Home > Carrier > Controller > Carrier Gen 2 Vvt Manual

Carrier Gen 2 Vvt Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Carrier Gen 2 Vvt Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							VELOCITY PRESSURE PROBE GAIN Ð The pressure
    pickup which sends the pressure data can distort data due to
    placement, vibration, or other factors. The Velocity Pressure
    Probe Gain option allows a multiplier to be added to the value
    being read by the pressure pickup. The default is 1.0 (mul-
    tiplying by 1 results in an identical value). The range of
    values is 0.5 to 5.0. To con®gure the Velocity Pressure Probe
    Gain option, set category 5, option 6. Enter the gain for the
    pickup probe speci®ed per the manufacturer.
    PRESSURE SENSOR RE-ZERO Ð To assure that the
    zone controller is able to maintain proper static pressure
    levels during normal operation, the zone controller will
    automatically re-zero when the Auto-Zero Enable option is
    selected.
    To auto-zero the pressure sensor, select category 5, option 7
    (Auto-Zero Enable). Set the option to ON. The zone con-
    troller will turn off the system fan and allow time for the
    pressure to settle. The zone controller will wait until the pres-
    sure in the system has dissipated before zeroing the sensor.
    Once this time period expires, the zone controller will au-
    tomatically zero the pressure sensor and reset the option to
    OFF.
    POSITION DAMPER (Pressure Independent Only) Ð The
    zone controller damper position can be forced to any posi-
    tion through the Position Damper option when in pressure
    independent operation. This can be used to help determine
    the desired velocity pressure when using pressure inde-
    pendent control. To con®gure this option, select category 5,
    option 8. The current damper position will be shown. Use
    the left set point buttons to adjust the value. The range of
    values is 0 to 15, with 0 fully closed and 15 fully open. The
    default is 0.
    Velocity Pressure Probe Calibration ÐThe ve-
    locity pressure probe is used in conjunction with the zone
    controller for Pressure Independent operation. Refer to the
    pressure sensor installation instructions for more informa-
    tion on tubing and sensor location.
    To calibrate the velocity pressure probe, perform the fol-
    lowing procedure:
    1. Install a manometer or Magnehelic gage in parallel with
    the pressure sensor. Tee the Magnehelic gage high port
    into the high port of the pressure sensor. The high pres-
    sure port is indicated with a P1 on the sensor. Tee the
    Magnehelic gage low port into the low port of the pres-
    sure sensor. The low pressure port is indicated with a P2
    on the sensor.
    2. Con®gure the zone controller pressure sensor range (cat-
    egory 5, option 5). The value of 0.5 in. wg should be set
    for use with a 33CSPS-01. Verify that it is set correctly.
    3. Con®gure the zone controller Velocity Pressure Probe Gain
    option (category 5, option 6). The default value is 1.0.
    The value entered for Velocity Pressure Probe Gain is based
    on which model PSP (Pressure Static Pickup) is used.
    A value of 2.3 (1.56 for 350-v) should be used for all
    PSP models.
    4. Initiate the zone controller Auto-Zero function (category
    5, option 7). Set the value to ON. The zone controller
    will position its damper full closed and zero the sensor
    reading. Once this is complete, the zone controller will
    automatically turn the option to OFF.
    5. Initiate the zone controller Position Damper function (cat-
    egory 5, option 8). Adjust the damper position until the
    desired velocity pressure is obtained at the manometer or
    Magnehelic gage.
    6. Calibrate the pressure sensor (category 5, option 9). Ad-
    just the displayed value until it matches the measured value
    of the manometer or Magnehelic gage.7. Set the Minimum and Maximum Air¯ow Set Points (cat-
    egory 3, options 7 and 8). Set the Minimum Air¯ow Set
    Point to allow acceptable fresh air requirements. Set the
    Maximum Air¯ow Set Point so acceptable noise levels
    are not exceeded.
    8. Set the Damper Size option (category 3, option 9). The
    value is set in square inches and is the cross sectional
    area in which the probe is located.
    9. Enable Pressure Independent Control (category 3, option 4).
    Set the value to ON.
