American Aldes Aldes SIP Ventilation Design Guide
Have a look at the manual American Aldes Aldes SIP Ventilation Design Guide online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 15 American Aldes manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Section 1 Page 11 Local Ventilation It is generally accepted by building-science experts and most code authorities that local ventilation is necessary to remove high concentrations of bathroom and kitchen pollutants such as humidity, odors, and cooking by-products. As a guideline, ANSI/ASHRAE Standards 62.1 and 62.2 recommend that, if local ventilation is operated intermittently, it must be capable of exhausting a minimum of 50 CFM for each bathroom and 100 CFM for the kitchen. If continuous ventilation is used, the rate is 25 CFM for each bathroom and 50 CFM for the kitchen. Some jurisdictions allow an operable window to substitute for mechanical ventilation in a bathroom. An open window will allow sound to infiltrate. For the purpose of FAA SIP ventilation programs, an operable window is not an allowable alternative to mechanical ventilation. While ASHRAE Standard 62.2 is generally accepted by national experts as the mi\ nimum standard for ventilation, it is not a best practice. If it was, it would assign ventilation rates based on factors such as the number of occupants in a dwelling and the strength of pollutant sources. Refer to local code authorities for jurisdiction-specific requirements. Residential SIP Ventilation Modification Design Guide
Section 1 Page 12 1.5 CLIMATE ZONES The ventilation recommendations outlined in later chapters are heavily influenced by the ASHRAE climate zone in which the structure is located. The continental United States is divided into seven specific climate zones, ranging from Very Hot in Zone 1 to Very Cold in Zone 7, as shown on the map below and in the table that follows. (Hawaii falls under Zone 1A, and parts of Alaska are Zone 8. See Appendix II.) Additionally, most zones are divided into Humid (eastern half of the United States), Dry (most of the western states), and Marine (west coast states) sub-zones. The climate zone and sub-zone dictate which ventilation solution is most appropriate for a dwelling. For example: • Supply ventilation is suitable for a dwelling in Zone 2, but not for one in Zone 7. In Zone 7, the positive-pressure scenario created by a supply system can push humid air into wall cavities, where it can then condensate when meeting colder exterior walls. This condensation can cause mold and mildew issues. • Exhaust ventilation is suitable for Zone 7, but not for a dwelling in Zone 1. In Zone 1, the negative- pressure scenario created by an exhaust system can pull humid air into wall cavities, where it can then condensate on colder interior walls, causing mold and mildew issues. Residential SIP Ventilation Modification Design Guide
Section 1 Page 13 • Balanced ventilation is suitable in all climates since, by definition, it means an equal amount of air is supplied and exhausted from the dwelling and pressure is equalized. However, two fans are required to achieve balanced ventilation. ASHRAE Climatic Zones Climate Zone 1A - Very Hot/Humid Also known as tropical. Temperature is constantly high and does not vary greatly from day to night. High heat and humidity levels make thunderstorms common. Climate Zone 2A - Hot/Humid Also known as tropical. Temperature is constantly high and does not vary greatly from day to night. High heat and humidity levels make thunderstorms common. Climate Zone 2B, Hot/Dry Also known as deserts or semi-deserts. Transition areas between humid, tropical climates and warm, moderate climates. Characterized by low humidity levels (less than 50% RH) and high levels of solar radiation. Overall precipitation is typically low and often falls rapidly over a short period of time. Climate Zone 3A, Warm/Humid Mixed, humid climates experience all four seasons, but season length and extremity vary by location. These regions receive more than 20 inches of rain annually. The average winter temperature typically drops below 45°F. Summers can be extremely hot and humid. Many of these regions will experience some snowfall and icing during winter months. Climate Zone 3B, Warm/Dry Mixed, dry climates experience seasonal temperature variations and typically experience all four seasons. Season length and extremity vary by location. These regions typically receive less than 20 inches of rain annually. Climate Zone 3C, Warm/Marine Temperate climates found on the coast. These areas typically do not have extreme seasons. Temperatures remain relatively mild year-round due to the high heat capacity of water. Marine climates only experience two seasons, summer and winter. Summer months are dry, while winter can be very wet. To be considered a marine climate, 65% of