Home > AirComm Corporation > Other > AirComm Corporation Cessna Citation 500 501 Maintenance Manual

AirComm Corporation Cessna Citation 500 501 Maintenance Manual

    Download as PDF Print this page Share this page

    Have a look at the manual AirComm Corporation Cessna Citation 500 501 Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 74 AirComm Corporation manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Products, Inc  
     Maintenance Manual 
     
     
        
       
    21-50-00
    May 15/95
    Page 2
    Two evaporator/blower units are located in the aft cabin at the spar (at floor level) 
    within the aircraft interior.  They  provide cooling airflow for the cabin  and cockpit 
    areas of the interior.  The left evaporator is ducted to provide cooling airflow to the 
    flight crew through a floor mounted air outlet or through dedicated ducting at the 
    pilots and co- pilots control stick.  The right evaporator is ducted to provide cooling 
    airflow to the aft cabin through a floor mounted air outlet.  Both evaporators are of a 
    design wherein the cabin air is drawn into the evaporator coil and the fan then 
    delivers the conditioned air to the cabin.  This recirculating system continues to dry 
    and cool the air each time it passes through the evaporator.  Moisture removed from 
    the air by the cold coil (condensate) is collected within the evaporator housing and is 
    forced overboard.  Each evaporator is equipped with a thermal expansion valve 
    which regulates the amount of refrigerant entering the coil to provide optimum cooling 
    effect.  The evaporator blowers can be operated in the FAN position to recirculate 
    cabin air without cooling.  Each blower is operated from an independent  fan speed 
    control. 
     
    The plumbing which connects the compressor, condenser and the evaporators, 
    consists of rubber based hoses with a nylon barrier.  The fittings are permanently 
    swaged onto the hoses.  All fittings are o-ring type  connections with sealant on the 
    fitting mating surfaces to prevent refrigerant leaks.  Two R134a service valves are 
    located near the compressor/condenser pallet assembly.  They are sized differently 
    to avoid incorrect cross-connecting when gaining access to the plumbing for system 
    recharging. 
     
    On the ground, the electrical system allows operation of the air conditioning system 
    from either aircraft generator or from an active GPU prior to engine start. System 
    safety features include electrical interlocking and load shedding.  In flight, the air 
    conditioning system can be operated from the aircraft electrical system only with both 
    generators on line.  Loss of either generator will automatically shed the air 
    conditioning system electrical loads except for the minimal loads of the evaporator 
    fans. 
     
    The entire air conditioning refrigerant loop is protected against over pressure 
    conditions by two separate safety devices.  The first device is a binary high/low 
    pressure switch that activates in the event of an overpressure and is on the 
    compressor discharge port.  This switch will open at approximately 350 PSIG and will 
    interrupt power to the compressor control circuit.  This in turn will de-energize the 
    compressor motor relay and remove power to the compressor motor.  The refrigerant 
    system pressures will then drop. The switch will also interrupt power to the 
    compressor control circuit under low pressure conditions.   The second overpressure 
    safety device is a fuse plug which will vent the system refrigerant safely overboard in 
    the event of a system pressure in excess of 425 PSIG.  It is located on the 
    receiver/drier.    
    						
    							Products, Inc  
     Maintenance Manual 
     
     
        
       
    21-50-00
    May 15/95
    Page 3
     
     
     
     
    Figure 1. Air Conditioning System General Arrangement 
      
    						
    							Products, Inc  
     Maintenance Manual 
     
     
     
     
     
     
    21-50-01
    May 15-95
    Page 1
     ELECTRICAL 
     
    DESCRIPTION AND OPERATION 
     
    1. GENERAL 
     
    The air conditioning system consists of one high energy compressor/condenser 
    drive motor and two centrifugal evaporator blowers.  The system is controlled by a 
    mode switch with Air Conditioning Off and Fan Only position.  Each evaporator has 
    a high and low position switch.  A blue indicator light will illuminate whenever the 
    compressor/condenser is selected.  The system incorporates a binary pressure 
    switch to sense an over pressure or under pressure condition in the system.   
     
    The air conditioning system in controlled by a Logic Card which monitors generator, 
    GPU and battery inputs to ensure operation or shedding of the system if a fault 
    exists.  
     
    The system is protected by a 15 amp control and blower breaker and a 100 amp 
    breaker for the compressor/condenser drive motor. 
     
    This section of the maintenance manual describes the electrical system  and 
    presents electrical troubleshooting  procedures.  An  Illustrated Parts List is included 
    in Figure 1.   
     
    2. LOAD/SHED DESCRIPTION 
     
    The system incorporates a logic control PC card that enables the system to operate 
    or be shed under various conditions.  The table below shows operation under 
    various conditions. 
     