    Indoor-Air Quality Sensor ÐThe Comfort IAQ fea-
    ture allows the Carrier Comfort system to interface with the
    economizer on the HVAC equipment and maintain the qual-
    ity of indoor air within acceptable limits. An IAQ sensor (CO
    2)
    is used to monitor the IAQ levels in a zone or in the return
    air duct. On zone controllers, the zone controller is con®g-
    ured to either participate in the IAQ system, ignore IAQ com-
    mands, or run IAQ monitoring locally.
    When the CO
    2level exceeds the preset level (factory con-
    ®guration is 1000 ppm), the sensor signals the indoor-fan
    motor to run. The indoor fan circulates the air throughout
    the occupied space. At the end of 5 to 30 minutes (on the
    ®rst IAQ alarm of the day only), if the CO
    2level still
    exceeds the set point, the indoor fan will stay energized. The
    zone controller opens the zone damper to the full open po-
    sition (in local mode) or all the participating zone dmapers
    open (in system IAQ mode). This forces fresh outside air to
    enter the zone(s) with de®cient IAQ. When the IAQ level
    drops below the IAQ set point, the zone dampers return to
    their standard operating mode.
    When the system is bringing in additional outside air, the
    thermostat is reset 0 to 10É F (®eld-con®gured) above or be-
    low the original set point to allow the outside air to circulate
    before the heating or cooling mode is initiated. If a CHR-06
    or CHR-06W relay pack is used, the auxiliary contact can be
    used to start a local exhaust fan when the system is bringing
    in additional outside air. The zone controller will display
    status when the system is in this mode.
    SYSTEM IAQ PARTICIPATION Ð To con®gure the Sys-
    tem IAQ Participation option, set category 14, option 1. When
    the option is con®gured ON, the zone controller will modu-
    late in IAQ mode during fan operation. When the option is
    con®gured OFF, the IAQ commands from the system are not
    used. The default is OFF.
    LOCAL IAQ SENSOR Ð The Local IAQ Sensor function
    speci®es if the zone controller (or controlling monitor ther-
    mostat) is using a CO
    2sensor. If the option is set to ON, the
    zone controller monitors the input of the sensor. If the op-
    tion is set to OFF, the zone controller does not monitor the
    input of the sensor.
    To con®gure the Local IAQ Sensor option, set category
    14, option 2. Use the left set point buttons to toggle the op-
    tion ON or OFF. The default is OFF.
    IAQ MAXIMUM SPACE TEMPERATURE RESET Ð When
    the IAQ mode brings in fresh outdoor air, the space tem-
    perature will rise or drop depending on the outside-air tem-
    perature. The IAQ Maximum Space Temperature option will
    keep the HVAC equipment from entering heating or cooling
    unless the temperature change is greater than the set point.
    This keeps the heating or cooling equipment from coming
    on during IAQ mode. The option is con®gured in category
    14, option 3. The set point can be con®gured from 0 to
    10É F. The default value is 2É F.
    NOTE: The IAQ Maximum Space Temperature Reset op-
    tion is always displayed is Fahrenheit, even when the Fahr-
    enheit Temperature Display option (category 1, option 6) is
    set to OFF.
    11 
    						
    							IAQ ALARM DELAY Ð The IAQ Alarm Delay option con-
    trols how long the zone controller will wait before issuing
    an IAQ alarm. To con®gure the IAQ Alarm Delay option,
    set category 14, option 4. The number of minutes will be
    shown. The range of acceptable values is 0 to 240 minutes
    in 1-minute increments. Use the left set point buttons to set
    the time limit to the desired value. The default value is
    0 minutes.
    DAMPER CONTROL
    The zone controller modulates a zone damper to maintain
    the zone temperature conditions as determined by the oc-
    cupied or unoccupied set points.
    The zone controller has 5 modes of damper operation
    available:
    · system mode
    · local mode
    · damper ventilation mode
    · IAQ mode
    · damper supplemental heat mode
    The zone controller selects a damper mode based on zone
    conditions and communications with the monitor thermo-
    stat. The proper damper position is determined by the set-
    tings of the Pressure Independent option (Pressure Depen-
    dent Operation or Pressure Independent Operation).
    During Pressure Independent Damper Modulation, the zone
    controller damper is modulated to maintain a speci®c quan-
    tity (cfm) of supply air.
    Damper Interface ÐThe zone controller is interfaced
    to the damper actuator through the wiring connector board.
    The zone controller can be used to control one master damper
    and up to 3 slave dampers. See Fig. 10. The zone controller
    directly controls only the master damper. Slave dampers will
    receive and follow damper position commands sent to the
    master damper, but do not send information to the zone
    controller.
