Home > AirComm Corporation > Air Conditioner > AirComm Corporation Bell 429 Air Conditioning 429EC200M1Rev9 User Manual

AirComm Corporation Bell 429 Air Conditioning 429EC200M1Rev9 User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual AirComm Corporation Bell 429 Air Conditioning 429EC200M1Rev9 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 74 AirComm Corporation manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 
    Revision 9 Page 33 
     
     
     
    Figure 25:  Aft Evaporator Drain Line Routing, Dual Evaporators 
     
     
     
     
     
    Figure 26:  Aft Evaporator Drain Line Routing, Single Evaporators 
     
       
    						
    							AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 
    Revision 8 Page 34 
     
    CHAPTER 5 
    PLACARDS AND MARKINGS 
    1. Placard and Marking Information 
     
     
    All  placards  and  markings  associated  with  the  installation  of the  air conditioner  system  are  part 
    of  the  type  design  of  this  helicopter.  Please  refer  to  the  Bell Helicopter  Instructions  for 
    Continued Airworthiness Manual for placards and markings information. 
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
    THIS AREA INTENTIONALLY LEFT BLANK 
     
      
    						
    							AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 
    Revision 9 Page 35 
    CHAPTER 6 
    SERVICING 
    1. Safety Precautions 
     
    CAUTION 
    Refrigeration  servicing  should  be  performed  by  qualified  personnel  only. 
    Check  all  local  and  federal  regulations  before  servicing  any  refrigerant 
    system or storage device. 
     
    The  refrigerant  used  in  the  air  conditioning  system  is  the  environmentally  safe  HFC 
    R134a.  This  refrigerant  is  non-explosive,  non-flammable,  and  non-corrosive,  has 
    practically  no  odor,  and  is  heavier  than  air. However,  certain  precautions  must  me 
    observed to ensure the safety of the equipment and any personnel servicing this system. 
     
    HFC R134A  is  stored  in  a  liquid  state.  It  will  rapidly  evaporate  or  sublimate  when 
    exposed  to  normal  temperature  and  atmospheric  pressure.  This  rapid  evaporation  can 
    causes  a  severe  drop  in  temperature. If  liquid  refrigerant  comes  in  contact  with  the  skin 
    or eyes it may cause severe frostbite or blindness. Care must be taken to prevent liquid 
    refrigerant from contacting the skin or the eyes. 
     
    WARNING 
    Safety  glasses  must  be  worn  at  all  times  when  servicing  the  air 
    conditioning  system. Should  any  liquid  refrigerant  come  in  contact  with 
    the  skin  or  eyes  seek  medical  attention  immediately  even  if  the  irritation 
    ceases. 
     
    WARNING 
    To  avoid  a  potential  explosion  NEVER  weld,  solder, steam  clean,  use  a  flame 
    type  leak  detector,  blow  torch,  bake  on  aircraft  finish, or  use excessive heat on, 
    or in the immediate area of refrigerant lines or supply tanks while they are closed 
    to the atmosphere. 
     
    WARNING 
    Refrigerant  servicing  must  be  performed  in  a  well-ventilated  area  to 
    minimize inhalation of the refrigeration gas. 
     
    2. Servicing Information 
     
    CAUTION 
    Refrigeration servicing should be performed by qualified personnel only. 
     
    NOTE 
    A list of suggested servicing equipment is provided later in this chapter. 
     
    2.1 Servicing Procedure using a Service Cart 
     
    A. Connect the servicing manifold to the servicing ports located on the forward R/H side of 
    the  transmission  deck.  BLUE  for  low  pressure  or  “Suction”  and  RED  for  high  pressure 
    or “Discharge.”  
    						
    							AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 
    Revision 9 Page 36 
     
    B. After  the  quick  disconnect  fittings  have  been  attached  to  the  servicing  ports,  tighten  the 
    knobs on  the  back  of  the  fittings  to  engage  the Schrader  valves  located  inside  the 
    charging ports. 
     
