Home
>
American Water Heater
>
Gas Heater
>
American Water Heater 98 Gallon High Recovery Natural Gas Water Heater G62100T774NOV User Manual
American Water Heater 98 Gallon High Recovery Natural Gas Water Heater G62100T774NOV User Manual
Have a look at the manual American Water Heater 98 Gallon High Recovery Natural Gas Water Heater G62100T774NOV User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
11 fIGure 9. Figure 9 shows the typical attachment of the water piping to the water heater. The water heater is equipped with 1” NPT threaded nipple (75 gallon models) or 1.25” NPT threaded nipple (100 gallon models) water connections. note: If using copper tubing, solder tubing to an adapter before attaching the adapter to the cold water inlet connection. do not solder the cold water supply line directly to the cold water inlet. It will harm the dip tube and damage the tank. teMperature-pressure relIef v alve This heater is provided with a properly certified combination temperature - pressure relief valve by the manufacturer. The valve is certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Relief Valves for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4, and the code requirements of ASME. If replaced, the valve must meet the requirements of local codes, but not less than a combination temperature and pressure relief valve certified as indicated in the above paragraph. The valve must be marked with a maximum set pressure not to exceed the marked maximum working pressure of the water heater (150 psi = 1,035 kPa) and a discharge capacity not less than the water heater input rate as shown on the model rating plate. For safe operation of the water heater, the relief valve must not be removed from its designated opening nor plugged. The temperature-pressure relief valve must be installed directly into the fitting of the water heater designed for the relief valve. Position the valve downward and provide tubing so that any discharge will exit only within 6” (153 mm) above, or at any distance below the structural floor. Be certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30’ (9.14 m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve, see Figure 10. No valve or other obstruction is to be placed between the relief valve and the tank. Do not connect tubing directly to discharge drain unless a 6 inch air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage. The Discharge Pipe: • Should not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions. • Should not be plugged or blocked. • Should be of material listed for hot water distribution. • Should be installed so as to allow complete drainage of both the temperature-pressure relief valve, and the discharge pipe. • Must terminate a maximum of six inches above a floor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building. • Should not have any valve between the relief valve and tank. The temperature-pressure relief valve must be manually operated at least once a year. Caution should be taken to ensure that (1) no one is in front of or around the outlet of the temperature-pressure relief valve discharge line, and (2) the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot. If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions, and replace the temperature-pressure relief valve with a new one.
12 fIGure 10. fIllInG the water heater Never use this water heater unless it is completely full of water. To prevent damage to the tank, the tank must be filled with water. Water must flow from the hot water faucet before turning “ON” gas to the water heater. To fill the water heater with water: 1. Close water heater drain valve by turning handle to the right (clockwise). The drain valve is on the lower front of water heater. 2. Open the cold water supply valve to the water heater. note: the cold water supply valve must be left open when the water heater is in use. 3. To insure complete filling of the tank, allow air to exit by opening the nearest hot water faucet. Allow water to run until a constant flow is obtained. This will let air out of the water heater and piping. 4. Check all water piping and connections for leaks. Repair as needed. ventInG VENT DAMPERS - Any vent damper, whether it is operated thermally or otherwise must be removed if its use inhibits proper drafting of the water heater. Thermally Operated Vent Dampers: this gas-fired water heater has a thermal efficiency at or above 80% which may produce a relatively low flue gas temperature. Such temperatures may not be high enough to properly open thermally operated vent dampers. This would cause spillage of the flue gases and may cause carbon monoxide poisoning. Vent dampers must bear evidence of certification as complying with the current edition of the American National Standard ANSI Z21.66 CGA 6.14 (covering electrically and mechanically actuated vent dampers). Before installation of any vent damper, consult the local gas utility for further information. To insure proper venting of this gas-fired water heater, the correct vent pipe diameter must be utilized. Any additions or deletions of other gas appliances on a common vent with this water heater may adversely affect the operation of the water heater. Consult your gas supplier if any such changes are planned. For proper venting in certain installations, a larger diameter vent pipe may be necessary. Consult your gas supplier to aid you in determining the proper venting for your water heater from the vent tables in the current edition of the National Fuel Gas Code ANSI Z223.1/NFPA 54. Periodically check the venting system for signs of obstruction or deterioration and replace if needed. The combustion and ventilation air flow must not be obstructed. The water heater with draft hood installed must be connected to a chimney or listed vent pipe system, which terminates to the outdoors. Never operate the water heater unless it is vented to the outdoors and has adequate air supply to avoid risks of improper operation, explosion or asphyxiation. • For proper draft hood attachment, the draft hood legs may be angled slightly inward. • Place the draft hood legs in the receiving holes on the top of the water heater. The legs will snap in the holes to give a tight fit. Secure draft hood with the supplied brackets. • Place the vent pipe over the draft hood. With the vent pipe in position, drill a small hole through both the vent pipe and draft hood. Secure them together with a sheet metal screw, see Figure 11. Obstructed or deteriorated vent systems may present serious health risk or asphyxiation. fIGure 11. The vent pipe from the water heater must be no less than the diameter of the draft hood outlet on the water heater and must slope upward at least 1/4 inch per linear foot (21 mm per meter), see Figure 12. All vent gases must be completely vented to the outdoors of the structure (dwelling). Install only the draft hood provided with the new water heater and no other draft hood. Vent pipes must be secured at each joint with sheet metal screws.
