Home
>
American Water Heater
>
Gas Heater
>
American Water Heater 80 Thermal Efficiency UltraLow NOx Heavy Duty Commercial Gas Water Heater BCL3 User Manual
American Water Heater 80 Thermal Efficiency UltraLow NOx Heavy Duty Commercial Gas Water Heater BCL3 User Manual
Here you can view all the pages of manual American Water Heater 80 Thermal Efficiency UltraLow NOx Heavy Duty Commercial Gas Water Heater BCL3 User Manual. The American Water Heater manuals for Gas Heater are available online for free. You can easily download all the documents as PDF.
Page 11
11 HIGH ALTITUDE INSTALLATIONS Fire and Explosion Hazard Gas and carbon monoxide detectors ar e available. Overfiring could result in fire or explosion. Under no circumstances should the input exceed the rate shown on the water heater ’s rating label. Breathing Hazard - Carbon Monoxide Ga s Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. Under no circumstances should the input exceed the rate shown on the water heater’s rating label....
Page 12
12 Some addition adjustment maybe required later to maintain a steady gas supply pressure. 5. When installing multiple water heaters in the same gas supply system it is recommended that individual positive lock-up gas pressure regulators be installed at each unit. POWER SUPPLY The water heaters covered in this manual require a 120 VAC, 1Ø (single phase), 60Hz, 15 amp power supply and must also be electrically grounded in accordance with local codes or, in the...
Page 13
13 HOT WATER OUTLET TO TA NK INLET CHECK VA LVE MIXING VA LVE COLD WA TER INLET TEMPERED WA TER OUTLET 12” TO 15” (30-38 cm) CHECK VA LVE FIGURE 10. DISHWASHING MACHINES All dishwashing machines meeting the National Sanitation Foundation requirements are designed to operate with water flow pressures between 15 and 25 pounds per square inch (103 kPa and 173 kPa). Flow pressures above 25 pounds per square inch (173 kPa), or below 15 pounds per square inch (103 kPa), will result in...
Page 14
14 No valve or other obstruction is to be placed between the Temperature-Pressure Relief Valve and the tank. Do not connect discharge piping directly to the drain unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in adequate quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable...
Page 15
15 provide combustion, ventilation and dilution air. Unusually Tight Construction In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of unusually tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.) additional air must be provided using the methods described in the Confined Space section that follows....
Page 16
16 FRESH AIR OPENINGS FOR CONFINED SPACES The following instructions shall be used to calculate the size, number and placement of openings providing fresh air for combustion, ventilation and dilution in confined spaces. The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confined spaces only. DO NOT refer to these illustrations for the purpose of vent installation. See Venting Installation on page...
Page 17
17 When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches. AIR FROM OTHER INDOOR SPACES FIGURE 18. The confined space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. See Figure 18. Each opening shall...
Page 18
18 VENTING INSTALLATION VENTING THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION. This heater is not approved for direct vent installation. Heater must be protected from freezing downdrafts. Remove all soot or other obstructions from the chimney that will retard a free draft. Type B venting is required with these heaters. For typical venting application see TECHNICAL...
Page 19
19 TYPE B GAS VENT Multiple Gas Fired Tank-Type Heaters When venting multiple tank type heaters using Type B vent pipe, follow the installation diagram (figure 13) and tables below which give sizing and data based upon NFPA 54/ANSI Z223. 2006. TABLE 6. TECHNICAL DATA VENTING Model BCL380T1206NOX Input: 120,000 Btu/hrTotal Vent Height (Feet) Vent connector size: 6 inches 6810 15203050100 Input Btu/hr Rise Vent Connector Diameter (Inches) 120,000 1 ft.66555555 120,000 2ft.55555555 120,000...
Page 20
20 TABLE 6. TECHNICAL DATA VENTING (Continued) Model BCL3100T2756NOX Input: 275,000 btu/hrTotal Vent Height (Feet) Vent connector size: 6 inches 6810 15203050100 Input Btu/hr Rise Vent Connector Diameter (Inches) 275,000 1 ft.88877666 275,000 2 ft.88777666 275,000 3 ft.77777666 Number of Heaters Combined Input (Btu/hr) Manifold and Common Vent Diameter (Inches) 2 550,0001010 998877 3 825,0001412121010 998 4 1,100,00014141412121210 9 Model BCL386T3106NOX Input: 310,000 btu/hr Total Vent Height (Feet) Vent...