Home > 3M > Locator > 3M CablePipe Locating Techniques Manual

3M CablePipe Locating Techniques Manual

    Download as PDF Print this page Share this page

    Have a look at the manual 3M CablePipe Locating Techniques Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 307 3M manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							21
    4. Applying Signal to Telephone Cable: Dyna-Coupler Method
    4.1 The Dyna-Coupler puts signal selectively on a cable by clamping around it.  This eliminates the
    need to disconnect the cable.  Do not use the Dyna-Coupler on a cable that has the shield
    ungrounded at both ends.
    4.2 Place the Dyna-Coupler on the cable between
    the ground bonding and the point where the
    cable enters the earth as shown (A).  Note
    that if you place the Dyna-Coupler above the
    bond, the signal travels to ground, and not
    onto the cable.
    Note: Always use the high output level when using the coupler. 4.3 On short cables, such as service drops, do
    not use the Dyna-Coupler on an ungrounded
    end (C). It works better on the grounded end
    (D). If possible, ground end (C); if not, be
    sure to use the highest frequency possible. 
    						
    							22
    4.4 If the cable is long, remove the bonding
    and signal goes both ways as shown.
    4.6 Several cables grounded at a common
    point present no problem for the Dyna-
    Coupler method. Even though signal is
    coupled into each cable, the cable with
    the Dyna-Coupler is clearly
    identifiable because it has the strongest
    signal. 4.5 Clamping the Dyna-Coupler to a cable
    with drop lines or laterals puts full
    signal on the cable until the junction
    point. The signal may split evenly at
    the lateral as shown. When tracing, the
    speaker volume and signal level
    indication drops when the Receiver
    passes the junction.  This is an easy
    way to find laterals. 
    						
    							23
    5. Locating Slack Loops and Butt Splices
    5.1 To identify the presence of a slack loop or
    butt splice in a cable path, first locate and
    mark the cable path.
    5.2 Find the strongest response over the marked
    cable path and reset the gain.
    5.3 Retrace the cable path with the Receiver
    held so the handle is perpendicular to
    (across) the cable path, as shown. When the
    Receiver passes over a slack loop or butt
    splice, the signal increases and the bar graph
    closes. Mark each response. Whenever you
    encounter such a condition, check to see if
    an unknown lateral exists.
    6. Locating Unknown Laterals
    6.1 To check for unknown laterals which may
    radiate from a butt splice type or closure, first
    trace and mark the cable path.  Retrace to
    locate any butt splices or slack loops. Mark
    the spot of any detected butt splices or slack
    loops.
     6.2 If the Receiver gain has not been set while
    performing the normal trace, go to the marked
    trace path and pinpoint the path. Reset the
    gain.
    6.3 Walk 10 to 25 feet off the trace path and away
    from the marked butt splice or slack loop.
    Hold the Receiver so that the display end of
    the handle points directly to the mark. Walk in
    a circle around the mark with the Receiver
    handle pointing to the mark.
    6.4 The Receiver remains relatively quiet until it
    crosses a lateral or the actual cable path.
    Since there could be several laterals radiating
    from the closure, mark each occurrence of
    signal around the circle.  After you locate each
    lateral, trace and mark its path. 
    						
    							24
    7. Locating Cables from Pedestals
    7.1 To locate a single cable path from a pedestal, follow these steps:
    7.2 At the pedestal, apply tracing signal on the target cable using the Dyna-Coupler method.  If the
    header in the pedestal is not grounded, use the ground rod and ground extension cable to ground
    it.
    7.3 Walk 10 to 25 feet away from the pedestal.  Hold the Receiver so that the display end of the
    handle points directly to the pedestal.  Start walking in a circle around the pedestal with the
    Receiver always pointing toward the pedestal.
    7.4 The Receiver remains relatively quiet until it crosses a cable.  Stop when there is a response.  Find
    the point of strongest signal and press gain. Check the numeric display for relative signal strength.
    Remember the number and continue walking the circle. As you walk away from the cable, the
    signal drops. Press gain and continue. When you encounter another response, find the point of
    strongest signal. If the greatest signal strength is more than 25 points higher than the others (if any
    found), then that is the target cable.  If the signal levels are closer, then measure the depth of each
    cable found and note the bar graph in the depth mode (this is a relative measurement of the current
    flowing in the cable). In the depth mode, the cable that shows at least two more segments on the
    bar graph than the other cables is the target cable. 
    						