annual total rainfall must occur in less than six months of the year. These climates are generally humid, but moisture and precipitation levels can vary greatly by location. Climate Zone 4A, Mixed/Humid Mixed, humid climates experience all four seasons, but season length and extremity vary by location. These regions receive more than 20 inches of rain annually. The average winter temperature typically drops below 45°F. Summers can be extremely hot and humid. Many of these regions will experience some snowfall and icing during winter months. Climate Zone 4B, Mixed/Dry Mixed, dry climates experience seasonal temperature variations and typically experience all four seasons. Season length and extremity vary by location. These regions typically receive less than 20 inches of rain annually. Climate Zone 4C, Mixed/Marine Temperate climates found on the coast. These areas typically do not have extreme seasons. Temperatures remain relatively mild year-round due to the high heat capacity of water. Marine climates only experience two seasons, summer and winter. Summer months are dry, while winter can be very wet. To be considered a marine climate, 65% of annual total rainfall must occur in less than six months of the year. These climates are generally humid, but moisture and precipitation levels can vary greatly by location. Climate Zone 5A, Cool/Humid Mixed, humid climates experience all four seasons, but season length and extremity vary by location. These regions receive more than 20 inches of rain annually. The average winter temperature typically drops below 45°F. Summers can be extremely hot and humid. Many of these regions will experience some snowfall and icing during winter months. Climate Zone 5B, Cool/Dry Mixed, dry climates experience seasonal temperature variations and typically experience all four seasons. Season length and extremity vary by location. These regions typically receive less than 20 inches of rain annually. Residential SIP Ventilation Modification Design Guide
Section 1 Page 14 Climate Zone 6A, Cold/HumidCold climates include those known as the tundra, taiga, or alpine. These climates are typically found close to the poles and include the majority of Canada, Northern Europe, and Northern Asia. Cold climates can be found at high altitudes in any region of the world. They typically have long, dark winters with short days; however, they can experience large seasonal temperature swings and very warm summers. Snow and ice accumulations are common in most cold climates. Climate Zone 6B, Cold/Dry Cold climates include those known as the tundra, taiga, or alpine. These climates are typically found close to the poles and include the majority of Canada, Northern Europe, and Northern Asia. Cold climates can be found at high altitudes in any region of the world. They typically have long, dark winters with short days; however, they can experience large seasonal temperature swings and very warm summers. Snow and ice accumulations are common in most cold climates. Climate Zone 7, Very Cold Cold climates include those known as the tundra, taiga, or alpine. These climates are typically found close to the poles and include the majority of Canada, Northern Europe, and Northern Asia. Cold climates can be found at high altitudes in any region of the world. They typically have long, dark winters with short days; however, they can experience large seasonal temperature swings and very warm summers. Snow and ice accumulations are common in most cold climates. For specific ventilation solutions based on climate zones, refer to Section 3. For specific climate zones by state and county, refer to Appendix II. Residential SIP Ventilation Modification Design Guide
Section 1 Page 15 1.6 CENTRAL VENTILATION SYSTEMS A central ventilation system can be defined as a centrally located ventilator specifically designed to provide controlled movement of air in and out of the building for general ventilation. The purpose of a central ventilation system is to provide a continuous low-level flow of air in and out of the building to ensure a safe environment for the occupants and protect the structural i\ ntegrity of the building. A central ventilation system provides low-level continuous flow using one of three methods: supply, exhaust, or balanced. These methods are explained in more detail in Section 2. The continuous low-level flow of air removes and dilutes the pollutants commonly found in buildings. A central ventilation system should not to be confused with a central heating and air conditioning handling unit (AHU). The differences between the two are explained in Section 1.7. Advantages of Central Ventilation Systems • Lower installed cost • Better performance • Significant energy savings from precise ventilation rate control and ENERGY STAR rated ventilators • Precisely controlled ventilation rates