Home > Anaheim > Stepper > Anaheim Stepper DPD72451 Users Guide

Anaheim Stepper DPD72451 Users Guide

    Download as PDF Print this page Share this page

    Have a look at the manual Anaheim Stepper DPD72451 Users Guide online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 523 Anaheim manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							1920 FIGURE  9 AA1754 - QUAD BOARD COUNTERThe selection of the switch banks is done by switching select lines 1 and 2 on
    The quad board module is a 4-bank version of the clickpot module with eachconnector P3.  The select lines are low true meaning that if a select line is
    bank having 6 decades.  The user can dial in four different move lengthspulled low (to 0Vdc), it is recognized as being on or true.  When a select
    and then select any one of them as desired.  The module is connected to theline is not pulled low it is internally pulled up to +5Vdc and is off or false. indexer via a supplied 5-lead cable. The bank select lines must be set at least 1 millisecond before the Index
    CONNECTORPin 1Pin 2Pin 3Pin 4Pin 5Pin 6
    P1 (To Indexer)Common+5VdcClockResetKey0Vdc
    P2 (Expansion)Common+5VdcClockResetKey0Vdc
    P3 (Select         Select #1Select #2Select #4Key+5Vdc0Vdc
    Inputs)command is given.  The select lines must remain in the set state until the
    index is complete.  Once the move is finished, the select lines may be
    changed as needed.
    BANK SELECT TABLESELECTLINE
    #1#2
    SWITCH BANK #100
    SWITCH BANK #210
    SWITCH BANK #301
    SWITCH BANK #411
    0=LOW (0-0.8Vdc), 1=HIGH(3.5-5Vdc)
    Select line #4 is only used if additional count input devices are
    daisychained to the expansion connector (P2).  If select line #4 is low, that
    quad board is ignored and the count input device connected to the P2
    expansion connector is read.  This allows multiple quad boards to be used
    together.  The daisychained count input device does not have to be a quad
    board; it could be a thumbwheel switch or click pot module. 
    						
    							2122 FIGURE 10 AA2210 BCD COUNTER MODULE
    The AA2210 BCD counter interface module enables the user to select any
    move length from 0 to 999,999 steps using a standard PLC (programmable
    logic controller).   Selecting the proper inputs creates a count value in steps,
    resulting in a move distance.  The module is connected to the indexer via a
    supplied 5-lead cable.
    Note:  All Inputs are active low (0-0.8Vdc).  All unused inputs may be ignored 
                 since they are pulled up.
    Example:  For a move distance of 1234 steps the following inputs should be   
                       pulled low.
    1s Decade: Bit 4 (TB1, pin 4)
    10s Decade: Bit 1 and 2 (TB2, pin 2 and 3)
    100s Decade: Bit 2 (TB1, pin 7)
    1000s Decade: Bit 1 (TB2, pin 6)
    All Other inputs must be open or high (3.5-5Vdc).FIGURE 11:  Dimensions SPECIFICATIONS
    Power Requirements: The standard 115VAC version can accept power
    inputs ranging from 105VAC to 125VAC 50-60Hz. 
    See Figure 14 for configurations with the X250A
    version.
    Ambient Temperature:0 to 50 degrees Celsius
    Shipping Weight:12 pounds
    BLD72 DRIVER:Control Inputs:TTL-MOS Compatible
    Logic 0: 0 to 0.8 Vdc
    Logic 1: 3.5 to 5 Vdc
    All Inputs are pulled up; No connection= logic 1.
    Half-step/Full-step:Logic 1 - Half-step
    (Terminal 8)Logic 0 - Full-step
    Motor Power On/Off:Logic 1 - Motor energized
    (Terminal 9)Logic  0 - Motor de-energized 
    						
