Home > GE > Gas Turbines > GE Frame 5 Service Manual

GE Frame 5 Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual GE Frame 5 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 45 GE manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							27
    inspection of all of the major flange-to-flange components of 
    the gas turbine, which are subject to deterioration during normal 
    turbine operation. This inspection includes previous elements of the 
    combustion and hot gas path inspections, and requires laying open 
    the complete flange-to-flange gas turbine to the horizontal joints, 
    as shown in Figure 32.
    Removal of all of the upper casings allows access to the 
    compressor rotor and stationary compressor blading, as well as 
    to the bearing assemblies. Prior to removing casings, shells, and 
    frames, the unit must be properly supported. Proper centerline 
    support using mechanical jacks and jacking sequence procedures 
    are necessary to assure proper alignment of rotor to stator, obtain 
    accurate half shell clearances, and to prevent twisting of the 
    casings while on the half shell. Reference the O&M Manual for 
    unit-specific jacking procedures. In addition to combustion and 
    hot gas path inspection requirements, typical major inspection 
    requirements are: •	
    Check all radial and axial clearances against their original values 
    (opening and closing).
    •	 Inspect all casings, shells, and frames/diffusers for cracks   
    and erosion.
    •	 Inspect compressor inlet and compressor flow-path for fouling, 
    erosion, corrosion, and leakage.
    •	 Check rotor and stator compressor blades for tip clearance,   
    rubs, object damage, corrosion pitting, and cracking.
    •	 Remove turbine buckets and perform a nondestructive check 
    of buckets and wheel dovetails. Wheel dovetail fillets, pressure 
    faces, edges, and intersecting features must be closely examined 
    for conditions of wear, galling, cracking, or fretting.
    •	 Inspect unit rotor for cracks, object damage, or rubs.
    •	 Inspect bearing liners and seals for clearance and wear.
    Figure 37  . Gas turbine major inspection – key elements
    Criteria
    •	 O&M	Manual	 •	 TILs
    •	 GE	 Field	EngineerInspection Methods
    •	 Visual	 •	 Liquid	Penetrant
    •	 Borescope	 •	 Ultrasonics
    Major Inspection
    Hot Gas Path Inspection Scope—Plus:
    Key Hardware  Inspect For  Potential Action
    Compressor blading  Foreign object damage  Repair/refurbishment/replace
    Unit rotor Oxidation/corrosion/erosion  •	Bearings/seals
    Journals and seal surfaces  Cracking  – Clean
    Bearing seals  Leaks  – Assess oil condition
    Exhaust system  Abnormal wear – Re-babbitt
    Missing hardware •	Compressor	 blades
    Clearance limits – Clean
    Coating wear – Blend
    Fretting •	Exhaust	 system
    – Weld repair
    – Replace flex seals/L-seals
    Compressor and compressor 
    discharge case hooks Wear 
    Repair
    All cases – exterior and interior  Cracks  Repair or monitor
    Cases – Exterior Slippage Casing alignment
    GE Power & Water | GER-3620M (00015001200140018
    )  
    						
