    Have a look at the manual American Water Heater Commercial Light Duty Electric Water Heaters Lowboy Standard and Upright Series User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							11
    ELECTRICAL
    GENERAL
    The installation must conform with these instructions and the local 
    code authority having jurisdiction and the requirements of the power 
    company. In the absence of local codes, the installation must comply 
    with the current editions of the National Electrical Code, NFPA 70 or 
    the Canadian Electrical Code CSA C22.1. 
    An  electrical  ground  is  required  to  reduce  risk  of  electrical  shock 
    or  possible  electrocution.  The  water  heater  should  be  connected 
    to  a  separate  grounded  branch  circuit  with  over-current  protection 
    and  disconnect  switch.  The  water  heater  should  be  grounded  in 
    accordance with national and local codes.
    Voltage applied to the heater should not vary more than +5% to -10% 
    of the model and rating plate marking for satisfactory operation.
    DO NOT ENERGIZE THE BRANCH CIRCUIT FOR ANY REASON 
    BEFORE  THE  HEATER  TANK  IS  FILLED  WITH  WATER.  DOING 
    SO WILL CAUSE THE HEATING ELEMENTS TO BURN OUT AND 
    VOID WARRANTY.
    The factory wiring is attached to a terminal block within the external 
    junction  box  unit.    The  branch  circuit  is  connected  to  the  terminal 
    block within this junction box. The water heater should be connected 
    to a separate, grounded, branch circuit with overcurrent protection 
    and  disconnect  switch.    The  water  heater  should  be  grounded  in 
    accordance with national and local codes.
    BRANCH CIRCUIT
    The branch circuit wire size should be established through reference 
    to  the  current  edition  of  NFPA-70,  the National  Electrical  Code 
    or  other  locally  approved  source  in  conjunction  with  the  heater 
    amperage rating. For convenience, portions of the wire size tables 
    from  the  Code  are  reproduced  here. The  branch  circuit  should  be 
    sized at 125 percent of the heater rating and further increase wire 
    size as necessary to compensate for voltage drop in long runs.
    CALCULATING AMPERAGE/OVERCURRENT PROTECTION
    The heaters come from the factory in two configurations:
    1.  Two  wire  C-2  circuit  for  single  element  heater  equipped  with  a 
    high limit control, single phase power input.
    2.  Four wire A-8 circuit for dual element heater equipped with two 
    high limit controls, single phase or three phase power input.
    The  heater  with  dual  elements  is  factory  wired  for  connection  to 
    a  three  wire,  three-phase  delta  branch  circuit,  non-simultaneous 
    operation. In addition a ground conductor is required.
    Element connection is for non-simultaneous operation. This means 
    only one element at a time operates. The wiring diagram, on page 
    12,  shows  the  heater  may  be  field  converted  to  simultaneous 
    element operation by moving the red wire on “J” terminal to L1. It is 
    then  possible  for  both  elements  to  operate  at  once  as  determined 
    by  the  thermostats.  Regardless  of  element  connection  the  heater 
    operates in an “unbalanced” fashion.
