Home > American Aldes > Ventilation > American Aldes Finding Acceptable IAQ with ASHRAE 6222013 User Manual

American Aldes Finding Acceptable IAQ with ASHRAE 6222013 User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual American Aldes Finding Acceptable IAQ with ASHRAE 6222013 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 15 American Aldes manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							60Mechanical Business 04.14
     HigH-performance HVac By Gord Cooke                          • Exciting advances  • The influence of buildin\
    g design VENTILATION By Gary Craw                          • Exciting advances  • The influence of buildin\
    g design
    A
    cceptable indoor air quality (IAQ) is dependent on many factors, 
    including indoor pollution sources, construction materials, 
    furnishings, lifestyle of occupants and outdoor air quality. Acceptable 
    IAQ is also impacted by the occupants’ tolerance to indoor pollutants. 
    ASHRAE 62.2-2013 should be used as a starting point for the design of a 
    ventilation system.  
    As ASHRAE 62.2-2013 becomes more prevalent in local and national 
    residential building requirements,  it is helpful for everyone involved to
    
     
    become familiar with the basic ventilation requirements of this standard\
    .  
    ASHRAE 62.2-2013 calls for two mechanical ventilation methods: “whole-
    building ventilation”  and “local exhaust.
    
    ” Both methods need to be used to 
    help achieve acceptable indoor air quality. And keep in mind that ventilation 
    equipment is to be rated in accordance with HVI procedures. Remote-
    mounted fans are not required to be tested or rated for sound.
    ASHRAE 62.2-2013  
    Finding AccE\ftAblE iA\b witH 
    THE STANDARD
    ASHRAE Standard 62.2-
    2013 is a ventilation 
    standard that defines 
    minimum requirements for 
    ventilation systems. The 
    goal of this standard is to 
    achieve acceptable indoor 
    air quality (IAQ) for typical 
    residences. This standard is 
    applicable to single-family 
    houses and multi-family 
    structures of no more than 
    three storeys. The standard 
    does not apply to transient 
    housing such as hotels or 
    dormitories. 
    Whole-Building Ventilation  
    ASHRAE 62.2-2013 has provisions for three basic mechanical   
    ventilation strategies that can be used for Intermittent or continuous  
    whole-building ventilation:  
    1.Exhaust ventilation
    2. Supply ventilation
    3. Balanced supply and exhaust ventilation
    When selecting the whole-building ventilation strategy that is best for \
    an application, 
    consideration should be made for local code requirements, geographic location, special 
    needs of occupants, and specific indoor and outdoor air quality issues\
    . 
    ASHRAE 62.2-2013 assumes that all buildings are tight and, as such, does not allow for 
    the default assumption of two cfm per 100 sq. ft. that the previous editions did. Rather, it 
    requires the use of a blower door to estimate the annual leakage. 
     
    teCh tiP   The airflow of all installed ventilation equi\fment that is used to achieve the whole-\building ventilation rate must \be 
    measured with an a\f\fro\friate airflow measuring device. 
    continues on page 62 
    						
    							Mechanical Business 04.14
    Ensuring a propEr  
    v
    Entilation ratE 
    For intermittently operating whole-buil\fing 
    ventilation systems that run at least once every 
    three hours\b the time average ventilation rate 
    cannot be less than the continuous ventilation 
    rate. If the intermittent ventilation system \futy 
    cycle (one on an\f off time) is longer than three 
    hours\b the require\f ventilation rate increases to 
    achieve an acceptable turnover of the air within 
    the \fwelling.
    62Mechanical Business 04.14
     HigH-perforance HVacBy Gord Cooke                         • Exciting advances  • The influence of buildin\
    g design VENTILATION    • Exciting advances  • The influence of building designcontinued from page 60
    For continuously operating ventilation systems, ASHRAE 62.2-
    2013 provides simple formulas and tables that can be used 
    to determine the minimum whole-building ventilation rates. 
    This minimum ventilation rate is based on the square footage 
    of the dwelling and the number of bedrooms. The number of 
    bedrooms is used to determine typical occupancy levels of the 
    dwelling. 
    This whole-building 
    ventilation rate can be 
    considered the required 
    mechanical ventilation 
    rate. Alternatively, the 
    whole-building ventilation 
    rate may be reduced by 
    up to two-thirds to account for the effective annual average 
    infiltration rate (Qinf). 
    ASHRAE 62.2-2013 provides equations and weather data and 
    describes various methods of testing to determine the Qinf for a 
    specific dwelling.
    Local exhaust 
    A local mechanical exhaust system is require\f to be installe\f in each 
    kitchen an\f in each bathroom. This local system can be \fesigne\f for 
    either continuous or on-\feman\f controlle\f operation. 
    The airflow of all installe\f ventilation equipment that is use\f to 
    achieve local exhaust rates shoul\f be measure\f with an appropriate 
    airflow measuring \fevice. Alternatively\b the airflow rating of 
    ventilation equipment at 0.25” w.c. may be use\f if the prescriptive 
    \fuct sizing of ASHRAE 62.2-2013 is followe\f. 
    The airflow rate of local exhaust systems can also be applie\f to the 
    require\f whole-buil\fing ventilation rate requirements\b as long as they 
    operate automatically.
    For on-\feman\f operating exhaust systems\b the minimum airflow rate 
    is 50 cfm for bathrooms an\f 100 cfm for kitchens.
    For continuously operating exhaust systems\b the minimum airflow rate 
    for bathrooms is 20 cfm. The minimum airflow rate for kitchens is to 
    result in five air changes per hour (base\f on kitchen volume). 
    continues on page 64 
    						