    							28
    •	Visually inspect compressor and compressor discharge case
    hooks for signs of wear.
    •	 Visually inspect compressor discharge case inner barrel.
    •	 Inspect exhaust frame flex seals, L-seals, and horizontal joint
    gaskets for any signs of wear or damage. Inspect steam gland
    seals for wear and oxidation.
    •	 Check torque values for steam gland bolts and re-torque
    to full values.
    •	 Check alignment – gas turbine to generator/gas turbine to
    accessory gear.
    •	 Inspect casings for signs of casing flange slippage.
    Comprehensive inspection and maintenance guidelines have been 
    developed by GE and are provided in the O&M Manual to assist 
    users in performing each of the inspections previously described.
    Parts Planning
    Prior to a scheduled disassembly inspection, adequate spares 
    should be on-site. Lack of adequate on-site spares can have   
    a major effect on plant availability. For example, a planned   
    outage such as a combustion inspection, which should only   
    take two to five days, could take weeks if adequate spares are   
    not on-site. GE will provide recommendations regarding the   
    types and quantities of spare parts needed; however, it is up   
    to the owner to purchase these spare parts on a planned basis 
    allowing adequate lead times.
    Early identification of spare parts requirements ensures their 
    availability at the time the planned inspections are performed. 
    Refer to the Reference Drawing Manual provided as part of the 
    comprehensive set of O&M Manuals to aid in identification and 
    ordering of gas turbine parts.
    Additional benefits available from the renewal parts catalog   
    data system are the capability to prepare recommended spare 
    parts lists for the combustion, hot gas path and major inspections 
    as well as capital and operational spares.
    Estimated repair and replacement intervals for some of the   
    major components are shown in Appendix D . These tables assume 
    that operation, inspections, and repairs of the unit have been   
    done in accordance with all of the manufacturer’s specifications 
    and instructions. The actual repair and replacement intervals for any particular 
    gas turbine should be based on the user’s operating procedures, 
    experience, maintenance practices, and repair practices. The 
    maintenance factors previously described can have a major effect 
    on both the component repair interval and service life. For this 
    reason, the intervals given in Appendix D
     should only be used 
    as guidelines and not certainties for long range parts planning. 
    Owners may want to include contingencies in their parts planning.
    The estimated repair and replacement interval values reflect 
    current production hardware (the typical case) with design 
    improvements such as advanced coatings and cooling technology. 
    With earlier production hardware, some of these lives may not be 
    achievable. Operating factors and experience gained during the 
    course of recommended inspection and maintenance procedures 
    will be a more accurate predictor of the actual intervals.
    The estimated repair and replacement intervals are based on 
    the recommended inspection intervals shown in Figure 39 . For 
    certain models, technology upgrades are available that extend the 
    maintenance inspection intervals. The application of inspection (or 
    repair) intervals other than those shown in Figure 39  can result in 
    different replacement intervals than those shown in Appendix D . 
    See your GE service representative for details on a specific system. 
    It should be recognized that, in some cases, the service life of a 
    component is reached when it is no longer economical to repair 
    any deterioration as opposed to replacing at a fixed interval. This 
    is illustrated in Figure 38  for a first stage nozzle, where repairs 
    continue until either the nozzle cannot be restored to minimum 
    acceptance standards or the repair cost exceeds or approaches 
    the replacement cost. In other cases, such as first-stage buckets, 
    repair options are limited by factors such as irreversible material 
    damage. In both cases, users should follow GE recommendations 
    regarding replacement or repair of these components.
    It should also be recognized that the life consumption of any one 
    individual part within a parts set can have variations. This may 
    lead to a certain percentage of “fallout,” or scrap, of parts being 
    repaired. Those parts that fallout during the repair process will 
    need to be replaced by new parts. Parts fallout will vary based on 
    the unit operating environment history, the specific part design, 
    and the current repair technology. 
    						
    							29
    Operating Hours
    Nozzle Construction
    Severe Deterioration
    10,00020,00030,00040,00050,00060,00070,00080,000
    New Nozzle
    Acceptance Standards
    Repaired Nozzle
    Min. Acceptance 
    Standard 1st
    Repair
    2nd
    Repair
    3rd
    Repair
    Repair Cost ExceedsReplacement CostWithout Repair
    Figure 38 .  First-stage nozzle repair program: natural  gas fired – continuous dry – base load
    Type of InspectionType of 
    hours/
    starts
    Hours/Starts
    6B 
    7E  9E
    MS3002K MS50 01PA MS5002C, D6B
     .037E .0
    
    3
     (6)9E .03 (7)
    Combustion (Non-DLN)  Factored 12000/400 (3) 12000/800 (1)(3)(5) 12000/800 (1)(3)(5) 
    12000/600 (2)(5) 8000/900 (2)(5)  8000/900 (2)(5)
    Combustion (DLN) 
    Factored  8000/400 (3)(5) 8000/400 (3)(5) 12000/450 (5) 
    12000/450 (5)  12000/450 (5)
    Hot Gas Path 
    Factored 24000/1200 (4) 
    24000/1200 (4)(5) 24000/1200 (4)(5) 24000/1200 (5) 24000/1200 (5) 24000/900 (5)
    Major 
    Actual 48000/2400 
    48000/2400 (5) 48000/2400 (5) 
    48000/2400 (5) 48000/2400 (5) 48000/2400 (5)
    Type of Inspection  Type of 
    hours/
    starts
    Hours/Starts
    6F
    7F 9F
    6 F  .
    0
     3   7 F  .
    0
     3  7 F
     .
    0
     4  7FB
     .01
    
     9 F
     .
    0
     3  9 F
     .
    0
     5
    Combustion (Non-DLN)  Factored 8000/400
    Combustion (DLN)  Factored 12000/450 
    (5) 24000/900 
    32000/900 (5) 12000/450 
    24000/900  12000/450
    Hot Gas Path  Factored 24000/900  24000/900 
    32000/1250 24000/900 
    24000/900  24000/900
    Major  Actual 48000/2400  48000/2400 
    64000/2400 48000/2400 
    48000/2400  48000/2400
    Factors that can reduce 
    maintenance intervals:
    •	 Fuel
    •	 Load setting
    •	 Steam/water injection
    •	 Peak load firing
    operation
    •	 Tr i p s
    •	 Start cycle
    •	 Hardware design
    •	 Off-frequency operation 1.
    U
    
    nits with Lean Head End liners have a 400-starts combustion inspection
    interval.
    2.
    M
    
