Home
>
AirComm Corporation
>
Air Conditioner
>
AirComm Corporation Bell 429 Air Conditioning 429EC200M1Rev9 User Manual
AirComm Corporation Bell 429 Air Conditioning 429EC200M1Rev9 User Manual
Have a look at the manual AirComm Corporation Bell 429 Air Conditioning 429EC200M1Rev9 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 74 AirComm Corporation manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 Revision 9 Page 33 Figure 25: Aft Evaporator Drain Line Routing, Dual Evaporators Figure 26: Aft Evaporator Drain Line Routing, Single Evaporators
AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 Revision 8 Page 34 CHAPTER 5 PLACARDS AND MARKINGS 1. Placard and Marking Information All placards and markings associated with the installation of the air conditioner system are part of the type design of this helicopter. Please refer to the Bell Helicopter Instructions for Continued Airworthiness Manual for placards and markings information. THIS AREA INTENTIONALLY LEFT BLANK
AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 Revision 9 Page 35 CHAPTER 6 SERVICING 1. Safety Precautions CAUTION Refrigeration servicing should be performed by qualified personnel only. Check all local and federal regulations before servicing any refrigerant system or storage device. The refrigerant used in the air conditioning system is the environmentally safe HFC R134a. This refrigerant is non-explosive, non-flammable, and non-corrosive, has practically no odor, and is heavier than air. However, certain precautions must me observed to ensure the safety of the equipment and any personnel servicing this system. HFC R134A is stored in a liquid state. It will rapidly evaporate or sublimate when exposed to normal temperature and atmospheric pressure. This rapid evaporation can causes a severe drop in temperature. If liquid refrigerant comes in contact with the skin or eyes it may cause severe frostbite or blindness. Care must be taken to prevent liquid refrigerant from contacting the skin or the eyes. WARNING Safety glasses must be worn at all times when servicing the air conditioning system. Should any liquid refrigerant come in contact with the skin or eyes seek medical attention immediately even if the irritation ceases. WARNING To avoid a potential explosion NEVER weld, solder, steam clean, use a flame type leak detector, blow torch, bake on aircraft finish, or use excessive heat on, or in the immediate area of refrigerant lines or supply tanks while they are closed to the atmosphere. WARNING Refrigerant servicing must be performed in a well-ventilated area to minimize inhalation of the refrigeration gas. 2. Servicing Information CAUTION Refrigeration servicing should be performed by qualified personnel only. NOTE A list of suggested servicing equipment is provided later in this chapter. 2.1 Servicing Procedure using a Service Cart A. Connect the servicing manifold to the servicing ports located on the forward R/H side of the transmission deck. BLUE for low pressure or “Suction” and RED for high pressure or “Discharge.”
AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 Revision 9 Page 36 B. After the quick disconnect fittings have been attached to the servicing ports, tighten the knobs on the back of the fittings to engage the Schrader valves located inside the charging ports. NOTE The Schrader valves inside the charging ports MUST be engaged to allow servicing of the air conditioner system. C. Connect the YELLOW line in the center of the manifold to the vacuum pump. Turn the vacuum pump on and open both valves on the charging manifold. Decreasing the pressure in the closed system to -29.40 InHg causes the moisture in the system to vaporize allowing it to be drawn out by the vacuum pump. Removal of all moisture is crucial to the operation of the A/C system. Any moisture left in the system will be turned into ice causing undesired operation or blockage of one or more expansion valve. Allow the vacuum pump to draw against the system for a minimum of ONE HOUR. NOTE Due to a drop in atmospheric pressure with an increase in altitude, the normal vacuum reading will drop 1” (1 kg/cm) for each 1000 ft of altitude gained e.g., Sea Lever Reading = 10 InHg, reading at 1000 feet above sea level = 9 InHg. D. After the system has been evacuated, turn both valves on the manifold assembly to the “OFF” position and switch the vacuum pump off. Allow the system to hold the vacuum for a minimum of ONE hour to check for vacuum leaks. If the system will not hold the vacuum, the system may have a fitting leak. It may be necessary to charge the system with one to two pounds of refrigerant and conduct a leak check using an electronic leak detector. CAUTION To ensure trouble free operation the system must be leak free. E. After the leak check has been performed evacuate the system for a minimum of ½ hour before charging per the levels below: 429 air conditioning system with dual Fwd evaporators, 2.7 lbs (1.2247 Kg) of refrigerant. 429 air conditioning system with single Fwd evaporator, 2.5 lbs (1.1340 Kg) of refrigerant. NOTE Static charging is the most accurate and safest way to charge an air conditioning system. To accomplish this all 2.7 Lbs. of refrigerant must be charged into the system without the compressor engaged or the system operating. If the system must be serviced with the compressor running, servicing must be performed through LO (BLUE) side only! Please make sure that the HIGH (RED) side valve stays closed during this procedure and any time the system is operating. Never Charge through the Discharge or “HIGH” (RED) side of the system while the compressor is running as this may cause severe damage to the compressor Assy.
AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 Revision 9 Page 37 CAUTION Operating the air conditioning system with a low refrigerant charge may cause severe damage to the compressor assembly. F. After charging, perform a test run to ensure proper function of the Air Conditioning System. 2.2 Servicing Procedure without using a Service Cart A. The following tools & materials will be required: 1. R134a Manifold Gauge Set 2. 3 pound bottle of R134a 3. Refrigerant Scale to weigh the refrigerant bottle 4. Vacuum Pump capable of maintaining 29in Hg of mercury at sea level 5. Ultra PAG oil B. Charging procedure: Note that the following steps 1 through 7 are to be accomplished while the aircraft and air conditioning system are “OFF”. 1. Connect the servicing lines from the manifold gauges to the servicing ports located on the forward R/H side of the transmission deck. The BLUE port is for low pressure (suction) and the RED port is for high pressure (discharge). 2. After the quick disconnect fittings have been connected to the servicing ports, tighten the knobs on the back of the fittings to engage the Schrader valves located inside the charging ports. If the knobs are not properly tightened, the Schrader valve inside of the ports will not engage. 3. To ensure there is no air or moisture in the system, use the Manifold Gauges and Vacuum Pump to pull the system down on a vacuum continuously for a minimum of 1 hour. To perform this, connect the YELLOW line in the center of the manifold to the vacuum pump. Turn the Vacuum pump on and open both valves on the charging manifold until the pressure has decreased to 29.40 in Hg. 4. After 1 hour of vacuuming and while the vacuum pump is still working, close both valves on the manifold gauge set and watch the High and Low pressure gauges to ensure the system pressures remain constant or “vacuumed.” If the system does not hold a vacuum it has a leak. 5. Once the system has been proven to be “Leak Free,” disconnect the vacuum pump and connect the refrigerant bottle to the manifold gauge set. 6. Purge the line between the refrigerant bottle and manifold gauge by opening the knob on the refrigerant bottle. Then, loosen the line at the manifold slightly to allow the refrigerant to push the air out. This will verify that there is no air in the line. 7. Charge the system by opening the low side and high side valves which will allow
AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 Revision 9 Page 38 the initial charge of 2.0 pounds to be added. This can be measured and tracked by placing the bottle on a scale. Note that the following step 8 is to be accomplished while the aircraft is running at 100% and the air conditioning system is “ON”. Ensure that the High side (RED) is closed at all times while system is operating.) 8. Add the remainder of the required charge in 0.2 lb. increments by opening the low side (BLUE) slightly to allow the refrigerant to be drawn in. Allow two minutes to elapse between each addition of refrigerant. The amount entering the system can be verified by monitoring the scale as the refrigerant is added. Note that the compressor can be damaged if an excessive amount is added. Charge the system as listed below: 429 air conditioning system with dual Fwd evaporators, 2.7 lbs (1.2247 Kg) of refrigerant. 429 air conditioning system with single Fwd evaporator, 2.5 lbs (1.1340 Kg) of refrigerant. WARNING If charging is to be accomplished with the compressor engaged it must be accomplished through the LO (BLUE) side only. Never Charge through the Discharge or “HIGH” (RED) side of the system while the compressor is running. This may cause severe damage to the servicing equipment and may cause personal injury or death. Care should be taken to ensure the HIGH (RED) side valve stays closed during this procedure and any time the system is operating. CAUTION When reclaiming refrigerant, be sure to note any oil that is removed from the system, and replace the lost oil before or during re-servicing. Maintaining a proper oil and refrigerant charge is critical to the life of the compressor assembly. Excessive system oil charge will reduce cooling performance. 2.3 Ambient Temperature effects on servicing Running the system when the ambient temperature is below 80 OF will present unusual (low) suction and discharge pressures on system gauges. An overcharge condition is likely if the process described in section 2.1 is followed when the ambient temperature is below 80 OF. Running the air conditioning system when the outside air temperature is appreciably colder than the normal design operating temperatures may result in damage to the compressor. The following guidelines will provide means to mitigate the chances of system damage. The following assumes that the system is either a freshly installed system or a previously operated system with a newly installed compressor.
AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 Revision 9 Page 39 Ambient temperature above 80OF: If the system was charged by refrigerant weight utilizing a charging station and the compressor has not been rotated since the oil and refrigerant were added, then manually rotate the compressor shaft clockwise a minimum of 10 full revolutions prior to running the compressor. A socket or wrench applied to the shaft nut is the recommended method. Always rotate clockwise to insure against loosening the compressor shaft nut. If the system was charged per section 2.2 of this Chapter then disregard manual rotation. Operate system normally, check for evaporator fan operation on both high and low speed settings. Insure that condenser fans are operating and airflow direction is correct. Ambient temperature between 60 OF and 80 OF: At these ambient temperatures system charging is to be accomplished by refrigerant weight. The method discussed in section 2.2 is not applicable at these condenser inlet temperatures. It is recommended that the aircraft heater be used during air conditioner system testing in order to provide a heat load to the evaporators. Manually rotate the compressor shaft clockwise a minimum of 10 full revolutions prior to running of compressor. A socket or wrench applied to the shaft nut is recommended method. Always rotate clockwise to insure against loosening the compressor shaft nut. Normal suction and discharge pressures are not expected under these conditions and the evaporators may be cold enough to cause the freeze switch to activate and the bypass valve to open and close in a cyclic pattern. Even though the bypass valve may be cycling this test may be conducted for sufficient time to thoroughly check for condenser blower and fan operation. Check for evaporator fan operation on both high and low speed settings. Insure that the condenser fan is operating and the airflow direction is correct. Low side pressure may be observed to be higher than expected when the bypass valve is open. Ambient Temperatures between 60 OF and 32 OF: At these ambient temperatures system charging is to be accomplished by refrigerant weight. The method discussed in section 2.2 is not allowed at these condenser inlet temperatures. It is required that the aircraft heater, or another means of elevating the evaporator inlet air, be used during air conditioner system testing in order to provide a heat load to the evaporators. It is recommended that the aircraft be warmed in a heated hangar immediately prior to running the air conditioner test. Upon removing the aircraft from the heated environment the test should be started within ten minutes or as soon as practical.
AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 Revision 9 Page 40 Manually rotate the compressor shaft clockwise a minimum of 10 full revolutions prior to running of compressor. A socket or wrench applied to the shaft nut is recommended method. Always rotate clockwise to insure against loosening the compressor shaft nut. Normal suction and discharge pressures are not expected under these conditions and the evaporators may be cold enough to cause the freeze switch to activate and the bypass valve to open and close in a cyclic pattern. At these ambient temperatures this test should not be conducted for more than 15 minutes. Testing the evaporator fan operation using the vent position prior to rolling out of the hangar and prior to running the air conditioner system is recommended. Check for evaporator fan operation on both high and low speed settings. Insure that condenser fan is operating and the airflow direction is correct. Ambient Temperature less than 32 OF: There is no safe way to operate the air conditioning compressor with ambient temperatures below 32 OF. Much of the system can be tested for proper operation even though the compressor cannot be run. Charge the system by refrigerant weight only. Manually rotate the compressor shaft clockwise a minimum of 10 full revolutions. A socket or wrench applied to the shaft nut is recommended method. Always rotate clockwise to insure against loosening the compressor shaft nut. Temporarily disconnect the wire energizing the compressor clutch. Run the aircraft and turn the switch to air conditioning. Check the condenser fan for operation and correct direction of airflow. Check evaporator fans for airflow on both high and low settings. 2.4 Purging procedure If the system has become contaminated or if the amount of oil in the system is unknown, the following purge steps will prep the system for charging. 1. Remove all refrigerant from the system and discard. Ensure the charging station is cleaned afterwards from the contaminated oil and refrigerant. 2. Disconnect all tubing and hoses from the system components. 3. Purge all hoses and tubes using solvents specifically made for air conditioning systems such as Four Seasons Dura II A/C flush solvent (Isopropyl alcohol or Denatured alcohol are acceptable substitutes). A/C flushing equipment available from sources such as hecatinc.com is also recommended. 4. (This step does not need to be completed if the compressor is being replaced)
AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 Revision 9 Page 41 Remove the compressor from the aircraft, remove the drain plug and let the compressor drain. Rotate the compressor and allow it to drain again. Repeat this process until the compressor no longer has fluid inside. Do not use solvent to clean the compressor. This will damage and possibly destroy the compressor. Add 8.0 ounces of Ultra PAG oil to the compressor (see section 3.0 below) and ensure the O- ring on the drain plug is undamaged and retighten. 5. Purge the evaporators using air conditioner solvent (or equivalent i.e. Isopropyl alcohol, Denatured alcohol). Flush the evaporator in the same direction as refrigerant flow. The solvent should enter from the expansion valve side and exit on the discharge side until the solvent runs out clean. 6. Purge the condenser using air conditioner solvent (or equivalent i.e. Isopropyl alcohol, Denatured alcohol). 7. Flush the bypass valve with air conditioner solvent. Do not use pressure to force solvent through the valve. 8. Replace the receiver drier bottle. THIS IS CRITICAL AND MUST BE PERFORMED. 9. Reconnect all components. Replace O-rings as needed. 10.Reconnect the compressor hose and place the system on a constant vacuum for 1 hour minimum. 11. Service the system with fresh R134a refrigerant and run an operational check out. 3. Lubrication Information SYSTEM DESCRIPTION REFRIGERANT CHARGE OIL CHARGE 429 air conditioning system with dual fwd evaporators 2.7 lbs 1.2247 Kg 8.0 oz. 237 ml 429 air conditioning system with single fwd evaporator 2.5 lbs 1.1340 Kg 8.0 oz 237 ml CAUTION This system may be serviced with either Polyolester (POE) or Double End Capped Polyalkylene Glycol (DEC PAG, also known as Ultra PAG) oil. Polyalkylene Glycol oil is preferred due to its superior lubricating properties and improved compressor service life. There are several types of PAG available. Only the “Double End Capped” type is permissible in Air Comm Corporation air conditioning systems. Double End Capped PAG oil is available from Air Comm Corporation in 8 ounce bottles (P/N ES94006-13). Mixing of POE and PAG is acceptable. Disregard previous statements to the contrary. They referenced PAG oil that was not “Double End Capped”. Current versions of compressors are designed to be operated using PAG oil. Testing by Air Comm Corporation has shown that “Double End Capped” PAG is compatible with POE and can therefore be mixed. “Double End Capped” is a reference to the chemical structure of the molecule and not to the container.
AIR CONDITIONER SERVICE MANUAL 429EC-200M-1 Revision 9 Page 42 Do not use Mineral oil in this system with R134a refrigerant. Do not use any refrigerant oil other than Double End Capped Polyalkylene Glycol (also known as “ULTRA PAG”) or Polyolester (also POE). Containers of DEC PAG or POE will absorb moisture if left open (hygroscopic). Keep containers tightly capped when not in use and keep all system components capped while servicing system. The oil charge is continuously circulated by the refrigerant during the operation of the system. A quantity of oil is trapped by the compressor, as well as by other parts of the system. The following chart may be used to calculate the amount of oil to be added in case a component is being replaced with a new part. Component Oil Amount Compressor See Instructions Evaporator 1.0 oz. per evaporator Condenser 1.5 oz. Receiver Drier 1.5 oz. Hose - Vapor 1.0 oz. per 10 foot Hose – Liquid 1.0 oz. per 20 foot Compressor Replacement – To properly calculate the amount of oil required in the replacement compressor, it is necessary to pour the oil out of the old compressor into a clean container. Drain the oil out of the fill plug hole and then pour oil out of the suction and discharge ports while rotating the center shaft clockwise. Measure the total amount of oil removed from the old compressor. Add ½ oz. to the total measured to account for unrecoverable oil in the old compressor. This total is what is needed in the new compressor. New compressors come from Air Comm charged with 8 oz. (237 cc) of oil. This should be adjusted according to the amount of oil recovered from the old compressor and any other components being replaced. The receiver drier should always be replaced when the compressor is replaced or when the system has been open for an appreciable time, which accounts for another 1.5 oz. of oil that should be added. Below is an example of a compressor (and receiver drier) replacement for illustration: Evacuating the system recovers 1.5 oz. of oil. Draining the old compressor recovered 2.0 oz. of oil. Adding 0.5 oz. of residual unrecoverable oil in the compressor gives 2.5 oz. The new receiver/drier requires an additional 1.5 oz., plus 1.5 oz. lost when the refrigerant was evacuated from the system. So the total oil needed in the replacement compressor for this case is 5.5 oz. Since the new compressor comes with 8 oz. of oil, remove the oil fill plug and pour out 2.5 oz. of oil. Torque compressor oil fill cap to 132- 216 in-lb. The total system oil charge is 8.0 fl. oz. (237 ml.) of Refrigerant Oil. The compressor is charged with 8.0 fl. oz. of oil at the factory.