    Damper Modes ÐThe zone controller has 5 modes of
    damper operation available: local mode, system mode, damper
    ventilation mode, supplemental heat mode, and IAQ mode.
    If the zone controller is a member of a zoning system, it
    will have an associated system control (monitor thermostat)
    that determines the heating/cooling equipment operation based
    on zone demand.
    When a system control has chosen a system mode, the
    zone controller selects a damper mode based on the system
    mode. If the associated system control has not chosen a sys-
    tem mode, the zone controller selects a damper mode based
    on the local mode.
    ASSOCIATED CONTROL SYSTEM MODE Ð When cen-
    tral system heating is needed, the system mode will beheating mode. When central system cooling is needed, the
    system mode will be cooling mode.
    If the zone controller zone has a heating demand and the
    system is in heating mode, the zone damper is modulated in
    the damper heating mode.
    If the zone controller zone has a cooling demand and the
    system is in cooling mode, the zone damper is modulated in
    the damper cooling mode.
    If the zone controller has no zone heating or cooling de-
    mand, or if the zone controller zone demand is opposite of
    the system mode, the zone controller will modulate the zone
    damper in damper minimum air¯ow mode.
    LOCAL MODE Ð When the system control has not
    selected a system mode, the zone controller compares zone
    temperature to supply-air temperature and determines the lo-
    cal damper mode.
    If the zone damper supply-air temperature is warmer than
    the zone temperature and the zone controller is in heating
    mode, then the zone damper is modulated in the damper heat-
    ing mode.
    If the zone damper supply air temperature is colder than
    the zone temperature and the zone controller is in cooling
    mode, then the zone damper is modulated in the damper cool-
    ing mode.
    If the zone controller has a zone heating or cooling de-
    mand which is directly opposite of the local mode, the zone
    controller will modulate the zone damper in the damper mini-
    mum air¯ow mode.
    If the zone controller has no zone heating or cooling de-
    mand, the zone controller can modulate the zone damper in
    the damper ventilation mode.
    INDOOR AIR QUALITY (IAQ) MODE Ð When a local
    sensor signals an alarm, the zone controller will check sys-
    tem mode. If zone demand matches system mode, the zone
    controller will participate in IAQ mode.
    If the system mode is opposite of zone demand, the zone
    controller will check its zone temperature, set points, and
    reset temperature to determine if it will participate in IAQ
    mode. If the zone temperature is outside the reset tempera-
    ture range, the zone controller will look at duct temperature.
    If the duct temperature will improve zone conditions, the zone
    controller will participate in IAQ mode.
    When in IAQ mode, the zone controller will position the
    damper at the minimum position and send a signal to the
    monitor thermostat to con®rm IAQ mode.
    DAMPER VENTILATION AIRFLOW POSITION Ð The
    Damper Ventilation Air¯ow Position is the position that the
    damper will modulate to while in the ventilation mode. To
    con®gure the option, set category 3, option 3. Use the set
    point buttons to raise or lower the setting to the desired value.
    The range of values is 0 to 7, where 0 is fully closed and 7
    is half open. The default is 5. If the Damper Ventilation
    Position is set to 0, or to a value equal or less than the
    Minimum Damper Position, then ventilation mode is off. If
    the Damper Ventilation Position is set to a value higher than
    the Minimum Damper Position, then ventilation mode is on.
    MAXIMUM DAMPER POSITION Ð The damper maxi-
    mum position determines the maximum amount that the damper
    will open or close during modulation. To con®gure the Maxi-
    mum Damper Position option, set category 3, option 1. Use
    the left set point buttons to raise or lower the Maximum Damper
    Position setting. The range of values is 15 to 08, where 15
    is fully open and 08 is half open. The default is 15.
    MINIMUM DAMPER POSITION Ð The damper mini-
    mum position determines the minimum amount that the damper
    will open or close during modulation. To con®gure the Mini-
    mum Damper Position option, set category 3, option 2. Use
    Fig. 10 Ð Damper Wiring Connections
    12 
    						
    							the left set point buttons to raise or lower the Minimum Damper
    Position setting. The range of values is 0 to 7, where 0 is
    fully closed and 7 is half open. The default is 5.