    ultiple Non-DLN configurations exist (Standard, MNQC, IGCC). The typical
    case is shown; however, different quoting limits may exist on a machine and
    hardware basis. Contact a GE service representative for further information.
    3.
    C
    
    ombustion inspection without transition piece removal. Combustion
    inspection with transition pieces removal to be performed every 2
    combustion inspection intervals.
    4.
    H
    
    ot gas path inspection for factored hours eliminated on units that operate
    on natural gas fuel without steam or water injection.
    5.
    U
    
    pgraded technology (Extendor*, PIP, DLN 2.6+, etc) may have longer
    inspection intervals.
    6.
    A
    
    lso applicable to 7121(EA) models.
    7.
    A
    
    pplicable to non-AGP units only.
    *Trademark of General Electric Company
    Note: 
    B
     aseline inspection intervals 
    reflect current production 
    hardware, unless otherwise 
    noted, and operation 
    in accordance with 
    manufacturer specifications. 
    They represent initial 
    recommended intervals in 
    the absence of operating 
    and condition experience.
    For Repair/Replace intervals 
    see  Appendix D .
    Figure 39 . Baseline recommended inspection intervals: base load – natural gas fuel – dry
    GE Power & Water | GER-3620M (00015001200140018
    )  
    						
    							30
    Inspection Intervals
    In the absence of operating experience and resulting part 
    conditions, Figure 39 lists the recommended combustion, hot   
    gas path and major inspection intervals for current production 
    GE turbines operating under typical conditions of natural gas fuel, 
    base load, and no water/steam injection. These recommended 
    intervals represent factored hours or starts calculated using 
    maintenance factors to account for application specific operating 
    conditions. Initially, recommended intervals are based on   
    the expected operation of a turbine at installation, but this   
    should be reviewed and adjusted as operating and maintenance 
    data are accumulated. While reductions in the recommended 
    intervals will result from the factors described previously or 
    unfavorable operating experience, increases in the recommended 
    intervals may also be considered where operating experience   
    has been favorable. 
    The condition of the combustion and hot gas path parts provides a 
    basis for customizing a program for inspection and maintenance. 
    The condition of the compressor and bearing assemblies is the   
    key driver in planning a major inspection. Historical operation   
    and machine conditions can be used to tailor maintenance 
    programs such as optimized repair and inspection criteria to 
    specific sites/machines. GE leverages these principles and 
    accumulated site and fleet experience in a “Condition Based 
    Maintenance” program as the basis for maintenance of units 
    under Contractual Service Agreements. This experience was 
    accumulated on units that operate with GE approved repairs, 
    field services, monitoring, and full compliance to GE’s technical 
    recommendations.
    GE can assist operators in determining the appropriate 
    maintenance intervals for their particular application. Equations 
    have been developed that account for the factors described earlier 
    and can be used to determine application-specific combustion,   
    hot gas path, and major inspection intervals.
    Borescope Inspection Interval
    In addition to the planned maintenance intervals, which   
    undertake scheduled inspections or component repairs or 
    replacements, borescope inspections should be conducted to 
    identify any additional actions, as discussed in the sections   “Gas Turbine Design Maintenance Features.” Such inspections 
     
    may identify additional areas to be addressed at a future 
    scheduled maintenance outage, assist with parts or resource 
    planning, or indicate the need to change the timing of a future 
    outage. The BI should use all the available access points to verify 
    the condition of the internal hardware. As much of the Major 
    Inspection workscope as possible should be done using this visual 
    inspection without dissassembly. Refer to Figure 4  for standard 
    recommended BI frequency. Specific concerns may warrant 
    subsequent BIs in order to operate the unit to the next scheduled 
    outage without teardown.
    Combustion Inspection Interval
    Equations have been developed that account for the earlier 
    mentioned factors affecting combustion maintenance intervals. 
    These equations represent a generic set of maintenance factors 
    that provide guidance on maintenance planning. As such, these 
    equations do not represent the specific capability of any given 
    combustion system. For combustion parts, the baseline operating 
    conditions that result in a maintenance factor of one are normal 
    fired startup and shutdown (no trip) to base load on natural gas 
    fuel without steam or water injection.
    An hours-based combustion maintenance factor can be determined 
    from the equations given in Figure 40  as the ratio of factored hours 
    to actual operating hours. Factored hours considers the effects of 
    fuel type, load setting, and steam/water injection. Maintenance 
    factors greater than one reduce recommended combustion 
    inspection intervals from those shown in Figure 39  representing 
    baseline operating conditions. To obtain a recommended 
    inspection interval for a specific application, the maintenance 
    factor is divided into the recommended baseline inspection interval.
    A starts-based combustion maintenance factor can be determined 
    from the equations given in Figure 41  and considers the effect of 
    fuel type, load setting, peaking-fast starts, trips, and steam/water 
    injection. An application-specific recommended inspection interval 
    can be determined from the baseline inspection interval in Figure 39  
    and the maintenance factor from Figure 41 . Appendix B  shows six 
    example maintenance factor calculations using the above hours 
    and starts maintenance factor equations. 
    						
