Page 31
AIR CONDITIONER SERVICE MANUAL A119-206M-1 Revision 12 Page 25 CHAPTER 6 SERVICING 1. Safety Precautions CAUTION Refrigeration servicing should be performed by qualified personnel only. The refrigerant used in the air conditioning system is the environmentally safe HFC R134a. This refrigerant is non-explosive, non-flammable, and non-corrosive, has practically no odor, and is heavier than air. Although R134a is classified as a safe refrigerant, certain...
Page 32
AIR CONDITIONER SERVICE MANUAL A119-206M-1 Revision 12 Page 26 hold a vacuum, the system has a fitting leak). It may be necessary to charge the system with one or two lbs. (.45 to .86 Kg.) of refrigerant and conduct a leak check survey using an electronic leak detector. CAUTION It is mandatory that the system be leak free to insure trouble free operation. Continuous operation of the system with insufficient charge will result in reduced compressor life. D. After the system is...
Page 33
AIR CONDITIONER SERVICE MANUAL A119-206M-1 Revision 12 Page 27 4.0 fl. oz. (118.8 ml.) of oil must be added at the time of the system installation. This oil should be added to the compressor discharge line prior to system charging. If oil is spilled during installation / maintenance, or is lost due to a leak in the system, it is necessary to approximate the amount of lost oil and add this amount to the system. The oil charge is continuously circulated by the refrigerant during the...
Page 34
AIR CONDITIONER SERVICE MANUAL A119-206M-1 Revision 12 Page 28 NOTE Ensure that the O-ring is lubricated with refrigerant oil prior to its installation. A small amount of leakage (approximately one ounce per year) past the compressor shaft seal is normal. Most leak detectors are sensitive enough to show a leak of this magnitude. 5. Suggested Equipment for Servicing Recovery / Recycling / Recharging Station (Example: Snap-on Model ACT 3340, Robinair...
Page 35
AIR CONDITIONER SERVICE MANUAL A119-206M-1 Revision 12 Page 29 7. Suggested Spares List Item Part Number Effectivity Blower Motor – Fwd. Evaporator ES61064-1 Blower Motor – Aft Evaporator ES61142-1 Blower Assembly – Condenser A119-7008-1 Kit S/N 90 and subsequent S-6501EC-3 (alt.) Compressor Assembly A119-3040-1 Compressor Drive Belt ES35119-2 Receiver / Drier Bottle ES43030-5 Binary Switch ES57178-1 By-pass Valve ES26194-24 Blower Assembly – Condenser (Standard)...
Page 36
AIR CONDITIONER SERVICE MANUAL A119-206M-1 Revision 12 Page 30 THIS PAGE INTENTIONALLY LEFT BLANK
Page 37
AIR CONDITIONER SERVICE MANUAL A119-206M-1 Revision 12 Page 31 CHAPTER 7 STANDARD PRACTICES AND INFORMATION 1. Fitting Torque Procedures and Values INSERT O-RING FITTINGS Torq Lok FITTINGS Apply a thin coating of refrigerant oil to O-ring and Female side of fitting. Confirm there is no damage (nicks, dirt, etc.) on fittings. Slide B-nut back away from the end of the tube so you can see the O-ring as you slide the fitting together. Be careful not to pinch O-ring...
Page 38
AIR CONDITIONER SERVICE MANUAL A119-206M-1 Revision 12 Page 32 2. Removal and Replacement of Forward Evaporator Assembly (Figure 4-6) NOTE It will be necessary to evacuate (discharge) refrigerant from the system to remove or replace forward evaporator assembly. Instructions for servicing are found in Chapter 6. Removal a. Disconnect refrigerant plumbing from evaporator fittings once refrigerant is evacuated. Always use a back-up wrench. Cap open lines to prevent...
Page 39
AIR CONDITIONER SERVICE MANUAL A119-206M-1 Revision 12 Page 33 4. Removal and Replacement of Aft Evaporator Assembly (Figure 4-7) NOTE It will be necessary to evacuate (discharge) refrigerant from the system to remove or replace aft evaporator assembly. Instructions for servicing are found in Chapter 6. Removal a. Disconnect refrigerant plumbing from evaporator fittings once refrigerant is evacuated. Always use a back-up wrench. Cap open lines to prevent...
Page 40
AIR CONDITIONER SERVICE MANUAL A119-206M-1 Revision 12 Page 34 r. Connect air box assembly to blower outlet with attaching hardware. s. Connect flex duct from evaporator assembly and secure with cable ties. 6. Removal and Replacement of Air Box Assembly (Figure 4-7) Removal a. Remove fresh air flex duct coming from fresh air box by removing cable ties at air box assembly inlet. b. Remove attaching hardware securing air box assembly inlet to aft evaporator blower assembly outlet. c. Remove...