    The heater may be field converted to single-phase operation by moving 
    the wire on L3 of the terminal block to L2. L3 is not used, see page 12.
    The heater, now in single-phase non-simultaneous operation, may 
    be field-converted to single phase simultaneous operation by moving 
    the red wire on terminal “J” to L1, see page 12. This is an example of calculating heater amperage for both types 
    of element operation. From this, the branch circuit conductor and 
    overcurrent protection sizing can be established.
    The  example  is  of  a  three-phase  240  volt  unit  with  two,  6  kw 
    e l e m e n t s .  T h e  n o t a t i o n s  a r e  f o r  u n i t s  fi e l d  c o n v e r t e d  t o  s i n g l e - p h a s e .  
    Check  the  heater  model  and  rating  plate  for  actual  specifications 
    and substitute those values in the following.
    TABLE 3
    Non-simultaneous:
    (as factory wired)
    Simultaneous:
    (Field conversion)
    3000 : 240 = 12.5 amps* 3000 : 240 = 12.5 amps*
      12.5 x 1.73 = 21.6 amps
    *NOTE:  as  a  single-phase  non-
    simultaneous unit. *NOTE:  as  a  single-phase 
    simultaneous unit the total is:
    12.5 x 2 = 25 amps
    The rating of the overcurrent protection should be computed on the 
    b a s i s  o f  12 5  p e r c e n t  o f  t h e  t o t a l  c o n n e c t e d  l o a d  a m p e r a g e .   W h e r e  t h e  
    standard ratings and settings do not correspond with this computation, 
    the next higher standard rating or setting should be selected.
    Portion	of	Table	310-16	(NFPA-70)	follows:
    Allowable Ampacities of Insulated Copper Conductors. Not more 
    than three conductors in Raceway or Cable or Direct Burial (Based 
    on Ambient Temperature of 30° C, 86° F).
    These  ampacities  relate  only  to  conductors  described  in  Table 
    310 -13 in Code.
    For  ambient  temperatures  over  30°  C  (86°  F),  see  Correction 
    Factors, Note 13 in Code.
    For  ambient  temperatures  over  30°  C  (86°  F),  see  Correction 
    Factors, Note 13 in Code.
    TABLE 4
    Size Temperature Rating of Conductor
    See Table 310-13 in Code
    AMG
    MCM 60°C
    (140°F) 75°C
    (167°F)
    Types:
    RUW, (14-2), T, TW, UF Types:
    RH, RHW, RUH, (14-2), 
    THW, THWN, XHHW, USE
    18
    16
    14 - - -
    - - -
    15 - - -
    - - -
    15
    12
    10 8 20
    30
    40 20
    30
    45
    6
    4
    3 55
    70
    80 65
    85
    100
    Portion	of	Table	310-18	follows:
    Allowable  Ampacities  of  Insulated  Aluminum  and  Copper  -Clad  
    Aluminum Conductors.
    Not more than three conductors in Raceway or Cable or Direct Burial 
    (Based on Ambient Temperature of 30° C,  86° F.  These ampacities 
    relate only to conductors described in Table 310-13 in Code.
    For ambient temperatures over 30° C (86° F), see Correction Factors, 
    Note 13 in Code.
    TABLE 5
    Size Temperature Rating of Conductor
    See Table 310-13 in Code
    AMG
    MCM 60°C
    (140°F) 75°C
    (167°F)
    Types:
    RUW, (12-2), T, TW, UF Types:
    RH, RHW, RUH, (12-2), 
    THW, THWN, XHHW, USE
    12
    10 15
    25 15
    25
    8
    6 30
    40 40
    50
    4
    3 55
    65 65
    75
    2
    1 75
    85 90
    100 
    						
