Home > American Aldes > Ventilation > American Aldes HRVERV Installation User Manual

American Aldes HRVERV Installation User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual American Aldes HRVERV Installation User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 15 American Aldes manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							POINTS TO CONSIDER WHEN LOCATING THE HRV/ERV UNIT
    The Heat or Energy Recovery Ventilator (HRV/ERV) must be installed where temperatures will remain above freezing (32°F). The 
    unit must be installed where it is easily accessible for maintenance and filter changes. The unit should be relatively close to an 
    exterior wall to minimize the length of insulated duct to the exterior vent hoods. The outdoor duct connections must be insulated 
    with a complete exterior vapor jacket to prevent indoor moisture from condensing on the inner duct, which would water-log 
    the insulation layer. The duct connections to the heat exchanger and the exterior vent hoods must be designed to maintain this 
    vapor jacket over the insulation. The fresh air intake must be located approximately six feet or more from any exhaust device, 
    including the discharge from the HRV/ERV. It should not be installed where noxious gases from outdoor sources are likely to be 
    present, such as the exhaust of an automobile in a driveway.
    DUCTING TO THE INTERIOR SPACES - EXHAUST AIR CIRCUIT
    American Aldes recommends using the HRV/ERV to ventilate bathrooms and non-cooking, low exhaust areas in kitchens, pantries 
    and laundry rooms, provided that the duct runs can be accomplished within the recommended distance and availability of wall 
    and ceiling/floor cavities or special chases. If this is possible, the HRV/ERV can do double duty as the local exhaust of these spaces 
    and as general indoor air quality throughout the dwelling. In addition, quiet ventilation of these areas is assured by the remote 
    mounting of the ventilator.
    FRESH OUTDOOR AIR CIRCUIT
    Fresh supply air should be ducted to the bedrooms and main living areas (bedrooms with an attached bath that is being exhausted 
    do not require a dedicated supply, as fresh air will be drawn through the bedroom to the bathroom).
    AMERICAN ALDES DOES NOT RECOMMEND CONNECTING TO FORCED-AIR DUCTING. Contrary to the recommendations of most 
    manufacturers of heat and energy recovery ventilators, American Aldes strongly discourages drawing exhaust air from the return 
    HVAC ducting and supplying the fresh air directly into the HVAC duct system. In the case of both heating and cooling systems, 
    connecting to the ducting can result in severe imbalance of supply and exhaust airflows as the HRV/ERV operates on low to high 
    speeds, as well as the variable speed operation of modern furnaces and air conditioners. It is virtually impossible to assure the 
    design airflows will remain in balance when the two systems are operated at varying blower speeds, and the result is a large 
    variation of static pressure in the HVAC ducting system.
    The exhaust fan in the HRV/ERV is working against the negative pressure in the return plenum. If the return plenum pressure is 
    sufficiently high with the HVAC blower running, it can reduce or even stall the exhaust airflow. At the same time, if the HRV/ERV 
    supplies air to the return plenum, the supply blower has the assistance of the HVAC blower to supply excess fresh air whenever 
    the HVAC system is operating. This situation makes it difficult to assure the HRV/ERV will remain in balance.
    If the HRV/ERV is set up to operate only with the HVAC system, then mechanical ventilation is not provided when most needed – 
    in milder weather but when windows remain closed. Ventilation is likely to be excessive in severe weather when the air handler 
    operates more frequently.
    POINTS TO CONSIDER REGARDING CONTINUOUS OPERATION OF THE HVAC OR FURNACE
    NOTE:  American Aldes uses the term furnace to refer to a forced air heating system and HVAC to refer to a forced air heating and 
    cooling system. In climates where no air conditioning is required, it is possible to exhaust from and supply to the furnace return and 
    operate the furnace blower continuously (although there may be a significant electrical penalty for the continuous operation of the 
    furnace blower 24 hours per day).
    Continuous operation of the HVAC blower is strongly discouraged in climates with warm summers and high humidity, whether or 
    not fresh air is introduced to the system. If the blower continues to run for extended times after the cooling thermostat is satisfied, 
    the water remaining on the coil and in the drain pan re-evaporates. During this time, the air continues to be cooled by the cold AC 
    coil and by the evaporation of water, so the space temperature continues to decrease, while the relative humidity increases. On the 
    next cooling cycle, this humidity has to be condensed again, so any efficiency gain in evaporating this water is offset by the next 
    cycle and by the loss of comfort at higher relative humidity.
    More importantly, in the case of air conditioning, American Aldes does not recommend ducting the supply air from the HRV to the 
    Considerations for Locating, Installing, and 
    Ducting Heat & Energy Recovery Ventilators
    APPLICATION 
    GUIDE 
    						