13 fIGure 12. There must be a minimum of 6” (153 mm) clearance between single wall vent pipe and any combustible material. Fill and seal any clearance between single wall vent pipe and combustible surfaces with mortar mix, cement, or other noncombustible substance. For other than single wall, follow vent pipe manufacturer’s clearance specifications. To insure a tight fit of the vent pipe in a brick chimney, seal around the vent pipe with mortar mix cement. Failure to have required clearances between vent piping and combustible material will result in a fire hazard. Be sure vent pipe is properly connected to prevent escape of dangerous flue gases which could cause deadly asphyxiation. Chemical vapor corrosion of the flue and vent system may occur if air for combustion contains certain chemical vapors. Spray can propellants, cleaning solvents, refrigerator and air conditioner refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes, bleach and process chemicals are typical compounds which are potentially corrosive. Gas pIpInG M a k e s u r e t h e g a s s u p p l i e d i s t h e s a m e t y p e l i s t e d o n t h e m o d e l rating plate. The inlet gas pressure must not exceed 14 inch w a t e r c o l u m n ( 2 . 6 k P a) f o r n a t u r a l a n d p r o p a n e ( L . P.) g a s . T h e minimum inlet gas pressure shown on the rating plate is that which will permit firing at rated input. If the gas control valve is subjected to pressures exceeding 1/2 pound per square inch (3.5 kPa), the damage to the gas c o n t r o l v a l v e c o u l d r e s u l t i n a f i r e o r e x p l o s i o n f r o m l e a k i n g g a s . If the main gas line shut-off serving all gas appliances is used, also turn “off ” the gas at each appliance. Leave all gas appliances shut “off ” until the water heater installation is complete. A gas line of sufficient size must be run to the water heater. Consult the current edition of National Fuel Gas Code ANSI Z223.1/NFPA 54 and your gas supplier concerning pipe size. There must be: • A r e a d i l y a c c e s s i b l e m a n u a l s h u t o f f v a l v e i n t h e g a s s u p p l y line serving the water heater, and • A sediment trap ahead of the gas control valve to help prevent dirt and foreign materials from entering the gas control valve. • A flexible gas connector or a ground joint union between the shut off valve and control valve to permit servicing of the unit. Be sure to check all the gas piping for leaks before lighting the w a t e r h e a t e r. U s e a s o a py w a t e r s o l u t i o n , n o t a m a t c h o r o p e n flame. Rinse off soapy solution and wipe dry. The minimum inlet gas pressure shown on the rating plate is that which will permit firing at the rated input. Water heaters covered in this manual have been tested and approved for installation at elevations up to 7,700 feet (2,347 m) above sea level. For installation above 7,700 feet (2,347 m), the water heater’s Btu input should be reduced at the rate of 4 percent for each 1,000 feet (305 m) above sea level which requires replacement of the burner orifice in accordance with the National Fuel Gas Code ANSI Z223.1/NFPA 54. Contact your local gas supplier for further information. Failure to replace the standard orifice with the proper high altitude orifice when installed at elevations above 7,700 feet (2,347 m) could result in improper and inefficient operation of the water heater producing carbon monoxide gas in excess of the safe limits. This could result in serious injury or death. Contact your local gas supplier for any specific changes that may be required in your area.