    							12
    FIGURE 3 
    WIRING DIAGRAMS
    C-2 CIRCUIT 
    FOR Lowboy 6/10/15/20 
    HEATERS EQUIPPED WITH  HIGH LIMIT CONTROL
    A-8 CIRCUIT FOR DUAL ELEMENT HEATER
     FACTORY WIRED
    ----------  FIELD WIRING
    †     WHITE FOR 120V & 277V  
    						
    							13
    OPERATION
    GENERAL
    Refer to the Features and Components section of this manual (page 
    7)  for  the  location  of  components  mentioned  in  the  instructions 
    that follow.
    NEVER turn on power to the water heater without being certain the 
    water  heater  is  filled  with  water  and  a  temperature  and  pressure 
    relief valve is installed in the relief valve opening.
    DO  NOT  TEST  ELECTRICAL  SYSTEM  BEFORE  HEATER  IS 
    FILLED  WITH  WATER.  FOLLOW  FILLING  AND  START-UP 
    INSTRUCTIONS IN OPERATION SECTION.
    FILLING THE WATER HEATER
    1. Turn off the electrical disconnect switch.
    2.  Close the water heater drain valve.
    3.  Open a nearby hot water faucet to permit the air in the system 
    to escape.
    4.  Fully open the cold water inlet pipe valve allowing the heater and 
    piping to be filled.
    5.  Close  the  hot  water  faucet  as  water  starts  to  flow.  The 
    heater  is  now  ready  for  STARTUP  and  TEMPERATURE 
    REGULATION.
    INITIAL START UP
    The following checks should be made by the installer when the heater 
    is placed into operation for the first time.
    1. Turn off the electrical disconnect switch.
    2.  Open  the  front  panel  or  top  access  cover,  check  all  water  and 
    electrical connections for tightness. Also check connections on top 
    and or sides of heater. Repair water leaks and tighten electrical 
    connections as necessary.
    3.  Depress the red manual reset button on each Thermostat/ECO 
    combination control. (See Figure 5, Figure 6, Figure 7, or Figure 8)
    4.  Turn on the electrical disconnect switch.
    5.  Observe the operation of the electrical components during the first 
    heating cycle. Use care as the electrical circuits are energized.
    6.  Close the front panel or top access cover.
    Temperature control and contactor operation should be checked by 
    allowing heater to come up to temperature and shut off automatically. 
    Use care as the electrical circuits are energized.
    DRAINING THE WATER HEATER
    The water heater must be drained if it is to be shut down and exposed 
    to freezing temperatures. Maintenance and service procedures may 
    also require draining the heater.
    1.  Turn off the electrical disconnect switch.
    2.  Open  a  hot  water  valve  until  the  water  is  cool,  then  close  the 
    supply water inlet valve to heater.
    3.  Attach hose to outlet opening of drain valve and direct end to drain.
    4.  Open a nearby hot water faucet and the heater drain valve.
    5.  If  the  heater  is  being  drained  for  an  extended  shutdown,  it  is 
    suggested  the  drain  valve  be  left  open  during  this  period.  The 
    hose may be removed.
    Follow FILLING instructions when restoring hot water service.
    INSTALLATION 
    						
    							14
    THE  WATER  HEATER  IS  EQUIPPED  WITH  AN  ADJUSTABLE 
    THERMOSTAT  TO  CONTROL  WATER  TEMPERATURE.  HOT 
    WATER  AT  TEMPERATURES  DESIRED  FOR  AUTOMATIC 
    DISHWASHER  AND  LAUNDRY  USE  CAN  CAUSE  SCALDS 
    RESULTING  IN  SERIOUS  PERSONAL  INJURY AND/OR  DEATH. 
    THE TEMPERATURE AT WHICH INJURY OCCURS VARIES WITH 
    THE PERSON’S AGE AND TIME OF EXPOSURE. THE SLOWER 
    RESPONSE TIME OF CHILDREN , AGED OR DISABLED PERSONS 
    INCREASES  THE  HAZARD  TO  THEM.  NEVER  ALLOW  SMALL 
    CHILDREN TO USE A HOT WATER TAP, OR TO DRAW THEIR OWN 
    BATH WATER.  NEVER LEAVE A CHILD OR DISABLED PERSON 
    UNATTENDED IN A BATHTUB OR SHOWER.
    It is recommended that lower water temperatures be used to avoid 
    the risk of scalding. It is further recommended, in all cases, that the 
    water temperature thermostats (See Figure 4) be set for the lowest 
    temperature  which  satisfies  your  hot  water  needs.  This  will  also 
    provide the most energy efficient operation of the water heater. 
    Figure  4  shows  the  approximate  time-to-burn  relationship  for 
    normal  adult  skin.  The  thermostats  on  your  water  heater  have  a 
    linear  relationship  between  degrees  of  angular  rotation  and  the 
    corresponding change in temperature.  Thus rotating the temperature 
    adjustment  indicator  30  angular  degrees  will  result  in  a  10  degree 
    Fahrenheit change in water temperature.
    Water Temperature 
    °F (°C) Time for 1st Degree Burn
     
