Home
>
AirComm Corporation
>
Air Conditioner
>
AirComm Corporation Air Conditioner R134A Service Manual
AirComm Corporation Air Conditioner R134A Service Manual
Have a look at the manual AirComm Corporation Air Conditioner R134A Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 74 AirComm Corporation manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Products, INC. TR-134 System Service Manual Aug 21/06 Page 16 4. COIL CLEANING MAINTENANCE PROCEDURES A. General The following procedure is used for cleaning either evaporator or condenser coil. B. Tools and Equipment Designation Ref. No. Qty Remarks Vacuum Cleaner Comm. Avail. 1 None Coil Cleaner Comm. Avail. A/R Non-acid based C. Coil Cleaning Procedure 1. Use vacuum cleaner to remove large debris from upstream and downstream coil faces. 2. Spray coil cleaner on both coil faces. Wash off with water. 3. Allow coil to dry thoroughly prior to additional maintenance.
Products, INC. TR-134 System Service Manual Aug 21/06 Page 17 5. EXPANSION VALVE REMOVAL AND INSTALLATION A. General The following procedure is used to remove or install the air conditioning system expansion valve. B. Tools and Equipment Designation Ref. No. Qty Remarks Sealant ES49000-1 A/R None Polyolester Oil Comm. Avail. A/R Viscosity ISO 68 C. Expansion Valve Replacement 1. Discharge system in accordance with Refrigerant Servicing section. 2. Disconnect liquid line from inlet of expansion valve, and cap. Remove the thermal sense bulb from its clamp located on the suction tube of the evaporator and carefully remove insulation covering bulb. 3. Disconnect the fitting that connects the valve to the coil and plug coil fitting. 4. Install new expansion valve and o-ring (for o-ring fitting systems) in the reverse order. 5. Lubricate o-ring with polyolester oil or apply sealant to fitting mating surfaces prior to assembly. 6. Install the thermal sense bulb such that it makes contact with the suction tube along its entire length. When viewing the suction tube extruding out of the evaporator, the sense bulb should be in the three or nine o’clock position (Figure A and B). Attach the sensor bulb using two zip ties. Insulate the bulb and expansion valve thoroughly with insulation (Figure C).
Products, INC. TR-134 System Service Manual Aug 21/06 Page 18 (Figure A) (Figure B) (Figure C)
Products, INC. TR-134 System Service Manual Aug 21/06 Page 19 6. COMPRESSOR MAINTENANCE PROCEDURES A. General The following procedure is used whenever the compressor is replaced or contamination is suspected. B. Tools and Equipment Designation Ref. No. Qty Remarks None - - None C. Compressor Replacement 1. Flush system and replace compressor per the Refrigerant Servicing section.
Products, INC. TR-134 System Service Manual Aug 21/06 Page 20 TROUBLESHOOTING 1. GENERAL The procedures below present troubleshooting charts for the air conditioning system and the compressor. A diagnoses chart is presented for insufficient air conditioning system cooling. The performance characteristics of an aircrafts particular system is dependant upon the design parameters of the systems components. The performance of any one particular system varies with ambient temperature and humidity. The information below presents possible air conditioning system problems and solutions. CAUTION: Do not operate air conditioning system with condenser air outlet blocked. 2. AIR CONDITIONING SYSTEM DIAGNOSIS CHART Figure 3 shows a procedure for diagnosing air conditioning system problems. Following this procedure will expedite the troubleshooting process.
Products, INC. TR-134 System Service Manual Aug 21/06 Page 21 Figure 3. Air Conditioning System Diagnosis Chart
Products, INC. TR-134 System Service Manual Aug 21/06 Page 22 3. AIR CONDITIONING SYSTEM TROUBLESHOOTING CONDITION SERVICE PRESSURE GAUGE READING PROBABLE CAUSE CORRECTIVE ACTION INSUFFICIENT REFRIGERANT CHARGE Insufficient cooling. Bubbles appear in sight glass. SUCTION PRESSURE: below normal DISCHARGE PRESSURE: below normal Refrigerant is low, or leaking a little. 1. Leak test. 2. Repair leak. 3. Charge system. Evacuate as necessary and recharge system. ALMOST NO REFRIGERANT No cooling action. A lot of bubbles or something like mist appears in sight glass. SUCTION PRESSURE: much below normal DISCHARGE PRESSURE: much below normal Serious refrigerant leak. Stop compressor immediately. 1. Leak test. 2. Discharge system. 3. Repair Leak(s). 4. Replace receiver drier, if necessary. 5. Check oil level. 6. Evacuate and recharge system. FAULTY EXPANSION VALVE a) Slight cooling. Sweating or frosted expansion valve outlet. b) Insufficient cooling. Sweated suction line. c) No cooling. Sweating or frosted suction line. a) SUCTION PRESSURE: below normal DISCHARGE PRESSURE: below normal b) SUCTION PRESSURE: above normal DISCHARGE PRESSURE: above normal c) SUCTION PRESSURE: above normal DISCHARGE PRESSURE: below normal a) Expansion valve restricts refrigerant. Or, expansion valve is clogged. Or, expansion valve is inoperative. Or, valve stuck closed. Thermal bulb has lost charge. b) Expansion valve allows too much refrigerant through evaporator. Sensing bulb on suction line not well insulated or properly attached to line. c) Faulty expansion valve. a) Replace expansion valve. b) 1.Check valve for operation. If suction side does not show a pressure decrease, replace valve. 2. Check security and insulation on sensing bulb. c) 1. Discharge system. 2. Replace valve. 3. Evacuate and recharge system.