    NOTE 
    The Schrader valves inside the charging ports MUST be engaged to allow 
    servicing of the air conditioner system. 
     
    C. Connect  the  YELLOW  line  in  the  center  of  the  manifold  to  the  vacuum  pump.  Turn  the 
    vacuum  pump  on and  open  both  valves  on  the  charging  manifold.  Decreasing  the 
    pressure  in  the  closed  system  to -29.40  InHg  causes  the  moisture  in  the  system  to 
    vaporize  allowing  it  to  be  drawn  out  by  the  vacuum  pump.  Removal  of  all  moisture  is 
    crucial to the operation of the A/C system. Any moisture left in the system will be turned 
    into ice causing undesired operation or blockage of one or more expansion valve. Allow 
    the vacuum pump to draw against the system for a minimum of ONE HOUR. 
     
    NOTE 
    Due  to  a  drop  in  atmospheric  pressure  with  an  increase  in  altitude,  the 
    normal  vacuum  reading  will  drop  1”  (1  kg/cm)  for  each  1000  ft  of  altitude 
    gained  e.g., Sea  Lever  Reading  =  10  InHg,  reading  at  1000  feet  above 
    sea level = 9 InHg. 
     
    D. After the system has been evacuated, turn both valves on the manifold assembly to the 
    “OFF”  position  and  switch  the  vacuum  pump  off.  Allow  the  system  to  hold  the  vacuum 
    for  a  minimum  of ONE  hour  to  check  for  vacuum  leaks. If  the  system  will  not  hold  the 
    vacuum, the system may have a fitting leak. It may be necessary to charge the system 
    with one to two pounds of refrigerant and conduct a leak check using an electronic leak 
    detector. 
     
    CAUTION 
    To ensure trouble free operation the system must be leak free. 
     
    E. After the leak check has been performed evacuate the system for a minimum of ½ hour 
    before charging per the levels below: 
     
     429 air conditioning system with dual Fwd evaporators, 2.7 lbs (1.2247 Kg) of 
     refrigerant. 
     429 air conditioning system with single Fwd evaporator, 2.5 lbs (1.1340 Kg) of 
     refrigerant. 
     
    NOTE 
      Static charging is the most accurate and safest way to charge an air conditioning  
      system. To accomplish this all 2.7 Lbs. of refrigerant must be charged into the  
      system without the compressor engaged or the system operating. If the 
      system must be serviced with the compressor running, servicing must be   
      performed through LO (BLUE) side only! Please make sure that the HIGH (RED)  
      side valve stays closed during this procedure and any time the system is   
      operating. Never Charge through the Discharge or “HIGH” (RED) side of the  
      system while the compressor is running as this may cause severe damage to the 
      compressor Assy.  
    						
    							AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 
    Revision 9 Page 37 
     
     
    CAUTION 
    Operating  the  air  conditioning  system  with  a  low  refrigerant  charge  may 
    cause severe damage to the compressor assembly. 
     
    F. After  charging,  perform  a  test  run  to  ensure  proper  function  of  the  Air  Conditioning 
    System. 
     
     
          2.2 Servicing Procedure without using a Service Cart 
    A. The following tools & materials will be required: 
     1. R134a Manifold Gauge Set 
     2. 3 pound bottle of R134a 
     3. Refrigerant Scale to weigh the refrigerant bottle 
     4. Vacuum Pump capable of maintaining 29in Hg of mercury at sea level 
     5. Ultra PAG oil 
     
    B. Charging procedure: 
     Note that the following steps 1 through 7 are to be accomplished while the aircraft 
     and air conditioning system are “OFF”. 
      
     1. Connect the servicing lines from the manifold gauges to the servicing ports located on 
         the forward R/H side of the transmission deck. The BLUE port is for low pressure  
         (suction) and the RED port is for high pressure (discharge). 
      