14 Use pipe joint compound or teflon tape marked as being resistant to the action of petroleum [Propane (L.P.)] gases. The water heater and its gas connection must be leak tested before placing the water heater in operation. The water heater and its individual shut-off valve shall be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 pound per square inch (3.5 kPa). It shall be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 pound per square inch (3.5 kPa). Connecting the gas piping to the gas control valve of the water heater can be accomplished by either of the two methods shown in Figures 13 and 14. fIGure 13. Gas pIpInG wIth fleXIBle connector. fIGure 14. Gas pIpInG wIth all BlacK Iron pIpe to Gas control. sedIMent traps A sediment trap shall be installed as close to the inlet of the water heater as practical at the time of water heater installation. The sediment trap shall be either a tee fitting with a capped nipple in the bottom outlet or other device recognized as an effective sediment trap. If a tee fitting is used, it shall be installed in conformance with one of the methods of installation shown in Figures 13 and 14. Contaminants in the gas lines may cause improper operation of the gas control valve that may result in fire or explosion. Before attaching the gas line be sure that all gas pipe is clean on the inside. To trap any dirt or foreign material in the gas supply line, a sediment trap must be incorporated in the piping. The sediment trap must be readily accessible. Install in accordance with the “Gas Piping” section. Refer to the current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
16 for Your safetY read Before lIGhtInG Before lIGhtInG: entIre sYsteM Must Be fIlled wIth water and aIr purGed at faucets. warnInG: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of\ life. 1. STOP! Read the safety information above on this label. 2. Set the thermostat to the lowest setting by turning thermostat dial fully clockwise until it stops. 3. Push the gas control knob down slightly and turn clockwise to “OFF” (Figure A). NOTE: Gas control knob CANNOT be turned from “PILOT” to “OFF” unless it is pushed down slightly. Do not force. 4. Remove the inner and outer doors located below and behind the gas control unit. 5. Wait five (5) minutes to clear out any gas. If you then smell gas STOP! Follow “B” in the safety information above on this label. If you do not smell gas, go to the next step. 6. Find Pilot. Follow metal tube from the bottom , right of the gas control to the pilot burner. (Figure D). 7. Turn gas control knob counterclockwise to “PILOT” (Figure B). 8. Push gas control knob down all the way and hold it down. Immediately light the pilot with a match. Continue to hold the gas control knob down for about one (1) minute after the pilot is lit. Release the gas control knob and it will pop back up. Pilot should remain lit. If it goes out, repeat Steps 3 through 8. It may take several minutes for air to clear the lines, before the pilot will light. • If knob does not pop up when released, stop and immediately call your service technician or gas supplier. • If the pilot will not stay lit after several tries, turn the gas control knob to “OFF” (Figure A) and call your service technician or gas supplier. 9. Replace inner and outer burner doors. 10. At arm’s length away, turn the gas control knob counterclockwise to “ON” (Figure C). 11. Set thermostat to desired setting (See Figure). cautIon: hotter water increases the risk of scald injury. consult the instruction manual before changing temperature. lIGhtInG InstructIons to turn off Gas to applIance 1. Set the thermostat to lowest setting. 2. Push gas control knob down slightly and turn clockwise to “OFF”. Do not force, see Figure A. top vIew fIGure “d” Gas control A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly. B. Before lIGhtInG: smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. what to do If You sMell Gas • Do not try to light any appliance. • Do not touch any electric switch; do not use any phone in your building. • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. • If you cannot reach your gas supplier, call the fire department. C. Use only your hand to push down or turn the gas control knob. Never use tools. If the knob will not push down or turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part has been under water. Immediately contact a qualified installer or service agency to replace a flooded water heater. Do not attempt to repair the unit! It must be replaced!
