 1 1 91 92 6-12 91hrs * 1 0 1 1 1 0 0 92 93 6-13 92hrs * 1 0 1 1 1 0 1 93 94 6-14 93hrs * 1 0 1 1 1 1 0 94 95 6-15 94hrs * 1 0 1 1 1 1 1 95 96 6-16 95hrs * 1 1 0 0 0 0 0 96 97 7-1 96hrs * 1 1 0 0 0 0 1 97 98 7-2 97hrs * 1 1 0 0 0 1 0 98 99 7-3 98hrs * 1 1 0 0 0 1 1 99 100 7-4 99hrs * 1 1 0 0 1 0 0 100 101 7-5 100hrs * 1 1 0 0 1 0 1 101 102 7-6 101hrs * 1 1 0 0 1 1 0 102 103 7-7 102hrs * 1 1 0 0 1 1 1 103 104 7-8 103hrs \b \b \f \b\b\f\b \b \f \b\b\f -55 -
Installation and Debugging Tw o Unit Dialing setting Ä 1 means dialing to ON È0 means dialing to OFF Å NO.8 NO.7 NO.8 NO.7 NO.8 NO.7 NO.8 NO.7 Low 7-bit value Air conditioner installation sequence Unit number of central controller Two-unit switchover time * 1 1 0 1 0 0 0 104 105 7-9 104hrs * 1 1 0 1 0 0 1 105 106 7-10 105hrs * 1 1 0 1 0 1 0 106 107 7-11 106hrs * 1 1 0 1 0 1 1 107 108 7-12 107hrs * 1 1 0 1 1 0 0 108 109 7-13 108hrs * 1 1 0 1 1 0 1 109 110 7-14 109hrs * 1 1 0 1 1 1 0 110 111 7-15 110hrs * 1 1 0 1 1 1 1 111 112 7-16 111hrs * 1 1 1 0 0 0 0 112 113 8-1 112hrs * 1 1 1 0 0 0 1 113 114 8-2 113hrs * 1 1 1 0 0 1 0 114 115 8-3 114hrs * 1 1 1 0 0 1 1 115 116 8-4 115hrs * 1 1 1 0 1 0 0 116 117 8-5 116hrs * 1 1 1 0 1 0 1 117 118 8-6 117hrs * 1 1 1 0 1 1 0 118 119 8-7 118hrs * 1 1 1 0 1 1 1 119 120 8-8 119hrs * 1 1 1 1 0 0 0 120 121 8-9 120hrs * 1 1 1 1 0 0 1 121 122 8-10 121hrs * 1 1 1 1 0 1 0 122 123 8-11 122hrs * 1 1 1 1 0 1 1 123 124 8-12 123hrs * 1 1 1 1 1 0 0 124 125 8-13 124hrs * 1 1 1 1 1 0 1 125 126 8-14 125hrs * 1 1 1 1 1 1 0 126 127 8-15 126hrs * 1 1 1 1 1 1 1 127 128 8-16 127hrs \b \b \f \b\b\f -56 -
12 Connecting board IGU04 0010451976 IGU04 detector is used with ICR01 central controller, IGU04 appearanc e and dimension is same with detector YCJ-A001 12.1 Appearance Caution: One central cont roller can control Up to 5 units of IGU04 CN1 J4 From central controller To indoor units S1 LED2 LED3 LED1 B-A QP B-BFrom central controller To outdoor unitsIGU04 To 220V,50Hz 12.2 PCB photo and drawing 2. Dip switch setting of connecting board ICR01 The dip switch is as below figure (ON:1, OFF: 0): O N 12345 678 S1 LED4 \b \b \f \b\b\f -57 - S\b \f TT \b SSS \f TT \f \b SSS TT \f\f\f\f \b SSS TT \f\f\f\f\f \b SSS T \b S T \f \b S \f \b SS \b
Commercial Air Conditioner S1(3-8) is used to set IGU04 address, in one central control system, the address of IGU04 must be different. 12.3.Summarization For installation information ,please refer central controller ICR01 manual , one ICR01 can control up to 5 sets of IGU04. - 58 -