    (Less Severe Burns) Time for Permanent Burns
     
    2nd & 3rd Degree  
    (Most Severe Burns)
    110 (43) (normal shower temp.)
    116 (47) (pain threshold)
    116 (47) 35 minutes 45 minutes
    122 (50) 1 minute 5 minutes
    131 (55) 5 seconds 25 seconds
    140 (60) 2 seconds 5 seconds
    149 (65) 1 second 2 seconds
    154 (68) instantaneous 1 second
    (U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15, 1978)
    FIGURE 4
    TEMPERATURE ADJUSTMENT
    The water heater is supplied with thermostats that may come from 
    different manufactures and have different temperature indications 
    as described below.
    APCOM THERMOSTATS 
    A-8 Circuit thermostats have three designated set points; LO, MED 
    and HI.  (See Figure 5).The approximate equivalent temperatures for 
    these three settings are: LO = 140°F (60°C), MED = 160°F (71°C) and 
    HI = 181°F (83°C). These thermostats are set from the factory at the 
    LO 140°F (60°C) setting.  The over temperature device (ECO high 
    limit) attached to each thermostat has a manual reset. The C-2 circuit 
    thermostat is adjustable from approximately 130°F (54°C) to 170°F 
    (77°C)  (See Figure 6). These thermostats are set from the factory at  approximately the 140°F (60°C) setting. The over temperature device 
    (ECO high limit) attached to each thermostat has a manual reset.
            30A 120-250 VAC             22A 277 VAC        12.5A 480-600VAC125 VA.PT.DTY. 120-480 VAC
    MODELWH10C
    MED
    40A 120-277 VAC
    25A.480-600 VAC  125VA.PT.DTY.   120-480 VAC
    APCOM   INC
             FIGURE 5                 FIGURE 6 
    THERMODISC THERMOSTATS
    A-8  circuit  thermostats  are  adjustable  from  approximately  120°F 
    (49°C) (lowest setting) to 181°F (83°C) (highest setting) 
    (See Figure 
    7).  T h e  C - 2  c i r c u i t  t h e r m o s t a t  i s  a d j u s t a b l e  f r o m  a p p r o x i m a t e l y  110 ° F  
    (43°C) to 170°F (77°C)  (See Figure 8). These thermostats are set 
    from the factory at approximately the 140°F (60°C) setting. The over 
    temperature  device  (ECO  high  limit)  attached  to  each  thermostat 
    has a manual reset.
    L1 L3
    L4
    T2 T4
    L2
    T1
    THERM O DISC89T
    RESETRESET
    181°F120°F
    140°F
    L1 L3
    L4
    T2 T4
    L2
    T1
    THERM-O-DISC
    RESET
    170°F
    140°F 110°F
    RESET
             FIGURE 7                 FIGURE 8 
    NOTE: It is not necessary to adjust the upper thermostat for a dual 
    element unit. However, if it is adjusted above the factory set point 
    140°F  (60°C)  it  is  recommended  that  it  not  be  set  higher  than  the 
    lower thermostat setting.
    To change the temperature setting:
    1.
      DANGER: Turn off the heater electrical supply. Do not attempt 
    to adjust thermostat with power on.
    2.  Open  the  junction  box  door  (for  upper  thermostat  of  dual 
    element water heater only) and/or remove the (lower) thermostat 
    access panel. Do not remove the plastic personnel protectors 
    covering the thermostats. The thermostat is factory pre-set at 
    140°F (60°C). 
    3.  Using  a  flat  tip  screwdriver,  rotate  the  adjusting  knob  to  the 
    desired temperature setting.
    4.   Replace  the  covers  and  access  panels,  and  turn  on  heater 
    electrical supply.
    TEMPERATURE REGULATION 
    						