    							25
    8. Locating Service Drops
    8.1 When locating the path of a service drop from a house or other building, it is more convenient to
    apply signal at the house or building.  Connect the Transmitter using the direct-connect method.
    Use the standard tracing techniques described earlier.
    9. Locating an Open End
    9.1 To locate an unterminated or open end of a cable or drop, follow these steps.
    9.2 If the cable is bonded to ground at the access point, connect the Transmitter using the Dyna-
    Coupler method. Otherwise, if the cable is not bonded to ground at the access point, connect the
    Transmitter using the Direct-connect method. With either method, choose the highest frequency
    available, at high level.
    9.3 Trace the cable path. The receiverÕs response decreases suddenly at the site of the clear or severed
    end.
    10. Identifying Cables
    10.1 This procedure identifies a single cable in a group of similar cables. At an access where cable
    identity is known, use the Transmitter to put signal on the sought cable with the Dyna-Coupler.
    Select the highest frequency available.  Output level should be set to high.  It is not necessary to
    remove any bonds or ground. At an access at the far-end of the cable group, connect another
    Dyna-Coupler to the Receiver with the Extension Cable. On the Receiver, select the PEAK trace
    mode.  Select the same frequency as the Transmitter. Check the first cable in the group by
    clamping the Dyna-Coupler around the cable.  Press the GAIN ADJUST key and observe the
    numeric display, which is relative signal strength.  Remember the number and continue by
    clamping the Dyna-Coupler around the next cable in the group.  If the signal strength is greater
    than the previous observation, press the GAIN ADJUST key.  If the signal strength is less than
    before, ignore it.  After checking all the cables in the group, the cable with the highest reading is
    the one being sought. 
    						
    							26
    11. Pair Identification
    11.1 This procedure identifies individual conductors within the same cable.  It uses the Dyna-Coupler,
    so none of the pairs will need to be cut.  The use of the high frequency will also allow tagging of
    conductors in a wet pulp section.
    11.2 At a splice or access, use the Transmitter to put signal on the pair to be identified using the Dyna-
    Coupler. To minimize signal canceling and disruption on active pairs, clamp the Dyna-Coupler
    around both tip and ring of the pair and make sure it is fully closed.  Place the transmitter in the
    tone mode and select the highest frequency. If your Transmitter does not have this feature, the
    highest frequency trace mode will also work.
    11.3 Take the Receiver and Inductive Probe to the location where identification is needed.  Connect the
    Inductive Probe to the Receiver using the 6-ft. Probe Cable.  Both the probe and the cable are
    available as optional accessories.  Select the same mode and frequency as the Transmitter.
    11.4 Insert the Probe into the bundle of pairs (or the group, if known) and press the  GAIN ADJUST
    key.  Next, divide the pairs into two bundles and insert the Probe into each of the bundles and
    observe the numeric display.  The bundle with the highest reading will contain the sought pair.
    Continue by dividing the bundle with the sought pair into two parts and checking each part for the
    highest signal.  In this way the sought pair will be isolated.
    Note: There is a groove around the inductive Probe to indicate the location of the sensing coil. The
    coil is oriented so that maximum signal will be sensed when the probe is perpendicular to the
    cable conductor. 
    						
    							27
    12. Locating Splits
    12.1 To locate the splice where a split occurs, attach the Transmitter to tip and ring of one pair of the
    split. Strap the tips and rings of both pairs at a far-end access beyond the splice.
    12.2 On the Transmitter, select the tone mode and the low frequency.
    12.3 Using either the Receiver, a toning amplifier or a toning coil, detect a weak tone from the
    Transmitter to the split, and strong tone from the split to the strap.
    12.4 To verify that the split has been located, attach the Transmitter to a non-split conductor of one pair
    and a split conductor of the other pair. The tracing tone is strong from the Transmitter to the split,
    and weak from the split to the strap. 
    						