17 for Your InforMatIon start up condItIons draft hood operatIon Check draft hood operation by performing a worst case depressurization of the building. With all doors and windows closed, and with all air handling equipment and exhaust fans operating such as furnaces, clothes dryers, range hoods and bathroom fans, a match flame should still be drawn into the draft hood of the water heater with its burner firing. If the flame is not drawn toward the draft hood, shut off water heater and make necessary air supply changes to correct. condensatIon Whenever the water heater is filled with cold water, some condensate will form while the burner is on. A water heater may Never allow small children to use a hot water tap, or to draw their own bath water. Never leave a child or handicapped person unattended in a bathtub or shower. NOTE: A water temperature range of 120°F-140°F (49°C-60°C) is recommended by most dishwasher manufacturers. The thermostat of this water heater has been factory set at its lowest position (PILOT LIGHTING). It is adjustable and must be reset to the desired temperature setting to reduce the risk of scald injury. The mark ( ) indicative of approximately 120°F (49°C) is preferred starting point. Some States have a requirement for a lower setting. Turn the water temperature dial clockwise ( ) to decrease the temperature, or counterclockwise ( ) to increase the temperature. Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the water heater. fIGure 15. (U .S. Go vernme nt Me morand um , C. P.S. C. , Pe ter L. Ar ms tron g, Se pt. 15 , 19 78) 110 (43) (normal shower temp.) 116 (47) (pain threshold) 116 (47) 35 minutes 45 minutes 122 (50) 1 minute 5 minutes 131 (55) 5 seconds 25 seconds 140 (60) 2 seconds 5 seconds 149 (65) 1 second 2 seconds 154 (68) instantaneous 1 second Water Te mp erat ur e °F (°C) Time fo r 1s t Degree Burn(Less Severe Burns) Time for Pe rm anent Burns2nd & 3rd Degree(Most Severe Burns) (U.S. Go vernme nt Me morandum , C. P.S. C. , Pe ter L. Ar ms tron g, Se pt. 15 , 19 78) 43 (110) (temp. normale d’une douche ) 47 (116) (seuil de douleur ) 47 (116) 35 minutes 45 minutes 50 (122) 1 minute 5 minutes 55 (131) 5 secondes 25 secondes 60 (140) 2 secondes 5 secondes 65 (149) 1 seconde 2 secondes 68 (154) instantaneous 1 seconde Te mp ératu re de Ieau °C (°F) Délai pour des brûlures au 1er degré (b rû lures moin s gr aves ) Délai pour des brûlurespermanentes au 2e et 3e degrés(brûlures les plus graves) fIGure 16. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 30°F (16.7°C). If you experience this type of use you should consider using lower temperature settings to reduce scald hazards. Any water heater’s intended purpose is to heat water. Hot water is needed for cleansing, cleaning, and sanitizing (bodies, dishes, clothing). Untempered hot water can present a scald hazard. Depending on the time element, and the people involved (adults, children, elderly, infirm, etc.) scalding may occur at different temperatures. HOTTER WATER CAN SCALD: Water heaters are intended to produce hot water. Water heated to a temperature which will satisfy space heating, clothes washing, dish washing, and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infirm, or physically/ mentally handicapped. If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap, then you must take special precautions. In addition to using the lowest possible temperature setting that satisfies your hot water needs, a means such as a mixing valve should be used at the hot water taps used by these people or at the water heater. Mixing valves are available at plumbing supply or hardware stores, see Figure 2. Follow manufacturer’s instructions for installation of the valves. Before changing the factory setting on the thermostat, read the “Temperature Regulation” section in this manual, see Figures 15 and 16. teMperature reGulatIon a p p e a r t o b e l e a k i n g w h e n i n f a c t t h e w a t e r i s c o n d e n s a t i o n . T h i s usually happens when: a. A new water heater is filled with cold water for the first time. b. Burning gas produces water vapor in water heaters, particularly high efficiency models where flue temperatures are lower. c. Large amounts of hot water are used in a short time and the refill water in the tank is very cold. Moisture from the products of combustion condense on the cooler tank surfaces and form drops of water which may fall onto the burner or other hot surfaces to produce a “sizzling” or “frying” noise. Excessive condensation can cause pilot outage due to water running down the flue tube onto the main burner and putting out the pilot.