    							15
    GENERAL
    Periodically  the  drain  valve  should  be  opened  and  the  water 
    allowed to run until it flows clean. This will help to prevent sediment 
    buildup in the tank bottom.
    Periodically  check  the  temperature  and  pressure  relief  valve  to 
    ensure  that  it  is  in  operating  condition.  Lift  the  lever  at  the  top 
    of  the  valve  several  times  until  the  valve  seats  properly  and 
    operates freely.
    Water  heater  maintenance  includes  periodic  tank  flushing  and 
    cleaning, and removal of lime scale from the heating element.
    The heater tank is equipped with an anode rod to aid in corrosion 
    control.
    ANODE ROD INSPECTION
    The  anode  rod  is  used  to  protect  the  tank  from  corrosion.  Most  hot 
    water  tanks  are  equipped  with  an  anode  rod.  The  submerged  rod 
    sacrifices itself to protect the tank. Instead of corroding tank, water ions 
    attack and eat away the anode rod. This does not affect water’s taste or 
    color. The rod must be maintained to keep tank in operating condition.
    Anode deterioration depends on water conductivity, not necessarily 
    water condition. A corroded or pitted anode rod indicates high water 
    conductivity and should be checked and/or replaced more often than  
    an anode rod that appears to be intact. Replacement of a depleted 
    anode rod can extend the life of your water heater. Inspection should 
    be conducted by a qualified technician, and at a minimum should be 
    checked annually after the warranty period.
    Artificially  softened  water  is  exceedingly  corrosive  because  the 
    process  substitutes  sodium  ions  for  magnesium  and  calcium  ions.
    The  use  of  a  water  softener  may  decrease  the  life  of  the  water 
    heater tank.
    The anode rod should be inspected after a maximum of three years 
    and annually thereafter until the condition of the anode rod dictates 
    its replacement. 
    NOTE:  Artificially  softened  water  requires  the  anode  rod  to  be 
    inspected annually.
    MAINTENANCE 
    						
    							16
    TROUBLESHOOTING CHECKLIST
    CHECKLIST
    Before  calling  for  service,  check  the  following  points  to  see  if  the 
    cause of trouble can be identified and corrected.
    Reviewing  this  checklist  may  eliminate  the  need  of  a  service  call 
    and quickly restore hot water service. See Figure 2 on page 7 in this 
    manual to identify and locate water heater components.
    NOT ENOUGH OR NO HOT WATER
    1. Be certain the electrical disconnect switch serving the water heater 
    is in the ON position.
    2.  Check the fuses.
    • The electrical disconnect switch usually contains fuses.
    3.  If the water was excessively hot, and is now cold, the high limit 
    switch may have activated.
    • See  the  Temperature  Regulation  section  of  this  manual  for 
    more information on how to reset the ECO high limit controls.
    4.  The capacity of the heater may have been exceeded by a large 
    demand for hot water.
    • Large  demands  require  a  recovery  period  to  restore  water 
    temperature.
    5.  Cooler incoming water temperature will lengthen the time required 
    to heat water to the desired temperature.
    6.  Look for hot water leakage.
    7.  Sediment or pipe scale may be affecting water heater operation. ABNORMAL SOUNDS
    1. 
    Sediment  or  lime  scale  accumulations  on  the  elements  causes 
    sizzling and hissing noises when the heater is operating.
    • The  sounds  are  normal,  however,  the  tank  bottom  and 
    elements  should  be  cleaned.  See  the  Maintenance  section 
    of this manual.
    WATER LEAKAGE IS SUSPECTED
    Refer to Leakage Checkpoint on the following page 17.
    1.  Check to see if the heater drain valve is tightly closed.
    2.  If the outlet of the relief valve is leaking it may represent:
    • Excessive water temperature.
    •  Faulty relief valve.
    •  Excessive water pressure.
    3.  Excessive water pressure is the most common cause of relief valve 
    leakage.  It  is  often  caused  by  a  “closed  system”.  See  “Closed 
    Water  Systems”  and  “Thermal  Expansion”  in  the  Installation 
    section of this manual for more information.
    4.  Examine the area around the element for gasket leakage.
    • Tighten the elements or, if necessary, replace the gaskets.
    IF YOU CANNOT IDENTIFY OR CORRECT THE SOURCE OF 
    MALFUNCTION
    1.  Turn the power supply to the water heater off.
    2.  Close the supply water inlet valve to the heater.
    3.  Contact a Qualified Service Agency in your area. Call the toll free 
    phone number on the water heater label for assistance in locating 
    a service agency in your area.
    REPLACEMENT PARTS
    For  replacement  parts  shown  in  this  manual  please  contact  the 
    company it was purchased from or direct from the manufacturer listed 
    on the rating plate on the water heater. 
    						