with very effective air distribution • Minimal penetrations in the building envelope (no more than two for balanced operation) Local ventilation, such as bathroom and kitchen fans, is designed to remove the high levels of humidity, odors, and other pollutants that are typically created by an event such as taking a shower or cooking. This type of ventilation eliminates most of these pollutants at the source, but it does not capture it all. Moreover, local ventilation methods do not have the distribution efficiency to provide the whole-house continuous ventilation that tight buildings need. Hybrid central ventilation systems provide continuous low- level ventilation for the entire home, as well as local ventilation for kitchens and bathrooms, if necessary. Balanced Ventilation System Local (Exhaust) Ventilation System Residential SIP Ventilation Modification Design Guide
Section 1 Page 16 1.7 DIFFERENCES BETWEEN VENTILATION AND HVAC/AC UNIT It is a common misconception that the home’s central heating and air conditioning handling unit (AHU) provides ventilation. In fact, the AHU is designed to recirculate existing indoor air through the air- conditioning and/or heating units. This is a closed system that neither exhausts pollutants nor supplies fresh air to the home. Ventilation is the process by which “clean” air (usually outdoor air) is intentionally provided to a space, and stale air is removed. This process is usually accomplished mechanically, but it can occur naturally in rare cases and under specific circumstances. Most confusion can be attributed to the typical installation of the AHU by Heating, Ventilation, and Air- Conditioning (HVAC) contractors, as well as the assumption that air movement equals ventilation. Proper ventilation strategies are dependent upon the climate zone in which a home or building resides. To select the best ventilation strategy for a particular building, consider the regional climate zone and the project budget. Air Handling Unit Residential SIP Ventilation Modification Design Guide
Section 1 Page 17 1.8 VENTILATING WITH AN AHU Using a fresh air duct to provide supply ventilation via the central heating and air conditioning \ handling unit (AHU) is not recommended, except in very limited circumstances (Refer to Section 2.2 for recommen\ ded supply air solutions). AHU are designed to respond to thermostat requests. They will not respond to ventilation requirements without special equipment. Disadvantages of Ventilating with an AHU: • Unregulated amount of air being pulled into the building envelope • Potential damage to gas heat exchangers • Creates drafts and thermal discomfort in the winter • Excess condensation in A/C ducting during warm-moist seasons can cause water to blow off coils, potentially causing mold to form in duct systems • No filtration of incoming air • Continuous operation of AHU to provide proper ventilation (even in non-cooling/heating seasons) can result in excess energy expense • Difficult to calibrate and deliver recommended ventilation rates • Unsuitable for cold climates (due to the positive-pressure scenario, as\ explained on page 21) Fresh Air Air Handler Ventilating with an AHU Residential SIP Ventilation Modification Design Guide
Section 1 Page 18 1.9 OTHER INSTALLATION CONSIDERATIONS FOR RETROFIT PROJECTS When introducing a continuously operating appliance to a home that did not have one previously, consider the following: • The appliance should be silent • The appliance should be ENERGY STAR rated • The appliance should be low maintenance Residential SIP Ventilation Modification Design Guide
Section 2 Page 19 SECTION 2 COMMON MECHANICAL VENTILATION METHODS 003500480056004C0047004800510057004C0044004F00030036002C0033
Section 2 Page 20 2.1 CONTINUOUS EXHAUST • A fan brings in outside air by creating negative pressure inside the building • Good for source contaminant removal • Requires dedicated air-intake points to direct outside air to habitable spaces • ENERGY STAR rated fan recommendedCentral Exhaust Fan Exhaust Air Outlet Air Flow Air Infiltration Positive Air Pressure Negative Air Pressure Exhaust Ventilation Types of Equipment* In-Line Fan (VS) Multi-Port Fan (MPVS) Air Inlets *Remote-mounted fans are preferred for noise-free operation Pros • Central systems can combine spot (bathroom) exhaust and whole-building ventilation • Low power consumption • Relatively low cost • Good for Climate Zones 2B, 3B, 3C, 4B, 4C, 5A, 5B, 6A, 6B, 7A & 7C (see pages 12-14) Cons • Potential to backdraft appliances and fireplaces • Cannot effectively filter incoming air • Cannot use in Climate Zones 1, 2A, 3A, and 4A (see pages 12-14) • Not suitable for use in warm-humid climates. • Warm, moist air will condense on cold surfaces in walls and leakage areas in building envelope Residential SIP Ventilation Modification Design Guide