18 Because of the suddenness and amount of water, condensation water may be diagnosed as a “tank leak”. After the water in the tank warms up (about 1-2 hours), the condition should disappear. Do not assume the water heater is leaking until there has been enough time for the water in the tank to warm up. An undersized water heater will cause more condensation. The water heater must be sized properly to meet the family’s demands for hot water including dishwashers, washing machines and shower heads. Excessive condensation may be noticed during the winter and early spring months when incoming water temperatures are at their lowest. Good venting is essential for a gas fired water heater to operate properly as well as to carry away products of combustion and water vapor. sMoKe/odor It is not uncommon to experience a small amount of smoke and odor during the initial start-up. This is due to burning off of oil from metal parts, and will disappear in a short while. therMal eXpansIon As water is heated, it expands (thermal expansion). In a closed system the volume of water will grow when it is heated. As the volume of water grows there will be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause premature tank failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent Temperature-Pressure Relief Valve operation: water discharged from the valve due to excessive pressure build up. This condition is not covered under the limited warranty. The Temperature-Pressure Relief Valve is not intended for the constant relief of thermal expansion. A properly sized thermal expansion tank must be installed on all closed systems to control the harmful effects of thermal expansion. Contact a local plumbing service agency to have a thermal expansion tank installed. stranGe sounds Possible noises due to expansion and contraction of some metal parts during periods of heat-up and cool-down do not necessarily represent harmful or dangerous conditions. Condensation causes sizzling and popping within the burner area during heating and cooling periods and should be considered normal. See “Condensation” in this section. operatIonal condItIons sMell Y w ater In each water heater there is installed at least one anode rod (see parts section) for corrosion protection of the tank. Certain water conditions will cause a reaction between this rod and the water. The most common complaint associated with the anode rod is one of a “rotten egg smell” in the hot water. This odor is derived from hydrogen sulfide gas dissolved in the water. The smell is the result of four factors which must all be present for the odor to develop: a. A concentration of sulfate in the supply water. b. Little or no dissolved oxygen in the water. c. A sulfate reducing bacteria which has accumulated within the water heater (this harmless bacteria is nontoxic to humans). d. An excess of active hydrogen in the tank. This is caused by the corrosion protective action of the anode. Smelly water may be eliminated or reduced in some water heater models by replacing the anode(s) with one of less active material, and then chlorinating the water heater tank and all hot water lines. Contact the local water heater supplier or service agency for further information concerning an Anode Replacement Kit and this chlorination treatment. If the smelly water persists after the anode replacement and chlorination treatment, we can only suggest that chlorination or aeration of the water supply be considered to eliminate the water problem. do not remove the anode leaving the tank unprotected. By doing so, all warranty on the water heater tank is voided. “aIr” In hot water faucets HYDROGEN GAS: Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable and explosive. To prevent the possibility of injury under these conditions, we recommend the hot water faucet, located farthest away, be opened for several minutes before any electrical appliances which are connected to the hot water system are used (such as a dishwasher or washing machine). If hydrogen gas is present, there will probably be an unusual sound similar to air escaping through the pipe as the hot water faucet is opened. There must be no smoking or open flame near the faucet at the time it is open. hIGh water teMperature shut off sYsteM This water heater is equipped with an automatic gas Shut-off system. This system works when high water temperatures are present. The high temperature Shut-off is built into the gas control valve. It is non-resettable. If the high temperature Shut-off activates, the gas control valve must be replaced. Contact your gas supplier or service agency. Turn “OFF” the entire gas supply to the water heater.
19 You should check for sooting. Soot is not normal and will impair proper combustion. Soot build-up indicates a problem that requires correction before further use. Turn “OFF” gas to water heater and leave off until repairs are made, because failure to correct the cause of the sooting can result in a fire causing death, serious injury, or property damage. natural propane fIGure 17. Burner cleanInG If inspection of the burner shows that cleaning is required, turn the gas control knob clockwise ( ) to the “OFF” position, depressing slightly. note: the knob cannot be turned from “pI lot” to “off ” unless knob is depressed slightly. do not force. Loose deposits on or around the burner can be removed by carefully using the hose of a vacuum cleaner inserted through the access door of the water heater. If the burner needs to be removed for additional cleaning, call a service agency to remove and clean the burner and correct the problem that required the burner to be cleaned. houseKeepInG Vacuum around base of water heater for dust, dirt, and lint on a regular basis. ventInG sYsteM InspectIon At least once a year a visual inspection should be made of the venting system. You should look for: 1. Obstructions which could cause improper venting. The combustion and ventilation air flow must not be obstructed. 