    The ADS PrimeProbe®2 is a bi-directional insertion flowmeter for use in managing water 
    distribution systems. It has no moving parts making it reliable and ideal for use over a wide range 
    of flows. PrimeProbe2 is suitable for use in pipe sizes from 4” to 48” (larger sizes available upon 
    request).   
    QUICK REFERENCE GUIDE
    Precautions and Switch-on of the ADS PrimeProbe2 
    Safety and Precautions 
    Please read these instructions carefully as they contain important safety information.  PrimeProbe2 
    must be used for the specified application - improper use or tampering will invalidate the warranty. 
    ADS is responsible only if used in original product configuration.
    The PrimeProbe2 should be installed away from any bends or hydraulic fittings. For best results, •	
    it should be installed with at least 25 pipe diameters of straight unrestricted pipe upstream of the 
    sensor, and 10 pipe diameter downstream of the sensor.  
    For correct operation, the pipe must be completely full of water.  It is not necessary that the •	
    probe be installed vertically. But must be installed at 90° to the pipe.
    Before inserting the probe, ensure the safety chain is correctly secured at both ends•	.  Pipes are 
    under pressure - failure to tighten the locking collar and connect the safety chain could cause the 
    probe to be forced upwards with potential injury to the user.
    Important•	 – Fully tighten all screws as water ingress can occur.
    PrimeProbe 2
    ®
    Installation Do’s and Don’ts
    Vertical installations are preferable in ascendingflow
    For vertical installationswith descending flowdirection, contact ADS
    Avoid installation near curves or hydraulicaccessories
    The opening of the ball valve before tightening the fixing side screws could cause the expulsion of the sensor from the pipeline
    Avoid the functioning with the pipe partially empty
    WARNING!!!WARNING!!!
    During the functioning, the pipe must be completely full of liquid, or completely empty
    Install the sensor away from curves and hydraulic          accessories
    Before opening the ball valve, fix the sensor with two side screws 
    						
    							Flow Direction
    Before completion of installation, confirm the direction of the flow of liquid in the pipe.  Using 
    the nameplate as a reference, flow direction is positive when the flow direction is from – to +. 
    If the flow direction is reversed after installation, it is sufficient to reverse the sign of the KA 
    Factor (refer to operating manual “Programming the Converter”). However, it is preferable to 
    reverse the probe by rotating through 180 degrees.
    Grounding the Probe
    For accurate results, it is necessary that the probe and the liquid are both 
    at the same potential.  To achieve this always connect the sensor to the 
    earth.  On pipes with cathodic protection, please contact ADS for advice.
    IMPORTANT NOTE:
    Fluctuating flow-rates are usually an indication of a poor earth connection, excessive vibration or electrical 
    noise on the pipe.
    Switch-on and Off
    When installation is complete the PrimeProbe2 must be switched ON to take it out of Sleep Mode, as described below.  See 
    Operating Manual for further details.
    1) Launch the PrimeWorks software.  Connect the PrimeProbe2 to the software using the communications cable. In PrimeWorks 
    select the PrimeProbe2 - Wake up menu option.  The software will initiate communications with the PrimeProbe2 to bring it out of 
    Sleep mode.  The probe is now ready for use. 
    2) Upon completion of usage it is recommended that the probe is returned to Sleep Mode by selecting Primeprobe2 - Sleep in 
    PrimeWorks.
    QUICK REFERENCE GUIDE
    4940 Research Drive - Huntsville, AL 35805 - 800.633.7246     www.adsenv.com
    The ADS PrimeProbe2 Operating 
    Manual can be Downloaded Online at 
    www.adsenv.com/manuals. 
    P r i m e P r o b e   2®
    PrimeWorks software reflecting 15-minute average flow rate. PrimeProbe2 bi-directional 
    insertion flowmeter.  
    						