    							28
    A. Can the Fiber Be Traced?
    13.1 Fiber optic cables consist of fragile optical fibers encased in a strengthened outer member. The
    internal sheath of the cable may or may not be metallic. If it is not metallic, the manufacturer may
    include a metallic strength member (wire) within the sheath.  Some fiber optic cables have no
    internal metal structure, in which case the contractor installing the cable may pull an insulated
    wire through the underground duct with the fiber optic cable. If a metallic conductor is not in or
    next to the fiber optic cable, you cannot trace the cable path. You must then rely on site plans for
    physical location.
    13.2 You normally find underground fiber optic cable installed in a duct, or a tube within the duct. The
    installation is normally made from a central office to a remote terminal office or distribution point.
    There may be several splice points in hand holes or manholes along the route. Installation
    practices generally require that the fiber optic cable metallic sheath or strength member be
    grounded at the terminating ends. Bonding practices at the splice points vary by company.
    Therefore, the metallic strength member may or may not be grounded or may be grounded
    through a remotely-actuated relay or a voltage transient suppression device.  Some installations
    include a permanently installed rack-mounted transmitter that can selectively place a tracing
    signal on one of several fiber optic cables. If this transmitter produces a 577 Hz signal, you can
    trace the fiber optic cable using the Dynatel Receiver. 13. Fiber Optic Locating 
    						
    							29
    B. Applying the Trace Signal
    13.3 If the office installation includes a rack-mounted transmitter, check to see if your Receiver has the
    same frequency.  Some Receivers will receive 512 Hz and 560 Hz as well as 577 Hz. To use the
    transmitter, attach it to the sheath or strength member of the fiber optic cable to be traced and turn
    it on. If the transmitter frequency does not match the Receiver, or a rack-mounted transmitter is
    not available, attach the Dynatel Transmitter at the CO/Remote Terminal Office, or at an
    intermediate splice point.
    13.6 To attach the Transmitter at a field splice point, access the splice case.  If the splice case has one
    or two metal straps connected to ground, you can attach the Transmitter at this location.
    13.7 If the splice case has two straps, one of
    them most likely attaches to the
    metallic sheath or strength member on
    the incoming side and the other strap
    attaches to the outgoing side. This lets
    you connect the Transmitter to the
    incoming or outgoing side. The two
    straps may also be connected inside
    the splice case. 13.4 To attach the Transmitter at the Central
    Office or Remote Terminal Office, bring it
    to the location in the office where the fiber
    optic cable strength member is grounded.
    Typically, this is near the rack-mounted
    digital conversion equipment. Locate and
    disconnect the metal strength member from
    the frame or rack ground point.
    13.5 Check the resistance using the ohms mode.
    Relatively high resistance (greater than 2 k
    ohms) means there may be an open between
    this connection point and the ground at the
    terminating end or intermediate splice
    points. If the resistance is very low (less
    than 250 ohms), there may be another
    ground point on the strength member within
    the CO. Either condition probably causes
    very little of the signal to be placed on the
    fiber optic cable outside. An acceptable
    condition is a resistance reading between
    250 ohms and 2 k ohms.
    Attaching at the Splice Point
    Attaching at CO or Remote Terminal Office 
    						
    							30
    13.8 Maximum tracing signal is obtained
    by disconnecting the bonding
    strap(s) from the ground point before
    attaching the Transmitter, but local
    practice may not allow this.  In this
    case, the signal splits between the
    incoming cable, outgoing cable, and
    the ground point, thus reducing the
    tracing range.
    13.9 Use high level output if tracing fiber
    optic cable longer than .5 miles.
    C. Tracing the Fiber Optic Cable
    13.10 When tracing from a CO or Remote Terminal office, move to the cableÕs expected exit point
    outside the building. Select the same Receiver frequency as the Transmitter.
    13.11 Search the area until the unit receives the signal.  When tracing at a manhole or hand hole, walk in
    a circle around the hole with your back or front toward the hole.  Move toward increasing signal
    strength, adjusting Receiver gain as needed until you locate the cable.  Trace the path of the cable.
    13.12 When tracing a cable over a long distance, the signal strength decreases. This can be caused by the
    signal ÒbleedingÓ off into the earth due to capacitance or by additional grounds at splice points
    along the fiber optic cable. The ÒbleedingÓ effect causes a gradual reduction in signal strength as
    the Receiver moves along the cable. The splice point ground causes an abrupt or distinct drop in
    signal because the signal is split between the outgoing fiber optic cable and the local ground.
    These intermediate ground points can severely limit the tracing distance unless you use a high-
    powered Transmitter.  This abrupt drop in signal is a good indication of the presence of an earth
    ground at a splice point. 
    						
    All 3M manuals Comments (0)

    Related Manuals for 3M CablePipe Locating Techniques Manual