    							CMOS+5VDC
    INPUT1K
    10K
    220pF115 VAC HOOKUP
    100 VAC HOOKUP130 VAC HOOKUP
    245 VAC HOOKUP 230 VAC HOOKUP 215 VAC HOOKUP 110 VAC MAX
    100 VAC NOM
    90 VAC MIN125 VAC MAX
    115 VAC NOM
    105 VAC MIN140 VAC MAX
    130 VAC NOM
    120 VAC MIN235 VAC MAX
    215 VAC NOM
    195 VAC MIN250 VAC MAX
    230 VAC NOM
    210 VAC MIN265 VAC MAX
    245 VAC NOM
    225 VAC MIN2324 Reset Fault:Logic 1 - Driver enabled and Fault detection
    enabled
    (Terminal 4)Logic 0 - Resets a Fault condition (driver is
    disabled when this input is low).  This input must be
    held low for at least 100ms.
    Output Current:7.0 Amperes continues maximum
    MANUAL PRESET INDEXER BOARD:Control Inputs:TTL-MOS Compatible
    Logic 0: 0 to 0.8 Vdc
    Logic 1: 3.5 to 5 Vdc
    All Input Terminals are pulled up
    to +5Vdc through 1k ohm
    resistors.
    Busy and Complete Outputs (pins 16 and 20) are open collector outputs that
    can sink 500mA and stand-off 40Vdc maximum (no sourcing).  Pull-up
    resistors may be jumpered to these outputs to produce TTL level signals (see
    section on jumpers).  
    Ground (pin 18) - 0Vdc
    +5Vdc Output (TB2, pin 1) - Up to 250mA is available for the user to power
    up external circuitry.  The total current drawn from pin 1 and pin 2 must not
    exceed 250mA.
    +12Vdc Unregulated Output (TB2, pin 2) - Up to 250mA is available for the
    user to power up external circuitry.  The total current drawn from pin 1 and
    pin 2 must not exceed 1.0A.
    FIGURE 12:  POWER HOOKUP DIAGRAM FOR DPD72451X250AX250A VERSION
    The DPD72451X250A can be configured to accept nominal power inputs of
    100VAC, 115VAC, 130VAC, 215VAC, 230VAC, and 245VAC.  See figure 14. 
    						
    							25 TROUBLESHOOTING DRIVER FAULTS
    If a Fault occurs, reset the Fault by applying a logic “0 to the Reset Fault
    Input (terminal 4) for at least 100ms (or by cycling power OFF for at least 15
    seconds).  After resetting, try to run the motor again.  If the driver faults again
    then check the conditions listed below.
    Is the LED blinking Slowly?
    This indicates that the motor has a phase shorted or there is a short in the
    motor cable or wiring.  Check the motor and the wiring for shorts. If the driver
    continues to sense “shorts” after the motor and wiring are determined to be
    good, then the output transistors should be checked (see below).
    Is the LED blinking Quickly? 
    This indicates that there is an open connection in one of the motor wires. 
    Check the motor and the wiring for opens.  Another condition that may cause
    this type of fault is when a large motor is ramped down too quickly so that it
    loses it’s positioning.
    Is the LED on Steadily?
    This indicates that there is a ground fault - a voltage shorted to 0V.  This
    detection is useful in detecting a short-to-case in a motor when the motor’s
    case AND the driver’s 0V are both connected to earth ground.  Excessive
    noise on the 0V line may also cause the driver to sense this type of fault. 
    This type of fault sensing may be disabled by placing jumper JP3 in position
    “1-2 (see figure 3A).  NOTE: IF THE GROUND FAULT DETECTION IS
    DISABLED, DO NOT CONNECT THE DRIVER’S 0V TO EARTH GROUND!
    Checking Output Transistors1.Remove the side plate on the driver side of the unit.
    2.Set the multimeter to Diode Test.
    3.Place the RED meter lead on Pin 7 (0Vdc) of the driver terminal
    block.
    4.Touch the BLACK meter lead to each phase (terminals 1, 2, 12, and
    13).
    5.Readings should be between 0.450V and 0.550V.
    6.If any  readings are significantly less than 0.450V, then the unit has
    been damaged.  To send the unit in for repair, contact the factory for
    an RMA#.
    910 E. Orangefair Lane, Anaheim CA 92801
     Phone (714) 992-6990   Fax (714) 992-0471
    website: http://www.anaheimautomation.com
    e-mail: [email protected] 
    						
    All Anaheim manuals Comments (0)

    Related Manuals for Anaheim Stepper DPD72451 Users Guide