    							64Mechanical Business 04.14
     HigH-perforance HVac By Gord Cooke                          • Exciting advances  • The influence of buildin\
    g design VENTILATION                    • Exciting advances  • The influence of building designcontinued from page 62
    Me\fh Bus News Ad Can\gada_Layout 1  1/23\g/14  1:20 PM  Page \g1E1 Multi HVAC Quar\dter page ad \f4C Mech\da\bical Busi\bess)_Lay\dout 1  2014-
    Working with existing buildings  
    For existing, occupied, buildings that do not meet the provisions of 
    ASHRAE 62.2, an alternative method of compliance is available. 
    1. Local exhaust
    • If existing exhaust ventilation equipment in bathrooms and kitchens 
    does not meet the minimum airflow requirements, the whole-building 
    ventilation rate can be increased to offset the insufficient local exhaust 
    airflow.
    • Existing exhaust ventilation equipment in bathrooms and 
    kitchens does not need to be tested to AMCA standards 
    or rated to HVI procedures.
    • If exhaust ventilation equipment is replaced in bathrooms and kitchens, 
    this equipment needs to meet all requirements of ASHRAE 62.2-2013.
    2. Whole-building ventilation
    • The required ventilation rate for existing buildings may need to be 
    increased to offset insufficient local exhaust.
    • For existing buildings, if the calculated required airflow rate is less than 
    or equal to zero cfm, no whole-building ventilation fan is required.
    ASHRAE 62.2-2013 and mul\fi-family \buildings  
    For mul\fi-family \building
    
    s: 
    1.  Reduc\fions \fo \fhe mechanical ven\fila\fion ra\fe due \fo effec\five
    annual averag e 
    
    infil\fra\fion ra\fe (Qinf ) are no\f permi\f\fed.
    2.   Common areas are \fo \be ven\fila\fed a\f a ra\fe of 0.06 cfm per sq. f\f.
    3.  Non-residen\fial areas of mixed use \buildings are \fo use ASHRAE 62.1.
    4.  Common parking garages \fha\f adjoin occupied spaces are required
    \fo have exhaus\f ven\fila\fion a\f a ra\fe of 0.4 cfm per sq. f\f.
    5.  Specific s\feps need \fo \be \faken \fo minimize \fhe air \fha\f is
    \fransferred \be\fween dwelling uni\fs.
    6.  The following requiremen\fs are in place \fo preven\f air \fransfer
    \fhrough \fhe ven\fila\fion sys\fem:
    •  Exhaus\f fans in separa\fe dwellings shall no\f share a common
    exhaus\f duc\f. 
    •  Exhaus\f inle\fs from  more \fhan one dwelling can use a single exhaus\f 
    fan if \fhe fan 
    
    is loca\fed downs\fream of all of \fhe inle\fs and \fhe fan 
     
    is run con\finuously, or 
    
    if each inle\f has a \backdraf\f damper.
    •  Supply ou\fle\fs \fo more \fhan one dwelling can use a single supply fan 
    if \fhe fan is loca
    
    \fed ups\fream of all of \fhe supply ou\fle\fs and \fhe 
     
    fan is run con\finuously, or if each ou\fle\f has a \backdraf\f damper. G
    ary  Craw  is  Director  of  Engineering  for  American 
    A
    LDES  Ventilation  Corporation  and  a  member-at-large 
    o
    f  the  Home  Ventilating  Institute’s  Board  of  Directors. 
    T
    o learn more, visit  www.aldes.us and  www.hvi.org   
    						
    All American Aldes manuals Comments (0)

    Related Manuals for American Aldes Finding Acceptable IAQ with ASHRAE 6222013 User Manual