    							17
    LEAKAGE CHECKPOINTS
    Instructions: Use this illustration as a guide when checking for sources of water leakage. You or your dealer may be able to correct what 
    appears to be a problem.  NOTE:	Cover	and	Insulation	shown	removed	to	reveal	tank	top.
    Relief Valve
    To Open Drain
    Condensation and dripping may appear 
    on pipes when cold water temperature is 
    low.	Pipe	fitting	may	be	leaking. Relief valve operation and leakage 
    may be due to water expansion during 
    heating cycle or foreign material on seat 
    of valve. If the valve is not piped to an 
    open drain the released water could be 
    mistaken for a leaking heater. To check 
    where threaded material between jacket 
    opening and swab spud area. Remove 
    valve* if indicated and repair with pipe 
    joint compound.
    Water on the side of the tank may 
    be condensation due to the panel or 
    insulation not being in place.
    Drain valve leakage could be from the 
    valve itself.* To check for leakage where 
    threaded portion enters tank, insert Q-tip 
    or similar absorbent material between 
    jacket opening and valve to swab spud 
    area. Remove valve* if leak is indicated 
    and repair with pipe joint compound.
    *Contact  your  dealer  as  it  is  necessary  to 
    shut off electricity and drain tank to perform 
    procedure.
    Water leaks at the elements may be due 
    to:
    1.
     Defective element which leaks at 
    terminals or thru flange. Replace 
    element*.
    2.  Loose	element/gasket	leak:
    	 (a)	 Screw-in	 type:	tighten	 with	1-1/2” 	
    socket wrench. If leak continues, 
    remove element*, discard gasket 
    and clean thread areas.Apply 
    nonhardening Permatex Number 2 
    to thread areas, install new gasket 
    and	 screw	 element	 into	fitting	 until	
    it seats. Tighten 1/2 to 3/4 turn with 
    wrench.
    	 (b)	 Flange	 type:	tighten 	screw 	with 	
    wrench. If leak continues remove 
    element* and discard gasket. Clean 
    gasket seating areas and re-install 
    element with new gasket. A new 
    element may be required where 
    threads have become rusted or 
    damaged, preventing tightening.
    All water which appears at the water 
    h e a t e r 	b o t t o m 	o r	o n 	t h e 	s u r r o u n d i n g 	fl o o r	
    may be caused by condensation, loose 
    connections or relief valve operation 
    and leakage. Do not replace the water 
    heater until full inspection of all potential 
    leak points is made and corrective steps 
    taken to stop the leak. Leakage from other 
    appliances, water lines or ground (see 
    page 16) should also be suspected until 
    proven otherwise. Anode Rod (Some Models)
    Where possible remove or lift top cover to 
    examine threads of fittings installed into tank 
    for evidence of leakage.  Correct fitting leaks 
    as necessary.
    To Open Drain
    FIGURE 9  
    						