    							31
    Figure 40 . Combustion inspection hours-based maintenance factors
    Syngas units require unit-specific intervals to account for unit-
    specific fuel constituents and water/steam injection schedules.   
    As such, the combustion inspection interval equations may not 
    apply to those units. 
    Hours-Based Combustion Inspection 
    Where:
    i   = Discrete Operating mode (or Operating Practice   
        of Time Interval)
    t
    i  =  Operating hours at Load in a Given Operating mode
    Ap
    i  =  Load Severity factor
        Ap  =  1.0 up to Base Load
        Ap  =  For Peak Load Factor See Figure 11
    Af
    i   =   Fuel Severity Factor
        Af = 1.0 for Natural Gas Fuel
     (1)
       Af = 1.5 for Distillate Fuel, Non-DLN (2.5 for DLN)
        Af = 2.5 for Crude (Non-DLN)
        Af = 3.5 for Residual (Non-DLN)
    K
    i   =   Water/Steam Injection Severity Factor
        (% Steam Referenced to Compressor Inlet Air Flow,   
        w/f = Water to Fuel Ratio)
        K  =  Max(1.0, exp(0.34(%Steam – 2.00%)))   
            for Steam, Dry Control Curve
        K  =  Max(1.0, exp(0.34(%Steam – 1.00%)))   
            for Steam, Wet Control Curve
        K  =  Max(1.0, exp(1.80(w/f – 0.80)))   
            for Water, Dry Control Curve
        K  =  Max(1.0, exp(1.80(w/f – 0.40)))   
            for Water, Wet Control Curve
    (1)  Af = 10 for DLN 1/DLN 1+ extended lean-lean, and DLN 2.0/ DLN 2+ 
    extended piloted premixed operating modes.
    Maintenance Factor = Factored Hours 
    Actual Hours 
    Factored Hours =  (Ki · Afi · Api · ti ), i = 1 to n in Operating Modes 
    Actual Hours =  (ti ), i = 1 to n in Operating Modes 
     Maintenance  Interval   =  
    Baseline CI (Figure 39)  
          Maintenance Factor
    Figure 41 . Combustion inspection starts-based maintenance factors
    Starts-Based Combustion Inspection 
    Where:
    i  = Discrete Start/Stop Cycle (or Operating Practice)
    N
    i   =   Start/Stop Cycles in a Given Operating Mode
    As
    i  =   Start Type Severity Factor
        As  =  1.0 for Normal Start
        As  =  For Peaking-Fast Start See Figure 14
    Ap
    i   =   Load Severity Factor
        Ap  =  1.0 up to Base Load
        Ap  =  exp (0.009 x Peak Firing Temp Adder in °F)   
            for Peak Load
    At
    i   =   Trip Severity Factor
        At  =  0.5 + exp(0.0125*%Load) for Trip
        At  =  1 for No Trip
    Af
    i   =   Fuel Severity Factor
        Af  =  1.0 for Natural Gas Fuel
        Af  =  1.25 for Non-DLN (or 1.5 for DLN) for Distillate Fuel
        Af  =  2.0 for Crude (Non-DLN)
        Af  =  3.0 for Residual (Non-DLN)
    K
    i   =   Water/Steam Injection Severity Factor
        (% Steam Referenced to Compressor Inlet Air Flow,   
        w/f = Water to Fuel Ratio)
        K  =  Max(1.0, exp(0.34(%Steam – 1.00%)))   
            for Steam, Dry Control Curve
        K  =  Max(1.0, exp(0.34(%Steam – 0.50%)))   
            for Steam, Wet Control Curve
        K  =  Max(1.0, exp(1.80(w/f – 0.40)))   
            for Water, Dry Control Curve
        K  =  Max(1.0, exp(1.80(w/f – 0.20)))   
            for Water, Wet Control Curve
    Maintenance Factor = Factored Star ts 
    Actual Star ts 
    Factor ed Star ts =  (Ki · Afi · Ati · Api · Asi · Ni ), i = 1 to n Star t/Stop Cycles
    Actual Starts =  (Ni ), i = 1 to n in Star t/Stop Cycles
     Maintenance  Interval   =  
    Baseline CI (Figure 39)  
          Maintenance Factor
    GE Power & Water | GER-3620M (00015001200140018
    )  
    						