     2. After the quick disconnect fittings have been connected to the servicing ports, tighten 
         the knobs on the back of the fittings to engage the Schrader valves located inside the        
         charging ports. If the knobs are not properly tightened, the Schrader valve inside of     
         the ports will not engage. 
     
     3. To ensure there is no air or moisture in the system, use the Manifold Gauges and 
         Vacuum Pump to pull the system down on a vacuum continuously for a minimum of 1     
          hour. To perform this, connect the YELLOW line in the center of the manifold to the   
         vacuum pump. Turn the Vacuum pump on and open both valves on the charging   
         manifold until the pressure has decreased to 29.40 in Hg. 
     
     4. After 1 hour of vacuuming and while the vacuum pump is still working, close both   
         valves on the manifold gauge set and watch the High and Low pressure gauges to   
         ensure the system pressures remain constant or “vacuumed.” If the system does not   
         hold a vacuum it has a leak. 
     
     5. Once the system has been proven to be “Leak Free,” disconnect the vacuum pump   
         and connect the refrigerant bottle to the manifold gauge set. 
     
     6. Purge the line between the refrigerant bottle and manifold gauge by opening the knob 
         on the refrigerant bottle. Then, loosen the line at the manifold slightly to allow the   
         refrigerant to push the air out. This will verify that there is no air in the line. 
     
     7. Charge the system by opening the low side and high side valves which will allow    
    						
    							AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 
    Revision 9 Page 38 
         the initial charge of 2.0 pounds to be added. This can be measured and tracked by  
         placing the bottle on a scale. 
     
      
     Note that the following step 8 is to be accomplished while the aircraft is running at 
     100%  and the air conditioning system is “ON”. Ensure that the High side (RED) 
     is closed at all times while system is operating.) 
     
     8. Add the remainder of the required charge in 0.2 lb. increments by opening the low   
        side (BLUE) slightly to allow the refrigerant to be drawn in. Allow two minutes       
        to elapse between each addition of refrigerant. The amount entering the        
        system can be verified by monitoring the scale as the refrigerant is added. Note that  
        the compressor can be damaged if an excessive amount is added. Charge the system     
        as listed  below: 
     
        429 air conditioning system with dual Fwd evaporators, 2.7 lbs (1.2247 Kg) of   
        refrigerant. 
        429 air conditioning system with single Fwd evaporator, 2.5 lbs (1.1340 Kg) of   
        refrigerant. 
     
    WARNING 
    If charging is to be accomplished with the compressor engaged it must be 
    accomplished  through  the  LO  (BLUE)  side  only. Never  Charge  through 
    the  Discharge  or  “HIGH”  (RED)  side  of  the  system  while  the 
    compressor  is  running. This  may  cause  severe  damage  to  the 
    servicing  equipment  and  may  cause  personal  injury  or  death.  Care 
    should be taken to ensure the HIGH (RED) side valve stays closed during 
    this procedure and any time the system is operating. 
     
    CAUTION 
    When  reclaiming  refrigerant,  be  sure  to  note  any  oil  that  is  removed  from  the  system,  and 
    replace the  lost  oil  before  or  during  re-servicing.  Maintaining  a  proper  oil  and  refrigerant 
    charge  is  critical  to  the  life  of  the  compressor  assembly. Excessive  system  oil  charge  will 
    reduce cooling performance. 
     
     
    2.3 Ambient Temperature effects on servicing 
    Running  the  system  when  the  ambient  temperature  is  below  80 OF  will  present  unusual 
    (low) suction and discharge pressures on system gauges. An overcharge condition is likely 
    if the process described in section 2.1 is followed when the ambient temperature is below 
    80 OF. Running the air conditioning system when the outside air temperature is appreciably 
    colder  than  the  normal  design  operating  temperatures  may  result  in  damage  to  the 
    compressor. The following guidelines will provide means to mitigate the chances of system 
    damage. 
    The following  assumes that  the  system  is  either a  freshly  installed  system  or  a  previously 
    operated system with a newly installed compressor.  
    						