    							HRV/ERV Considerations
    2
    ducting of the HVAC. (During summer months, the outdoor 
    humidity supplied through the HRV may cause condensation 
    on interior surfaces of the HVAC equipment and the supply 
    plenum and ducting. These surfaces will be around 60°F, and 
    outdoor air dew points in the summer in much of the United 
    States are well above this temperature. These are the very 
    conditions that promote mold growth. It would be ironic if 
    the very system tasked to provide good indoor air quality by 
    means of ventilation were to be the means of promoting mold 
    growth, by lack of attention to basic psychrometric principles.
    THE SOLUTION RECOMMENDED BY AMERICAN ALDES
    The best solution is a totally independent ducted system 
    for the HRV/ERV, with exhaust from the bathrooms, kitchen 
    and laundry/utility rooms, and fresh air ducted to bedrooms. 
    (Bedrooms with attached baths connected to the HRV/ERV 
    exhaust ducting do not need direct supply, as the exhaust of 
    the bath will draw air from the main living areas and hallways 
    through the bedroom to the bathroom exhaust grille.)
    An alternate solution permits fresh air from the HRV/ERV 
    to be supplied to a main living area, where it can be drawn 
    into the return ducting and distributed by the HVAC system 
    throughout the house. A cycle timer can operate the HVAC 
    blower periodically to assure the distribution of fresh air. A 
    cycle timer permits the use of the HVAC system to distribute 
    the fresh air without the need for a dedicated supply duct 
    system. Rather than making a hard connection of the supply 
    air to the return duct of the HVAC system, American Aldes 
    recommends supplying air through a supply diffuser close 
    to a major return grille for the HVAC. This way the fresh air 
    is dispersed in the room, avoiding a high concentration of 
    outdoor humidity in the cold ducting.
    To assure thorough mixing of fresh air throughout the home, 
    use a cycle timer to periodically turn on the HVAC blower a 
    few minutes every hour. This device wires in parallel with 
    the thermostat to periodically operate the blower. It avoids 
    redundant fan operation by starting a timed off-cycle at the 
    end of blower operation for a heating, cooling or previous 
    ventilation cycle. Then it turns on for a few minutes, as set by 
    the installer or occupant. This approach reduces the electrical 
    cost of constant fan operation and reduces draft during the 
    winter, all while assuring good mixing of fresh air throughout 
    the home. (If the occupant intends to operate the central fan 
    continuously, as for an electronic air cleaner, and in those 
    cases where the issues discussed above regarding humidity, 
    comfort and potential of mold growth in the ducting do not 
    apply, then the use of a cycle timer is not necessary.)
    American ALDES Ventilation Corporation  •  4521 19th Street Court East, Suite 104  •  Bradenton, FL 34203 – USA
    941.351.3441  •  800.255.7749  •  941.351.3442 (fax)  •  [email protected]  •  www.aldes.us
    © 2013 American ALDES Ventilation Corporation.  Reproduction or distribution, in whole or in part, of this document, in any form or by any means, without the express written consent of American ALDES Ventilation Corporation, is strictly prohibited. The information contained within this document is subject to change without prior written notice.
    hrv-erv  considerations_application  guide_1113   
    The most desirable configuration. 
    Highly recommended to get the 
    best results in all climate types.
    A hybrid approach that allows 
    the system to be an effective 
    exhaust fan, while taking 
    advantage of the central H/AC 
    duct system to distribute fresh 
    air. Maintaining unit balance is 
    often challenging.
    The least desirable solution 
    because it is difficult to 
    assure balanced airflow 
    and can cause moisture 
    problems in duct during 
    warm, humid seasons. 
    Requires knowledgeable 
    installer.
    Fully Ducted System
    Dedicated Exhaust Points with Distribution of Fresh 
    Supply Air through the Central H/AC System
    Exhaust from H/AC Return and Distribution of Fresh Air 
    through H/AC System 
    						
    All American Aldes manuals Comments (0)

    Related Manuals for American Aldes HRVERV Installation User Manual