    							32
    Hot Gas Path Inspection Interval
    The hours-based hot gas path criterion is determined from the 
    equations given in Figure 42. With these equations, a maintenance 
    factor is determined that is the ratio of factored operating hours 
    and actual operating hours. The factored hours consider the 
    specifics of the duty cycle relating to fuel type, load setting and 
    steam or water injection. Maintenance factors greater than one 
    reduce the hot gas path inspection interval from the baseline 
    (typically 24,000 hour) case. To determine the application specific 
    maintenance interval, the maintenance factor is divided into the 
    baseline hot gas path inspection interval, as shown in Figure 42 .The starts-based hot gas path criterion is determined from the 
    equations given in Figure 43
    . 
    As previously described, the limiting criterion (hours or starts) 
    determines the maintenance interval. Examples of these equations 
    are in Appendix A .
    Rotor Inspection Interval
    Like hot gas path components, the unit rotor has a maintenance 
    interval involving removal, disassembly, and inspection. This 
    interval indicates the serviceable life of the rotor and is generally 
    considered to be the teardown inspection and repair/replacement 
    interval for the rotor. The disassembly inspection is usually 
    concurrent with a hot gas path or major inspection; however, 
    it should be noted that the maintenance factors for rotor 
    maintenance intervals are distinct from those of combustion and 
    hot gas path components. As such, the calculation of consumed 
    life on the rotor may vary from that of combustion and hot gas 
    path components. Customers should contact GE when their rotor is 
    approaching the end of its serviceable life for technical advisement.
    Hours-Based HGP Inspection 
    i 
     
    =
      
    1 to n d
     iscrete operating modes (or operating practices 
    of
    
     time interval)
    t
    i  =   Fired hours in a given operating mode
    Ap
    i  =  Load severity factor for given operating mode
    A
    
    p  
     =
      
    1
     .0 up to base load
    A
    
    p  
     =
      
    F
     or peak load factor see Figure 11 .
    Af
    i  =  Fuel severity factor for given operating mode
    A
    
    f   
    =
      
    1
     .0 for natural gas
    A
    
    f   
    = 
      
    1
     .5 for distillate  
     
    (
     =1.0 when Ap > 1, at minimum Af ∙ Ap = 1.5)
    A
    
    f   
    = 
      
    2 to 3 f
     or crude
    A
    
    f   
    = 
      
    3 to 4 f
     or residual
    S
    i  =   Water/steam injection severity factor = Ki + (Mi ∙ Ii)
    I
    
     
     = 
    
     
    P
    
    ercent water/steam injection referenced 
     
    to c
    
    ompressor inlet air flow
    M
    
    &K 
     
    = 
    
     
    W
    
    ater/steam injection constants
    M K Control Water/Steam Inj  .S2N/S3N Material
    0 1 Dry 2.2%Non-FSX-414
    0.18 0.6 Dry >2.2%FSX-414
    0.18 1 Wet >0%Non-FSX-414
    0.55 1 Wet >0%FSX-414
    Maintenance Factor = Factored Hours 
    Actual Hours 
    Factored Hours = ni=1 (Si · Afi · Api · ti ) 
    Actual Hours = ni=1 (ti ) 
     Maintenance Interval   =  B aseline HGPI (Figure 39) 
    (
    
    Hours)  
    M
     aintenance Factor
    Figure 42 . Hot gas path maintenance interval: hours-based criterion
    Starts-Based HGP Inspection
    Where:
    Actual Starts = (N
    A + NB + NP) 
    S
     
    =
    
     
    B
    
    aseline Starts-Based Maintenance Interval ( Figure 39)
    N
    A =  Annual Number of Part Load Start/Stop Cycles 
    (
    
    
    
    100% Load)
    P
    s =  Peaking-Fast Start Factor (See Figure 14 )
    F
     
    =
      
    A
     nnual Number of Peaking-Fast Starts
    T
     
    =
      
    A
     nnual Number of Trips
    a
    T =  Trip Severity Factor = f(Load) (See Figure 20 )
    n
     
    =
      
    N
     umber of Trip Categories (i.e. Full Load, Part Load, etc.)
    Maintenance Factor = Factored Star ts
    Actual Starts
    Factored Starts = 0.5NA + NB + 1.3NP + PsF + n i=1 (aTi – 1) Ti
    Figure 43 .  Hot gas path maintenance interval: starts-based criterion
     Maintenance  Interval   =  S 
    (S
    