    CONDITIONS
         EVAP FANS   COMP/COND 
    Gnd Power Cart/On    On      On 
    Gnd Power Cart Connected/Off    On      Off      
    Battery Only     On   Off 
    One Generator on Ground    On      On 
    Both Generators on ground    On      On 
    Refrigerant Over/Under Pressure    On      Off 
    One Generator in Flight    On      Off 
    Both Generators in Flight    On      On  
    						
    							Products, Inc  
     Maintenance Manual 
     
     
      
     
    21-50-01
    May 15/95
    Page 101
     
    TROUBLESHOOTING 
     
    1. GENERAL 
     
    The following procedures are used for troubleshooting the electrical system and the 
    electrical interfaces with the other assemblies of the air conditioning system. 
     
    2.  TOOLS AND EQUIPMENT 
     
     
    Designation  
    Ref. No.  
    Qty  
    Remarks 
     
     
    Service Pressure Gauge  
    Comm. Avail.  
    1  
    None 
     
    Multi-meter  
    Comm. Avail.  
    1  
    None 
     
    28vdc Source  
      
    A/R  
    None 
     
    3. ELECTRICAL TROUBLESHOOTING PROCEDURES (REF. IPL Fig. 1) 
     
    NOTE:   Always attach a service gauge set to system prior to beginning trouble 
    shooting to insure proper refrigerant charge is present. 
     
    A.  Air Condition Selected, Compressor/Condenser Motor Does Not Turn. 
     
    1.  Connect service pressure gauge to service ports located near 
    compressor/condenser pallet. 
    2.  Connect ground power to aircraft. 
    3.  Select air conditioning system to ON. 
    4.  Check that load shed start conditions in the Description and Operation 
    paragraph are met. 
    5.  Check for power at comp/cond relay located on the pallet assembly , if not 
    present check 100A circuit breaker (3)  Replace if necessary. 
    6.  Check continuity of pressure switch (Ref. 21-50-02 IPL Fig. 1 item 11).  If 
    no continuity and gauge set reads adequate pressure, replace pressure 
    switch.  Switch can be removed without discharge of refrigeration.  Back 
    switch off in a counter clockwise direction.  Re-install in reverse order.  
    Lubricate o-ring in switch per 21-50-02 page 202.  
    						
    							Products, Inc  
     Maintenance Manual 
     
     
      
     
    21-50-01
    May 15/95
    Page 102
     
    7.  Check for power at motor .  If power is present, proceed to step 8.  If power 
    is not present on either pin and load/shed conditions of step 4 are met, 
    check power on the load shed unit at connector Pin 1.  If power is present, 
    system problem exists in load shed system start unit.  If power is not 
    present, check 15 amp CB (4) and mode switch (6). 
    8.  Fault is isolated to compressor/condenser motor.  Unit should be replaced. 
    9.  Select air conditioning OFF, remove electrical power, disconnect service 
    gauge when troubleshooting is complete. 
     
    B.   Left Evaporator Blower will not operate in high or low speed.  
    1.  Connect ground power to aircraft. 
    2.  Select air conditioning system to ON. 
    3.  Check if power and ground present at fan wire splices and GND terminal 
    strip.   If power and ground are present, blower motor (Ref. 21-50-04 IPL 
    Fig.1, item 22) has failed.  
    4.  Select air conditioning OFF, remove electrical power. 
    5.  Remove blower assy from aircraft.  Remove the four screws attaching the 
    motor to the housing.  Using a 1/8 allen wrench remove blower wheel ( use 
    extreme care not to bend blower wheel). Cut power wires at splice and 
    remove Gnd wire from GND terminal. Install new motor in reverse order. 
     
    C.  Left Evaporator Blower will not operate in the low speed setting.  
    1.  Connect ground power to aircraft. 
    2.  Select air conditioning system to ON. 
    3.  Check if power is present at wire EVAP-FL ( at splice).  If power is present, 
    the low speed resistor (Ref. 21-50-04 IPL Fig. 1, item 21) has failed. 
    4.  Select air conditioning OFF, remove electrical power. 
    5.  Remove blower assembly and using a #21 drill  remove the two rivets 
    securing the resistor. Cut the wires at the splice and remove GND wire 
    from GND terminal.  Install new resistor in reverse order. 
     
    D.   Right Evaporator Blower will not operate in high or low speed.  
    1.  Connect ground power to aircraft. 
    2.  Select air conditioning system to ON. 
    3.  Check if power and ground present at fan wire splices and GND terminal 
    strip.   If power and ground are present, blower motor (Ref. 21-50-04 IPL 
    Fig.1, item 22) has failed.  
    4.  Select air conditioning OFF, remove electrical power.  
    						
    							Products, Inc  
     Maintenance Manual 
     
     
     
     
     
     
    21-50-01
    May 15/95
    Page 103
     
    5.  Remove blower assy from aircraft.  Remove the four screws attaching the 
    motor to the housing.  Using a 1/8 allen wrench remove blower wheel ( use 
    extreme care not to bend blower wheel).  Cut power wires at splice and 
    remove Gnd wire from GND terminal.  Install new motor in reverse order. 
     