2. Damage or deterioration which could cause improper venting or leakage of combustion products. 3. Rusted flakes around top of water heater. Be sure the vent piping is properly connected to prevent escape of dangerous flue gases which could cause deadly asphyxiation. Obstructions and deteriorated vent systems may present serious health risk or asphyxiation. Chemical vapor corrosion of the flue and vent system may occur if air for combustion contains certain chemical vapors. Spray can propellants, cleaning solvents, refrigerator and air conditioner refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes, bleach and process chemicals are typical compounds which are potentially corrosive. If after inspection of the vent system you found sooting or deterioration, something is wrong. Call the local gas utility to correct the problem and clean or replace the flue and venting before resuming operation of the water heater. Burner InspectIon Flood damage to a water heater may not be readily visible or immediately detectable. However, over a period of time a flooded water heater will create dangerous conditions which can cause DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE. Contact a qualified installer or service agency to replace a flooded water heater. Do not attempt to repair the unit! It must be replaced! At least once a year a visual inspection should be made of the main burner and pilot burner, see Figure 17. perIodIc MaIntenance
20 In replacing the anode: 1. Turn off gas supply to the water heater. 2. Shut off the water supply and open a nearby hot water faucet to depressurize the water tank. 3. Drain approximately 5 gallons of water from tank. (Refer to “Draining and Flushing” for proper procedures). Close drain valve. 4. Remove old anode rod. 5. Use Tefl on® tape or approved pipe sealant on threads and install new anode rod. 6. Turn on water supply and open a nearby hot water faucet to purge air from water system. Check for any leaks and immediately correct any if found. 7. Restart the water heater as directed in this manual. See the Repair Parts Illustration for anode rod location. teMperature-pressure relIef v alve operatIon The temperature-pressure relief valve must be manually operated at least once a year. When checking the temperature-pressure relief valve operation, make sure that (1) no one is in front of or around the outlet of the temperature-pressure relief valve discharge line, and (2) that the water discharge will not cause any property damage, as the water may be extremely hot, see Figure 18. fIGure 19. If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions, and replace the temperature-pressure relief valve with a new one. If the temperature-pressure relief valve on the water heater weeps or discharges periodically, this may be due to thermal expansion. You may have a check valve installed in the water line or a water meter with a check valve. Consult your local water supplier or service agency for further information. Do not plug the temperature- pressure relief valve. INSTALLED IN SUITABLE AREA: To insure sufficient ventilation and combustion air supply, proper clearances from the water heater must be maintained. See “Locating the New Water Heater” section. Combustible materials such as clothing, cleaning materials, or flammable liquids, etc. must not be placed against or adjacent to the water heater which can cause a fire. anode rod InspectIon Each water heater contains at least one anode rod, which will slowly deplete (due to electrolysis) prolonging the life of the water heater by protecting the glass-lined tank from corrosion. Adverse water quality, hotter water temperatures, high hot water usage, and water softening methods can increase the rate of anode rod depletion. Once the anode rod is depleted, the tank will start to corrode, eventually developing a leak. Certain water conditions will cause a reaction between the anode r o d a n d t h e w a t e r. T h e m o s t c o m m o n c o m p l a i n t a s s o c i a t e d w i t h t h e a n o d e r o d i s a “ r o t t e n e g g s m e l l ” p r o d u c e d f r o m t h e p r e s e n c e o f h y d r o g e n s u l f i d e g a s d i s s o l v e d i n t h e w a t e r. I M P O R TA N T: D o not remove this rod permanently as it will void any warranties. A s p e c i a l a n o d e r o d m a y b e a v a i l a b l e i f w a t e r o d o r o r d i s c o l o r a t i o n o c c u r s . N O T E : T h i s r o d m a y r e d u c e b u t n o t e l i m i n a t e w a t e r o d o r p r o b l e m s . T h e w a t e r s u p p l y s y s t e m m a y r e q u i r e s p e c i a l f i l t r a t i o n equipment from a water conditioning company to successfully eliminate all water odor problems. A r t i f i c i a l l y s o f t e n e d w a t e r i s e x c e e d i n g l y c o r r o s i v e b e c a u s e t h e process substitutes sodium ions for magnesium and calcium ions. The use of a water softener may decrease the life of the water heater tank. T he an o de r o d sh o ul d b e insp e c te d af te r a ma x imum of t hre e years and annually thereafter until the condition of the anode rod dictates its replacement. NOTE: Artifi cially softened water requires the anode rod to be inspected annually. The following are typical (but not all) signs of a depleted anode rod: • The majority of the rods diameter is less than 3/8”. • Significant sections of the support wire (approx. 1/3 or more of the anode rod’s length) are visible. fIGure 18. If the anode rod show signs of either or both it should be replaced. NOTE: Whether re-installing or replacing the anode rod, check for any leaks and immediately correct if found.