Installation, Service, and Troubleshooting Instructions PART NO. 33CSZC--01AND33CSZC--PI CONTENTS Page GENERAL................................. 2 INSTALLATION............................ 2-4 Zone Controller Placement................. 2 Wiring Requirements...................... 2 Damper Circuit Board Installation.......... 2 Wiring Connections........................ 2 Indoor-Air Quality (IAQ) Sensor Installation....................... 3 Provide Power To Damper Circuit Board.... 4...
Page 2
GENERAL The zone controller operates in a VVTtsystem. The VVT system allows a single-zone heating/cooling unit to operate as a multiple-zone system. The conditioned space is divided into occupied zones. Each occupied zone is monitored by a zone controller. The zone controller regulates the amount of conditioned air entering a zone through the control of a supply- air damper. Air¯ow to each zone is controlled individually by each zone controller. Each zone controller communicates with the monitor ther-...
Page 3
Electric shock can cause injury or death. Ensure power to the transformer has been disconnected before wiring. WIRE NETWORK TO ZONE CONTROLLER Ð Connect the black, red, and green wires from the network cable to the terminals on the zone controller wiring connector board. WIRE SENSORS TO DAMPER BOARD Ð The damper board sensor wiring bundle contains the wires required to connect the sensors. See Fig. 3. Wire nut the pressure sensor to the WHT, BLU, and GRN wires in the larger wiring bundle. The other wires...
Page 4
LOCAL MODE IAQ WIRING Ð Wire the dry contact relay output from the sensor (connections 3 and 4) to the red and black wires of the O section of the ®eld-supplied pressure sensor harness of the zone controller damper. A pres- sure sensor harness is supplied with a pressure sensor for use with the bypass damper. Recommended gage of wire is 14, stranded. Wire the 2 wires from the isolated 24 vac power supply to the power input side of the sensor (connections 1 and 5). Recommended gage of wire is 14,...
Page 5
left set point buttons are used to change the data values. When the desired setting is shown press the select button to store the change. To exit without saving changes, press both upper or both lower set point buttons or press the escape button. If no buttons are pressed while in programming mode for 4 minutes, the zone controller will reset back to the sys- tem status display. Each option is discussed in detail in this manual. Refer to the correct section for more information. NOTE: Occupancy schedule...
Page 6
Table 1 Ð VVTTZone Controller Categories and Options OPTION DESCRIPTION DEFAULT MINIMUM MAXIMUM CATEGORY 1.0 SET POINTS 1.1Cooling Set Point Low Limit (F) 68 50 99 1.2Heating Set Point High Limit (F) 75 50 99 1.3Unoccupied Cooling Set Point (F) 80 50 99 1.4Unoccupied Heating Set Point (F) 65 40 99 1.5Rotating Display OFF OFF ON 1.6Fahrenheit Temperature Display ON OFF ON CATEGORY 2.0 OCCUPANCY SCHEDULE 2.1-2.8Occupancy Period 1-8 Days Active Start Time Stop TimeMTWTF 6:00 AM 6:00 PMNONE 12:00 AM 12:00...
Page 7
Table 1 Ð VVTTZone Controller Categories and Options (cont) OPTION DESCRIPTION DEFAULT MINIMUM MAXIMUM CATEGORY 10.0 HOLIDAY SCHEDULES 10.1-10.18Holiday Schedule 1-18 Holiday Start Month Start Day Duration (Days)0 0 00 0 012 31 99 CATEGORY 11.0 ALARM 11.1Equipment Priority 7 0 9 11.2Communication Failure Retry Time (Minutes) 10 0 (Disabled) 240 11.3Re-Alarm Time (Minutes) 30 1 255 CATEGORY 12.0 OPTIMAL START No con®guration required by zone controller. CATEGORY 13.0 LOADSHED No con®guration required by...
Page 8
maintained in the zone controlled by the zone controller dur- ing the occupied mode. The range of allowable temperatures is 50 to 99 F for heating and cooling (dependent on the occupied set point limits). The left set point buttons control the cooling set point. Press the top set point button to raise the set point. Press the bottom set point button to lower the set point. The cooling set point is displayed in the top left corner of the zone con- troller screen. The right set point buttons control the...
Page 9
Instead of showing option 2, the screen will display the active days for the occupied schedule. Each occupied sched- ule (options 2.1 through 2.8) will have three different screens associated with it Ð start time, stop time, and active days. Start Time Ð When the select button is pressed from the ®rst option screen, the hours number will ¯ash. The hours are modi®ed through the left set point buttons. The AM/PM modi®er will automatically switch when scrolling through the times. To change the minutes,...
Page 10
Remote Room Temperature Sensor ÐThe zone controller measures zone temperature through a solid-state temperature sensor located at a remote location up to 1000 ft from the zone controller. The sensor measures tem- perature with a range of 30 to 180 F in 1/10 degree incre- ments. The remote room temperature sensor is connected to the zone controller through the wiring connector board. See Fig. 7. Up to 4 remote room sensors can be used. When more than 1 remote room sensor is used, the temperatures are...