Carrier Airaaxcc20a Owners Manual
Here you can view all the pages of manual Carrier Airaaxcc20a Owners Manual. The Carrier manuals for Air Cleaner are available online for free. You can easily download all the documents as PDF.
Page 1
AIRA Electronic Air Cleaner Installation, Start-Up, and Operating Instructions NOTE:Read the entire instruction manual before starting the installation. TABLE OF CONTENTS Page SAFETY CONSIDERATIONS...................................................1 INTRODUCTION.....................................................................1-2 PLANNING AN INSTALLATION........................................2-3 · Application...................................................................................2 ·...
Page 2
Prefiltered air then passes through a 2-stage electric cleaner. In the first stage, all airborne particles, even submicron size, are electri- cally charged (positive) as they pass through the ionizer. The ionizer field is setup by a corona discharge emanating from fine, tightly strung wires suspended between 2 adjacent flat plates. In the second stage, charged particles pass into an intense electrical field established between alternately charged and grounded paral- lel plates. Here positively charged...
Page 3
Step 4ÐHumidifiers An evaporative humidifier can be mounted upstream of air cleaner. It is best to install atomizing humidifier downstream of air cleaner because hard water salt deposits and water droplets may damage air cleaner. If an atomizing humidifier must be mounted upstream of air cleaner: 1. Mount it as far upstream as possible. (Recommend at least 6 ft.) 2. Install standard disposable furnace filter between humidifier and air cleaner to trap water droplets and hard water salts. Select location...
Page 4
Fig. 4ÐTransition Fitting Installation A97057 AIR CLEANER OPENING MAXIMUM 4 DROP PER LINEAL FOOT FURNACE OPENING AIR FLOW FURNACE AIR CLEANER AIR FLOW20¡ TRANSITION SECTION Fig. 5ÐTurning Vanes Installation A97058 TURNING VANES Fig. 6ÐDimensional DrawingDimensions (In.) MODELABCDEF AIRAAXCC001420-1/2 13-7/8 16-1/4 22-1/2 25 7-1/4 AIRAAXCC002024-1/2 17-7/8 20-1/4 22-1/2 25 7-1/4 A97059 4 1⁄2²20 3⁄4² A F E C 3 1⁄2² 2 3⁄8² 2 1⁄8² 30¡ 5⁄8² 3⁄16² B D 4
Page 5
Cabinets will support a maximum weight of 400 lb when installed beneath a vertical furnace or air-handling unit. When setting furnace on cabinet, do not drop it into place. Position furnace correctly on cabinet to prevent a corner from slipping down and damaging cabinet. Prior to installing this product: 1. Read rules and instructions carefully for safe operation. Failure to follow them could damage product or cause hazardous condition. 2. Check ratings given on product to make sure it is suitable for...
Page 6
Fig. 11ÐSide Installation on Upflow Furnace Side installation. Cleaner is mounted vertically, where return air enters side inlet of furnace. A97064 AIR FLOW Fig. 9ÐBasement Furnace Mounted horizontally in return plenum just above furnace. A97062 AIR FLOW Fig. 12ÐOffset Installation If there is less than 7-in. for mounting air cleaner between duct and furnace, move return-air drop. A97065 AIR FLOW Fig. 10ÐDownflow Furnace Mounted horizontally in return duct or plenum just above furnace. A97063 AIR FLOW 6
Page 7
The following procedures will expose electrical components. Disconnect power between checks and proceed carefully. Electrical shock can cause injury or death. The air cleaner is powered by providing 120v, 60 Hz, 1-phase electrical service to pigtail leads at field wiring compartment (with knock-out holes) located at rear of power pack assembly. (See Fig. 15.) 1. Turn air cleaner off using ON/OFF rocker switch located on front panel. 2. Remove power supply cover plate by removing front door and 2 screws...
Page 8
1. Both input indicating light (green) and output voltage light (red) should now be on. 2. Check to assure that both lights go out when the cell access panel is removed, when rocker switch is switched to OFF position, and when system blower is not running. MAINTENANCE Sharp edges. Handle the cells carefully to avoid cuts from the sharp metal edges. Step 1ÐWashing Cells and Prefilters Regular washing is necessary to insure proper performance. A thorough washing every 2 months will be adequate for most...
Page 9
· Fluke No. 8021B multimeter or equivalent · Fluke No. 80K-40 high-voltage probe or equivalent. Step 2ÐIndication of Electrical Trouble Air cleaner is equipped with input power LED light (green) and output voltage LED light (red) for indicating proper unit operation. When unit is in normal operation, system blower running, access door in place, control switch in the ON position, and indicating lights go out, there is an electrical problem. If green light goes out there is a problem in the primary...
Page 10
If space between charged and grounded plates is bridged with conductive or semi-conductive material, a short circuit devel- ops. The bridging or short may be caused by damaged plates or foreign material lodged between or on plates. Since cell is periodically removed from unit to wash away collected dirt, it is susceptible to physical damage. Also, cell contains ionizing wires which, due to their function, have to be designed with minimal structural support and are susceptible to breakage. However,...