    tarts)  
    M
     aintenance Factor 
    						
    							33
    Figure 44 describes the procedure to determine the hours-
    based maintenance criterion. Peak load operation is the primary 
    maintenance factor for the F-class rotor and will act to increase 
    the hours-based maintenance factor and to reduce the rotor 
    maintenance interval. For B/E-class units time on turning gear also 
    affects rotor life.
    The starts-based rotor maintenance interval is determined from the 
    equations given in Figure 45 . Adjustments to the rotor maintenance 
    interval are determined from rotor-based operating factors as 
    described previously. In the calculation for the starts-based rotor 
    maintenance interval, equivalent starts are determined for cold, 
    warm, and hot starts over a defined time period by multiplying 
    the appropriate cold, warm, and hot start operating factors by the 
    number of cold, warm, and hot starts respectively. Additionally, 
    equivalent starts for trips from load are added. The total equivalent 
    starts are divided by the actual number of starts to yield the  maintenance factor. The rotor starts-based maintenance interval 
    is determined by dividing the baseline rotor maintenance interval 
    of 5000 starts by the calculated maintenance factor. The baseline 
    rotor maintenance interval is also the maximum interval, since 
    calculated maintenance factors less than one are not considered.
    When the rotor reaches the earlier of the inspection intervals 
    described in Figures 44 and 45
    , an unstack of the rotor is required 
    so that a complete inspection of the rotor components in both 
    the compressor and turbine can be performed. It should be 
    expected that some rotor components will either have reached 
    the end of their serviceable life or will have a minimal amount of 
    residual life remaining and will require repair or replacement at this 
    inspection point. Depending on the extent of refurbishment and 
    part replacement, subsequent inspections may be required at a 
    reduced interval.
    Hours-Based Rotor Inspection
    H = Non-peak load operating hours
    P = Peak load operating hours
    T
    G = Hours on turning gear
    R = Baseline rotor inspection interval
    Machine
    F-class
    All other  R(3)
    144,000
    200,000
    (1)  Maintenance factor equation to be used unless otherwise notified in unit-
    specific documentation.
    (2) 
     
    T
     o diminish potential turning gear impact, major inspections must include 
    a thorough visual and dimensional examination of the hot gas path 
    turbine rotor dovetails for signs of wearing, galling, fretting, or cracking. 
    If no distress is found during inspection or after repairs are performed to 
    the dovetails, time on turning gear may be omitted from the hours-based 
    maintenance factor.
    (3) 
     
    B
     aseline rotor inspection intervals to be used unless otherwise notified in 
    unit-specific documentation.
    MF = Factored Hours
    Actual Hours
    MF for
    B/E-class= H + 2P(1)
    H + P= H + 2P + 2TG (2)
    H + P
    Figure 44 .
     Rotor maintenance interval: hours-based criterion
     Maintenance  Interval   =  R 
    (
    
    Hours)  
    M
     aintenance Factor
    Starts-Based Rotor Inspection
    For units with published start factors:
    For B/E-class units
    For all other units additional start factors may apply.
    Number of Starts
    Nh1 = Number of hot 1 starts
    N
    h2 =  Number of hot 2 starts
    N
    w1 =  Number of warm 1 starts
    N
    w2 =  Number of warm 2 starts
    N
    c =  Number of cold starts
    N
    t =  Number of trips from load
    N
    s =  Total number of fired starts
    Start Factors (2)
    Fh1 = Hot 1 start factor (down 0-1 hr)
    F
    h2 =  Hot 2 start factor (down 1-4 hr)
    F
    w1 =  Warm 1 start factor (down 4-20 hr)
    F
    w2 = Warm 2 start factor (down 20-40 hr)
    F
    c =  Cold start factor (down >40 hr)
    F
    t =  Trip from load factor
    (
    1) 
     
    B
    
    aseline rotor inspection interval is 5,000 fired starts unless otherwise 
    notified in unit-specific documentation.
    (2) 
     
    S
    
    tart factors for certain F-class units are tabulated in Figure 22 . For all 
    other machines, consult unit-specific documentation to determine if start 
    factors apply.
    Maintenance Factor = Factored Starts
    Actual Star ts
    MaintenanceFactor = 
    (Fh1 · Nh1 + Fh2 · Nh2 + Fw1 · Nw1 + Fw2 · Nw2 + Fc · Nc + Ft · Nt)
    (Nh1+Nh2+Nw1+Nw2+Nc )
    Maintenance Factor = NS + NT
    NS
    Figure 45 .
     Rotor maintenance interval: starts-based criterion
     Maintenance  Interval   =  5 ,000(1) 
    (S
    
    tarts)
     
    M
    
    aintenance Factor
    GE Power & Water | GER-3620M (00015001200140018
    )  
    						