    							AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 
    Revision 9 Page 39 
     Ambient temperature above 80OF: 
    If  the  system  was  charged  by  refrigerant  weight  utilizing  a charging  station  and  the 
    compressor  has  not  been  rotated  since  the  oil  and  refrigerant  were  added,  then 
    manually rotate the compressor shaft clockwise a minimum of 10 full revolutions prior to 
    running  the  compressor.  A  socket  or  wrench  applied  to  the  shaft nut  is  the 
    recommended  method.  Always  rotate  clockwise  to  insure  against  loosening  the 
    compressor shaft nut. 
    If  the  system  was  charged  per section 2.2 of  this  Chapter  then  disregard  manual 
    rotation. 
    Operate  system  normally,  check  for  evaporator  fan  operation  on  both  high  and  low 
    speed settings. Insure that condenser fans are operating and airflow direction is correct.  
     Ambient temperature between 60 OF and 80 OF: 
    At  these  ambient  temperatures  system  charging  is  to  be  accomplished  by  refrigerant 
    weight.  The  method discussed in section  2.2 is  not  applicable  at  these  condenser  inlet 
    temperatures.  It  is  recommended  that  the  aircraft  heater  be  used  during  air  conditioner 
    system testing in order to provide a heat load to the evaporators. 
    Manually rotate the compressor shaft clockwise a minimum of 10 full revolutions prior to 
    running  of  compressor.  A  socket  or  wrench  applied  to  the  shaft  nut  is  recommended 
    method. Always rotate clockwise to insure against loosening the compressor shaft nut. 
    Normal  suction  and  discharge  pressures  are  not  expected  under  these  conditions  and 
    the  evaporators  may  be  cold  enough  to  cause  the  freeze  switch  to  activate  and  the 
    bypass valve to open and close in a cyclic pattern. 
    Even  though  the  bypass  valve  may  be  cycling  this  test  may  be  conducted  for  sufficient 
    time  to  thoroughly  check  for  condenser  blower  and  fan  operation.  Check  for  evaporator 
    fan  operation  on  both  high  and  low  speed  settings.  Insure  that  the  condenser  fan  is 
    operating  and the  airflow  direction  is  correct.  Low  side  pressure may  be  observed  to  be 
    higher than expected when the bypass valve is open. 
     Ambient Temperatures between 60 OF and 32 OF: 
    At  these  ambient  temperatures  system  charging  is  to  be  accomplished  by  refrigerant 
    weight.  The  method discussed in section  2.2 is  not  allowed  at  these  condenser  inlet 
    temperatures.  It  is  required  that  the  aircraft  heater,  or  another  means  of  elevating  the 
    evaporator  inlet  air,  be  used  during  air  conditioner  system  testing  in  order  to  provide  a 
    heat load to the evaporators. 
    It  is  recommended  that  the  aircraft  be  warmed  in  a  heated  hangar  immediately  prior  to 
    running the air conditioner test. Upon removing the aircraft from the heated environment 
    the test should be started within ten minutes or as soon as practical.  
    						