    							18
     EFFECTIVE
    For 3 Years, in the event of a tank leak, we will repair or, at our 
    discretion, replace the defective water heater.
    For 1 Year, in the event of part failure, we will repair or, at our 
    discretion, replace the defective part.
    We  warrant  this  product  against  defects  in  materials  or 
    workmanship  as  described  in  this  document  if  installed  within 
    the United States or Canada and provided the product remains 
    at its original place of installation.
    Warranty coverage begins the date of installation OR the date of 
    manufacture if installation cannot be verified.
     WHAT'S COVERED
    Subject  to  these  terms,  in  the  event  of  defect  in  materials  and/
    or  workmanship  resulting  in  a  tank leak  during  the first	three 	
    years, we will:
    •  Replace the water heater should the tank leak.
    Subject to these terms, in the event of a defect in materials and/or 
    workmanship appearing during the first	year, we will:
    •  Repair  or,  at  our  discretion,  replace  any  part  of  the  water 
    heater  covered  under  this  limited  warranty  excluding  parts 
    subject  to  normal  maintenance  (Example:  non-electronic 
    anode rod, filter, etc)
    Service/labor, shipping, delivery, installation, handling or any 
    other costs are not covered at any time under this warranty.
    Any  replacement  part  or  product  will  be  warranted  only  for 
    the  unexpired  portion  of  the  original  water  heater’s  limited 
    warranty period.
    If an identical model is no longer available due to a change in law, 
    regulation, or standard, we will replace the product with one having 
    comparable  capacity  and  input.  In  these  instances,  the  owner  will 
    have the option of paying the difference between what was paid for 
    the original model and the new model with the additional features, 
    or  receiving  a  refund  of  the  portion  of  the  purchase  price,  on  a 
    pro-rata basis allocable to the unexpired portion of the warranty.
     WHAT'S NOT COVERED
    •  Problems caused by improper: gas supply line sizing, gas type, 
    venting, connections, combustion air, voltage, wiring, or fusing   
    •   Failure to follow applicable codes   
    •   Failure to follow printed instructions   
    •   Abuse, misuse, accident, fire, flood, Acts of God   
    •   Improper installation,  sizing, delivery, or maintenance   
    •   Claims related to rust, noise, smell, or taste of water   
    •   Failure to conduct authorized factory start up if required   
    •   Alterations to the water heater   
    •   Non-outdoor heaters installed outdoors   
    •   Damages due to a failure to allow for thermal expansion   
    •  Heat exchanger failure due to lack of adequate / proper supply 
    of water   
    •   Heaters moved from their original location   
    •   Service trips to explain proper installation, use, or maintenance  of  the  product/unit  or  to  describe  compliance  requirements 
    under applicable codes and regulations   
    •    Charges  related  to  accessing  your  heater  including  but  not  limited to door/wall removal, equipment rental, etc.   
    •   Replacement parts after expiration of this warranty   
     LIMITATIONS
    NOTWITHSTANDING  ANYTHING  ELSE  TO  THE  CONTRARY, 
    THIS  IS  YOUR  SOLE  AND  EXCLUSIVE  WARRANTY.  
    ALL  OTHER  WARRANTIES  INCLUDING  A  WARRANTY 
    OF  MERCHANTABILITY  OR  FITNESS  FOR  PARTICULAR 
     
    PURPOSE  ARE  EXPRESSLY  DISCLAIMED.  SELLER  SHALL 
    NOT  BE  LIABLE  FOR  ANY  CONSEQUENTIAL,  INCIDENTAL, 
    SPECIAL, PUNITIVE OR OTHER INDIRECT DAMAGES.  TOTAL 
    LIABILITY  ARISING  AT  ANY  TIME  SHALL  NOT  EXCEED  THE 
    PURCHASE  PRICE  PAID  WHETHER  BASED  ON  CONTRACT, 
    TORT, STRICT LIABILITY OR ANY OTHER LEGAL THEORY.
    SERVICE	INQUIRIES:
    For service inquiries call the telephone number listed below.  Be prepared to provide the following information: 
    name, address, and telephone number; the model and serial number of the water heater; proof of installation; and a clear description 
    of the problem.  
    For your records, fill in the product:
    Serial: ___________________
    Model: ___________________
      U.S. Customers:  Canadian Customers:
      A. O. Smith Corporation  P. O. Box 310 – 768 Erie Street
     500 Tennessee Waltz Parkway  Stratford (Ontario) N5A 6T3
      Ashland City, Tennessee 37015  800-265-8520
     800-527-1953
    COMMERCIAL
    WATER HEATER 
    LIMITED WARRANTY 
    						
    							19
    NOTES 
    						
    							20
    REPAIR PARTS LIST
    Now that you have purchased this water heater, should a need ever 
    exist for repair parts or service, simply contact the company it was 
    purchased from or direct from the manufacturer listed on the rating 
    plate on the water heater.
    Selling prices will be furnished on request or parts will be shipped 
    at prevailing prices and you will be billed accordingly.
    The model number of your Water Heater will be found on the rating 
    plated located above the lower access panel.Be sure to provide all pertinent facts when you call or visit.
    WHEN  ORDERING  REPAIR  PARTS,  ALWAYS  GIVE  THE 
    FOLLOWING INFORMATION:
     
    •  MODEL NUMBER
      •  VOLTAGE AND ELEMENT WATTAGE
      •  SERIAL NUMBER
      •  PART DESCRIPTION
    Lowboy 6, 10, 15, 20 Series 102 (refer to repair parts table).
    DRAIN VALVE 
    (not supplied with heater)
    FIGURE 10  
    						