Products, INC. TR-134 System Service Manual Aug 21/06 Page 23 CONDITION SERVICE PRESSURE GAUGE READING PROBABLE CAUSE CORRECTIVE ACTION AIR IN SYSTEM Insufficient cooling. Sight glass shows occasional bubbles. SUCTION PRESSURE: above normal DISCHARGE PRESSURE: above normal Air mixed with refrigerant in system. 1. Discharge system. 2 Replace receiver drier. 3. Evacuate and charge system. MOISTURE IN SYSTEM After operation for a while, pressure on suction side may show vacuum pressure reading. During this condition, discharge air will be warm. As warning of this, reading shows approx 6 psi oscillation. SUCTION PRESSURE: below normal DISCHARGE PRESSURE: above normal Drier is saturated with moisture. Moisture has frozen at expansion valve. Refrigerant flow is restricted. 1. Discharge system. 2. Replace receiver drier (twice if necessary). 3. Evacuate system completely. (Repeat 30 minute evacuating three times.) 4. Recharge system. FAULTY CONDENSER Insufficient cooling. Bubbles appear in sight glass of drier. Suction line is very hot. SUCTION PRESSURE: above normal DISCHARGE PRESSURE: above normal Condenser air or refrigerant flow is restricted. Check condenser for dirt accumulation. Check for refrigerant overcharge. If pressure remains high in spite of all above actions taken, remove and inspect the condenser for possible oil clogging. HIGH PRESSURE LINE BLOCKED Insufficient cooling. Frosted high pressure liquid line. SUCTION PRESSURE: much below normal DISCHARGE PRESSURE: much above normal Drier clogged, or restriction in high pressure line. 1. Discharge system. 2. Remove receiver drier and replace it. 3. Evacuate and charge system.
Products, INC. TR-134 System Service Manual Aug 21/06 Page 24 CONDITION SERVICE PRESSURE GAUGE READING PROBABLE CAUSE CORRECTIVE ACTION FAULTY COMPRESSOR Insufficient cooling. SUCTION PRESSURE: much above normal DISCHARGE PRESSURE: much below normal Internal problem in compressor, or damaged gasket and valve. 1. Discharge system. 2. Remove and check compressor. 3. Repair or replace compressor. 4. Check oil level. 5. Replace receiver drier. 6. Evacuate and charge system. TOO MUCH OIL IN SYSTEM (Excessive) Insufficient cooling. SUCTION PRESSURE: above normal DISCHARGE PRESSURE: above normal Too much oil circulates with refrigerant, causing the cooling capacity of the system to be reduced. Refer to Oil Level Check for correcting oil level.
Products, INC. TR-134 System Service Manual Aug 21/06 Page 25 4. COMPRESSOR TROUBLESHOOTING A. General The following procedures are used for troubleshooting the compressor. B. Tools and Equipment Designation Ref. No. Qty Remarks Service Pressure Gauge Comm. Avail. 1 None DC Power Supply A/R None C. Compressor Troubleshooting Procedures With the air conditioning system operating, do any of the following conditions occur: NOTE: Always attach a service gauge set to the system prior to trouble shooting, to insure proper refrigerant charge is present. Trouble Probable Cause Correction 1. Unusually high suction pressure with low discharge pressure. 2. Unusually low suction and discharge pressure. 3. High compressor discharge pressure. 4. Rough running. (a) Internal problem with compressor body. (b) Faulty Expansion valve System or compressor Leak. (a) Air exhaust duct collapsed or restricted. (b) Refrigerant overcharge. Internal compressor problem. (a) Replace compressor. (b) Replace expansion valve Repair leak or replace compressor. (a) Inspect/replace exhaust duct. (b) Discharge refrigerant until only occasional bubbles are present in sight glass. Replace compressor.