    							AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 
    Revision 9 Page 40 
    Manually rotate the compressor shaft clockwise a minimum of 10 full revolutions prior to 
    running  of  compressor.  A  socket  or  wrench  applied  to  the  shaft  nut  is  recommended 
    method. Always rotate clockwise to insure against loosening the compressor shaft nut. 
    Normal  suction  and  discharge  pressures  are  not  expected  under  these  conditions  and 
    the  evaporators  may  be  cold  enough  to  cause  the  freeze  switch  to  activate  and  the 
    bypass valve to open and close in a cyclic pattern. 
    At  these  ambient  temperatures  this  test  should  not  be  conducted  for  more  than  15 
    minutes.  Testing  the  evaporator  fan  operation  using  the  vent  position  prior  to  rolling  out 
    of the hangar and prior to running the air conditioner system is recommended. Check for 
    evaporator fan operation on both high and low speed settings. Insure that condenser fan 
    is operating and the airflow direction is correct. 
     Ambient Temperature less than 32 OF: 
    There  is  no  safe  way  to  operate  the  air  conditioning  compressor  with  ambient 
    temperatures  below  32 OF.  Much  of  the  system  can  be tested for  proper operation  even 
    though the compressor cannot be run. 
    Charge the system by refrigerant weight only. 
    Manually  rotate  the  compressor  shaft  clockwise  a  minimum  of  10  full  revolutions.  A 
    socket  or  wrench  applied  to  the  shaft  nut  is  recommended method.  Always  rotate 
    clockwise to insure against loosening the compressor shaft nut. 
    Temporarily disconnect the wire energizing the compressor clutch. 
    Run  the  aircraft  and  turn  the  switch  to  air  conditioning.  Check  the  condenser  fan  for 
    operation and correct direction of airflow. Check evaporator fans for airflow on both high 
    and low settings. 
     
    2.4 Purging procedure  
     If the system has become contaminated or if the amount of oil in the system is unknown, 
     the following purge steps will prep the system for charging.  
     
     1. Remove all refrigerant from the system and discard. Ensure the charging station is     
         cleaned afterwards from the contaminated oil and refrigerant. 
     
     2. Disconnect all tubing and hoses from the system components. 
     
     3. Purge all hoses and tubes using solvents specifically made for air conditioning      
         systems such as Four Seasons Dura II A/C flush solvent (Isopropyl alcohol or     
         Denatured alcohol are acceptable substitutes). A/C flushing equipment available from      
         sources such as hecatinc.com is also recommended. 
     
     4. (This step does not need to be completed if the compressor is being replaced)  
    						
    							AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 
    Revision 9 Page 41 
         Remove the compressor from the aircraft, remove the drain plug and let the        
         compressor drain. Rotate the compressor and allow it to drain again. Repeat this      
         process until the compressor no longer has fluid inside. Do not use solvent to clean   
         the compressor. This will damage and possibly destroy the compressor. Add 8.0   
         ounces of Ultra PAG oil to the compressor (see section 3.0 below) and ensure the O-  
         ring on the drain plug is undamaged and retighten. 
     
     5. Purge the evaporators using air conditioner solvent (or equivalent i.e. Isopropyl  
         alcohol, Denatured alcohol). Flush the evaporator in the same direction as refrigerant   
         flow. The solvent should enter from the expansion valve side and exit on the     
         discharge side until the solvent runs out clean. 
     
     6. Purge the condenser using air conditioner solvent (or equivalent i.e. Isopropyl alcohol, 
         Denatured alcohol). 
     
     7. Flush the bypass valve with air conditioner solvent. Do not use pressure to force   
         solvent through the valve. 
     
     8. Replace the receiver drier bottle. THIS IS CRITICAL AND MUST BE PERFORMED. 
     
     9. Reconnect all components. Replace O-rings as needed. 
     
     10.Reconnect the compressor hose and place the system on a constant vacuum for 1   
          hour minimum. 
     
     11. Service the system with fresh R134a refrigerant and run an operational check out. 
     
    3. Lubrication Information 
     
    SYSTEM DESCRIPTION REFRIGERANT CHARGE OIL CHARGE 
    429 air conditioning system 
    with dual fwd evaporators 
     