    							34
    The baseline rotor life is predicated upon sound inspection results 
    at the major inspections. For F-class rotors the baseline intervals 
    are typically 144,000 hours and 5,000 starts. For rotors other than 
    F-class, the baseline intervals are typically 200,000 hours and 
    5,000 starts. Consult unit-specific documentation to determine if 
    alternate baseline intervals or maintenance factors may apply.
    Personnel Planning
    It is essential that personnel planning be conducted prior to an 
    outage. It should be understood that a wide range of experience, 
    productivity, and working conditions exist around the world. 
    However, an estimate can be made based upon maintenance 
    inspection labor assumptions, such as the use of a crew of  
    workers with trade skill (but not necessarily direct gas turbine 
    experience), with all needed tools and replacement parts (no   
    repair time) available. These estimated craft labor hours should 
    include controls/accessories and the generator. In addition to   
    the craft labor, additional resources are needed for technical 
    direction, specialized tooling, engineering reports, and site 
    mobilization/demobilization.
    Inspection frequencies and the amount of downtime varies   
    within the gas turbine fleet due to different duty cycles and the 
    economic need for a unit to be in a state of operational readiness. 
    Contact your local GE service representative for the estimated 
    labor hours and recommended crew size for your specific unit.
    Depending upon the extent of work to be done during each 
    maintenance task, a cooldown period of 4 to 24 hours may be 
    required before service may be performed. This time can be 
    utilized productively for job move-in, correct tagging and locking 
    equipment out-of-service, and general work preparations. At the 
    conclusion of the maintenance work and systems check out, a 
    turning gear time of two to eight hours is normally allocated prior 
    to starting the unit. This time can be used for job clean-up and 
    preparing for start.
    Local GE field service representatives are available to help plan 
    maintenance work to reduce downtime and labor costs. This 
    planned approach will outline the replacement parts that may be 
    needed and the projected work scope, showing which tasks can 
    be accomplished in parallel and which tasks must be sequential. 
    Planning techniques can be used to reduce maintenance cost by 
    optimizing lifting equipment schedules and labor requirements.  Precise estimates of the outage duration, resource requirements, 
    critical-path scheduling, recommended replacement parts, and 
    costs associated with the inspection of a specific installation may 
    be sourced from the local GE field services office.
    Conclusion
    GE heavy-duty gas turbines are designed to have high availability. 
    To achieve maximum gas turbine availability, an owner must 
    understand not only the equipment but also the factors affecting 
    it. This includes the training of operating and maintenance 
    personnel, following the manufacturer’s recommendations, regular 
    periodic inspections, and the stocking of spare parts for immediate 
    replacement. The recording and analysis of operating data is also 
    essential to preventative and planned maintenance. A key factor 
    in achieving this goal is a commitment by the owner to provide 
    effective outage management, to follow published maintenance 
    instructions, and to utilize the available service support facilities.
    It should be recognized that, while the manufacturer provides 
    general maintenance recommendations, it is the equipment 
    user who controls the maintenance and operation of equipment. 
    Inspection intervals for optimum turbine service are not fixed for 
    every installation but rather are developed based on operation 
    and experience. In addition, through application of a Contractual 
    Service Agreement to a particular turbine, GE can work with 
     
    a user to establish a maintenance program that may differ   
    from general recommendations but will be consistent with 
    contractual responsibilities.
    The level and quality of a rigorous maintenance program have a 
    direct effect on equipment reliability and availability. Therefore, 
    a rigorous maintenance program that reduces costs and outage 
    time while improving reliability and earning ability is the optimum 
    GE gas turbine user solution. 
    						
    							35
    References
    Jarvis, G., “Maintenance of Industrial Gas Turbines,” GE Gas Turbine 
    State of the Art Engineering Seminar, paper SOA-24-72, June 1972.
    Patterson, J. R., “Heavy-Duty Gas Turbine Maintenance Practices,” 
    GE Gas Turbine Reference Library, GER-2498, June 1977.
    Moore, W. J., Patterson, J.R, and Reeves, E.F., “Heavy-Duty Gas 
    Turbine Maintenance Planning and Scheduling,” GE Gas Turbine 
    Reference Library, GER-2498; June 1977, GER 2498A, June 1979.
    Carlstrom, L. A., et al., “The Operation and Maintenance of General 
    Electric Gas Turbines,” numerous maintenance articles/authors 
    reprinted from Power Engineering magazine, General Electric 
    Publication, GER-3148; December 1978.
    Knorr, R. H., and Reeves, E. F., “Heavy-Duty Gas Turbine 
    Maintenance Practices,” GE Gas Turbine Reference Library, GER-
    3412; October 1983; GER- 3412A, September 1984; and GER-3412B, 
    December 1985.
    Freeman, Alan, “Gas Turbine Advance Maintenance Planning,” 
    paper presented at Frontiers of Power, conference, Oklahoma State 
    University, October 1987.
    Hopkins, J. P, and Osswald, R. F., “Evolution of the Design, 
    Maintenance and Availability of a Large Heavy-Duty Gas Turbine,” 
    GE Gas Turbine Reference Library, GER-3544, February 1988 (never 
    printed).
    Freeman, M. A., and Walsh, E. J., “Heavy-Duty Gas Turbine 
    Operating and Maintenance Considerations,” GE Gas Turbine 
    Reference Library, GER-3620A.
    GEI-41040, “Fuel Gases for Combustion in Heavy-Duty Gas 
    Tu r b i n e s .”
    GEI-41047, “Gas Turbine Liquid Fuel Specifications.”
    GEK-101944, “Requirements for Water/Steam Purity in Gas 
    Tu r b i n e s .”
    GER-3419A, “Gas Turbine Inlet Air Treatment.”
    GER-3569F, “Advanced Gas Turbine Materials and Coatings.”
    GEK-32568, “Lubricating Oil Recommendations for Gas Turbines 
    with Bearing Ambients Above 500°F (260°C).”
    GEK-110483, “Cleanliness Requirements for Power Plant Installation, 
    Commissioning and Maintenance.”
    GE Power & Water | GER-3620M (00015001200140018
    )  
    						