    E.  Right Evaporator Blower will not operate in the low speed setting.  
    1.  Connect ground power to aircraft. 
    2.  Select air conditioning system to ON. 
    3.  Check if power is present at wire EVAP-AL ( at splice).  If power is present, 
    the low speed resistor (Ref. 21-50-04 IPL Fig. 1, item 21) has failed. 
    4.  Select air conditioning OFF, remove electrical power. 
    5.  Remove blower assembly and using a #21 drill  remove the two rivets 
    securing the resistor.  Cut the wires at the splice and remove GND wire 
    from GND terminal.  Install new resistor in reverse order. 
     
     
     
     
     
     
     
     
     
        
    						
    							Products, Inc  
     Maintenance Manual 
     
     
     
     
     
     
    21-50-01
    May 15/95
    Page 1001
     
     
    Figure 1.  Electrical System  
    						
    							Products, Inc  
     Maintenance Manual 
     
     
     
     
     
     
    21-50-01
    May 15/95
    Page 1002
     
    FIG. ITEM  
     PART 
     NUMBER  
     NOMENCLATURE  
     EFFECT  
     UNITS  
     PER  
     ASSY 
     
    1 1 
     
     2 
     
    3 
     
    4 
     
    5 
     
    6 
     
    7 
     
    8 
     
    9 
     
    10 
     
    11 
     
    12 
     
    13 
     
    14 
     
    15  
    82-75-103 
     
    JBS5005-2 
     
    MS25361-100 
     
    MS3320-15 
     
    ES57016-6 
     
    ES57016-5 
     
    ES57016-3 
     
    JBS275-2 
     
    JBS13001-1 
     
    ES32036-1 
     
    JBS11001-1 
     
    ES50162-1 
     
    MS25036-106 
     
    MS25036-156 
     
    MS25036-125 
     
      
    Electrical Installation  
     
    Compressor/Condenser 
     
    Circuit Breaker 
     
    Circuit Breaker 
     
    Switch 
     
    Switch 
     
    Switch 
     
    Blower R/H 
     
    Blower L/H 
     
    Grommet 
     
    Light Indicator 
     
    Lamp 
     
    Terminal  
     
    Terminal 
     
    Terminal 
     
      
     
      
     RF 
     
    1 ref 
     
    1 
     
    1 
     
    1 
     
    1 
     
    1 
     
    1 ref 
     
    1 ref 
     
    1 
     
    1 
     
    1 
     
    1 
     
    1 
     
    1 
     
     
     
     
     
    Air Conditioning System - Electrical System 
    IPL FIGURE 1  
    						
    							Products, Inc  
     Maintenance Manual 
     
     
     
     
     
     
    21-50-01
    May 15/95
    Page 1003
     
    FIG. ITEM  
     PART 
     NUMBER  
     NOMENCLATURE  
     EFFECT  
     UNITS  
     PER  
     ASSY 
     
     16 
     
     17 
     
     18 
     
     19 
     
     20 
     
    21 
     
    22 
     
    23 
     
    24 
     
    25 
     
      
    MS25036-123 
     
    MS25036-157 
     
    MS25181-2 
     
    ES58161-15 
     
    84-00-07-8 
     
    ES53010-3 
     
    MS25036-108 
     
    MS25036-101 
     
    MS25036-124 
     
    ES55077-2  
    Terminal 
     
    Terminal 
     
    Connector, Butt 
     
    Diode 
     
    Load Shed Assy 
     
    Connector 
     
    Terminal 
     
    Terminal 
     
    Terminal 
     
    Terminal 
     
     
     
     
     
     
     
     
     
     
     
      
      
     3 
     
     1 
     
     7 
     
     1 
     
     1 
     
    1 
     
    1 
     
    1 
     
    1 
     
    1 
     
     
    Air Conditioning System - Electrical System 
    IPL FIGURE 1  
    						
    							Products, Inc  
     Maintenance Manual 
     
     
       
     
       
    21-50-02
    May 15/95
    Page 1
     PLUMBING 
     
    DESCRIPTION AND OPERATION 
     
    1. GENERAL 
     
    The plumbing system consists of a flexible nylon lined refrigerant hose with 
    permanent swaged on fittings.  All connections are tube O-ring type with sealant on 
    the fitting mating surfaces to ensure leak free operation.  Hose,  O-ring material, and 
    sealant are specially designed to work with refrigerant R134a and polyol ester oils.  
    Two service valves are located near the compressor/condenser assembly.   They 
    are sized differently to avoid incorrect cross-connecting when gaining access to the 
    plumbing for system recharging.  A receiver/drier is installed downstream of the 
    condenser to remove moisture from the liquid refrigerant.   A binary pressure switch 
    monitors the refrigerant gas pressure.  This switch will open at a condenser over 
    pressure of 350 psi and under pressured conditions of 30 psi.  This will interrupt the 
    power to the compressor control circuit and stop the compressor. 
     
    This section of the maintenance manual discusses checks and maintenance 
    practices used for the plumbing portion of the air conditioning system.  An  
    Illustrated Parts List is included in Figure 1.   
    						
    All AirComm Corporation manuals Comments (2)

    Related Manuals for AirComm Corporation Cessna Citation 500 501 Maintenance Manual