    2.7 lbs 
     
    1.2247 Kg 8.0 oz. 237 ml 
    429 air conditioning system 
    with single fwd evaporator 
     
    2.5 lbs  
     
    1.1340 Kg  8.0 oz 
     
    237 ml 
     
     
    CAUTION 
    This system may be serviced with either Polyolester (POE) or Double End Capped Polyalkylene 
    Glycol (DEC PAG, also known as Ultra PAG) oil.  Polyalkylene Glycol oil is preferred due to its 
    superior lubricating properties and improved compressor service life.  There are several types of 
    PAG available. Only the “Double End Capped” type is permissible in Air Comm Corporation air 
    conditioning systems.  Double End Capped PAG oil is available from Air Comm Corporation in 8 
    ounce bottles (P/N ES94006-13).  Mixing of POE and PAG is acceptable.  Disregard previous 
    statements to the contrary. They referenced PAG oil that was not “Double End Capped”.  Current 
    versions of compressors are designed to be operated using PAG oil.  Testing by Air Comm 
    Corporation has shown that “Double End Capped” PAG is compatible with POE and can therefore 
    be mixed. “Double End Capped” is a reference to the chemical structure of the molecule and not to 
    the container.  
    						
    							AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 
    Revision 9 Page 42 
     
    Do not use Mineral oil in this system with R134a refrigerant. Do not use any refrigerant oil other 
    than Double End Capped Polyalkylene Glycol (also known as “ULTRA PAG”) or Polyolester (also 
    POE). 
     
    Containers of DEC PAG or POE will absorb moisture if left open (hygroscopic). Keep containers 
    tightly capped when not in use and keep all system components capped while servicing system. 
     
    The oil charge is continuously circulated by the refrigerant during the operation of the system. A 
    quantity of oil is trapped by the compressor, as well as by other parts of the system. 
     
    The following chart may be used to calculate the amount of oil to be added in case a component is 
    being replaced with a new part.  
     
     
    Component Oil Amount 
    Compressor See Instructions  
    Evaporator 1.0 oz. per evaporator 
    Condenser 1.5 oz. 
    Receiver Drier 1.5 oz. 
    Hose - Vapor 1.0 oz. per 10 foot 
    Hose – Liquid 1.0 oz. per 20 foot 
     
    Compressor  Replacement – To  properly  calculate  the  amount  of  oil required  in  the 
    replacement  compressor,  it  is  necessary  to  pour  the  oil  out  of  the  old  compressor  into  a  clean 
    container. Drain the oil out of the fill plug hole and then pour oil out of the suction and discharge 
    ports while rotating the center shaft clockwise. Measure the total amount of oil removed from the 
    old  compressor.  Add  ½  oz.  to  the  total  measured  to  account  for  unrecoverable  oil  in  the  old 
    compressor. This  total  is  what  is  needed  in  the  new  compressor.  New  compressors come from 
    Air Comm charged with 8 oz. (237 cc) of oil. This should be adjusted according to the amount of 
    oil recovered from the old compressor and any other components being replaced. The receiver 
    drier should always be replaced when the compressor is replaced or when the system has been 
    open for an appreciable time, which accounts for another 1.5 oz. of oil that should be added. 
     
    Below is an example of a compressor (and receiver drier) replacement for illustration: 
     
    Evacuating the system recovers 1.5 oz. of oil.  Draining the old compressor recovered 2.0 
    oz.  of  oil.    Adding  0.5  oz.  of  residual  unrecoverable  oil  in  the  compressor  gives  2.5  oz. 
    The  new  receiver/drier  requires  an  additional  1.5  oz.,  plus  1.5  oz.  lost  when  the 
    refrigerant  was  evacuated  from  the  system.  So  the  total  oil  needed  in  the  replacement 
    compressor  for  this  case  is  5.5  oz.  Since  the  new  compressor  comes  with  8  oz.  of  oil, 
    remove  the  oil  fill  plug  and  pour  out  2.5  oz.  of  oil.    Torque  compressor  oil  fill  cap  to  132-
    216 in-lb. 
     
    The  total  system  oil  charge  is  8.0  fl.  oz.  (237  ml.)  of  Refrigerant  Oil.  The  compressor  is 
    charged with 8.0 fl. oz. of oil at the factory.   
       
    						
    All AirComm Corporation manuals Comments (0)

    Related Manuals for AirComm Corporation Bell 429 Air Conditioning 429EC200M1Rev9 User Manual