    							36
    Appendix
    A .1) Example 1 – Hot Gas Path Maintenance 
    Interval Calculation
    A 7E.03 user has accumulated operating data since the last hot  
    gas path inspection and would like to estimate when the next   
    one should be scheduled. The user is aware from GE publications 
    that the baseline HGP interval is 24,000 hours if operating on 
    natural gas, with no water or steam injection, and at base load.   
    It is also understood that the baseline starts interval is 1200,   
    based on normal startups, no trips, no peaking-fast starts. The 
    actual operation of the unit since the last hot gas path inspection 
    is much different from the baseline case. The unit operates in four 
    different operating modes:
    1.
    T
    
    he unit runs 3200 hrs/yr in its first operating mode, which is
    natural gas at base or part load with no steam/water injection.
    2.
    T
    
    he unit runs 350 hrs/yr in its second operating mode, which is
    distillate fuel at base or part load with no steam/water injection.
    3.
    T
    
    he unit runs 120 hrs/yr in its third operating mode, which is
    natural gas at peak load (+100°F) with no steam/water injection.
    4.
    T
    
    he unit runs 20 hrs/yr in its fourth operating mode, which is
    natural gas at base load with 2.4% steam injection on a wet
    control curve.
    The hours-based hot gas path maintenance interval parameters 
    for these four operating modes are summarized below:
    Operating Mode (i)
    1 2 34
    Fired hours (hrs/yr) t 3200 350 120 20
    Fuel severity factor Af 1 1.5 1 1
    Load severity factor Ap 1 1 [e 
    (0.018*100)] = 61
    Steam/water injection rate (%) I 0 00 2.4
    For this particular unit, the second- and third-stage nozzles are 
    FSX-414 material. From Figure 42 , at a steam injection rate of 2.4% 
    on a wet control curve, 
    M
    4 = 0.55, K4 = 1
    The steam severity factor for mode 4 is therefore, = S
    4 = K4 + (M4 ∙ I4) = 1 + (0.55 ∙ 2.4) = 2.3
    At a steam injection rate of 0%, M = 0, K = 1 Therefore, the steam severity factor for modes 1, 2, and 3 are
    = S
    1 = S2 = S3 = K + (M ∙ I) = 1
    From the hours-based criteria, the maintenance factor is 
    determined from Figure 42 .
    MF = 1.22
    The hours-based adjusted inspection interval is therefore, Adjusted Inspection Interval = 24,000/1.22 = 19,700 hours
    [Note, since total annual operating hours is 3690, the estimated 
    time to reach 19,700 hours is 19,700/3690 = 5.3 years.]
    Also, since the last hot gas path inspection the unit has averaged 
    145 normal start-stop cycles per year, 5 peaking-fast start cycles 
    per year, and 20 base load cycles ending in trips (a
    T = 8) per year. 
    The starts-based hot gas path maintenance interval parameters 
    for this unit are summarized below:
    Normal  cycles Peaking 
    starts, °F Cycles ending 
    in trip, T Total
    Part load cycles, N
    A40 0040
    Base load cycles, N
    B100 520125
    Peak load cycles, N
    P5 005
    From the starts-based criteria, the maintenance factor is 
    determined from Figure 43 .
    MF = 1.8
    The adjusted inspection interval based on starts is Adjusted Inspection Interval = 1200/1.8 = 667 starts
    [Note, since the total annual number of starts is 170, the estimated 
    time to reach 667 starts is 667/170 = 3.9 years.]
    In this case the unit would reach the starts-based hot gas path 
    interval prior to reaching the hours-based hot gas path interval. 
    The hot gas path inspection interval for this unit is therefore 667 
    starts (or 3.9 years).
    MF = n i=1 (Si · Afi · Api · ti ) 
    
    n i=1) (ti ) 
    = (1 · 1 · 1 · 3200) + (1 · 1.5 · 1 · 350) + (1 ·\
     1 · 6 · 120) + (2.3 · 1 · 1 · 20)
    (3200 + 350 + 120 + 20)
    MF = 0.5NA + NB + 1.3NP + PsF + ni=1 (aTi - 1) Ti 
    NA + NB + NP
    MF = 0.5 (40) + 125 + 1.3 (5) + 3.5 (5) + (8 - 1 )20
    40 + 125 + 5 
    						
    All GE manuals Comments (0)