    MINIMUM AIRFLOW SET POINT Ð The Minimum Air-
    ¯ow Set Point establishes the minimum supply air¯ow that
    can be delivered to the zone controller zone during pressure
    independent damper modulation. The air¯ow set point is shown
    in cubic feet per minute.
    To con®gure the Minimum Air¯ow Set Point option, set
    category 3, option 7. The Minimum Air¯ow Set Point will
    be shown. The range of values is 0 to 5000 cfm. Use the left
    set point buttons to increase or decrease the Minimum Air-
    ¯ow Set Point. The default is 0.
    MAXIMUM AIRFLOW SET POINT Ð The Maximum Air-
    ¯ow Set Point establishes the maximum supply air¯ow that
    can be delivered to the zone controller zone during pressure
    independent damper modulation. The air¯ow set point is shown
    in cubic feet per minute.
    To con®gure the Maximum Air¯ow Set Point option, set
    category 3, option 8. The Maximum Air¯ow Set Point will
    be shown. The range of values is 0 to 5000 cfm. Use the left
    set point buttons to increase or decrease the Maximum Air-
    ¯ow Set Point. The default is 0.
    DAMPER SIZE Ð The Damper Size option allows the zone
    controller to be con®gured for the correct cross sectional area
    (square inches) of the duct at the pressure sensor pickup (PSP)
    location.
    To con®gure the Damper Size option, set category 3,
    option 9. Use the left set point buttons to toggle the display
    until the correct damper size is shown. See Table 2 for a
    description of damper sizes. The range of values is 0 to
    1000 sq in. The default is 0.
    Table 2 Ð Damper Sizes
    ZONE DAMPER
    MODEL NUMBERCROSS SECTIONAL
    AREA (sq. in.)
    ZD06 Carrier Round Zone Damper 28
    ZD08 Carrier Round Zone Damper 50
    ZD10 Carrier Round Zone Damper 78
    ZD12 Carrier Round Zone Damper 112
    ZD14 Carrier Round Zone Damper 153
    ZD16 Carrier Round Zone Damper 200
    RD8x10 Carrier Rectangular Damper 78
    RD8x14 Carrier Rectangular Damper 110
    RD8x18 Carrier Rectangular Damper 142
    RD8x24 Carrier Rectangular Damper 190
    NOTE: Cross sectional areas are calculated using inside diameters
    assuming 0.03 in sheet metal thickness and rounded off to the near-
    est whole square inch.
    ZD/RD ACTUATOR Ð If the ZD/RD Actuator option is set
    to ON, the zone controller is con®gured to operate a model
    ZD/RD actuator. If the ZD/RD Actuator option is set to OFF,
    the zone controller is con®gured to operate a high torque
    actuator.
    NOTE: The HTA-02 rotates through 60 degrees of travel.
    The HTA-03 rotates through 90 degrees of travel. The HTA-02
    and 03 are available as separate damper actuators and are
    not factory-assembled to a damper.
    To con®gure the ZD/RD Actuator option, set category 3,
    option 5. Use the left set point buttons to toggle the setting
    to ON or OFF. The default is ON.COUNTERCLOCKWISE OPEN DAMPER MODULA-
    TION Ð If the Counterclockwise Open Damper Modula-
    tion option is set to ON, the zone controller will modulate
    the damper counterclockwise to move it into the open po-
    sition. If the Counterclockwise Open Damper Modulation
    option is set to OFF, the zone controller will modulate the
    damper clockwise to move it into the open position.
    To con®gure the Counterclockwise Open Damper Modu-
    lation option, set category 3, option 6. Use the left set point
    buttons to toggle the setting to ON or OFF. The default is
    ON.
    The following VAV (variable air volume) zone dampers
    require counterclockwise rotation to modulate the damper to
    an open position:
    · Model ZD Zone Damper
    · Model RD Rectangular Damper
    · Model MA08 Actuator
    Pressure Dependent Damper Modulation ÐThe
    zone controller modulates the zone damper depending on zone
    temperature, supply-air temperature, zone demand, and mode.
    The zone damper may be modulated to one of 16 mechani-
    cal positions. Position 0 is fully closed, position 15 is fully
    open.
    The zone controller modulates the zone damper to the
    Damper Maximum Open Position when zone demand is greater
    than 1.5É F or greater and the system mode matches zone
    demand. The zone damper cannot open to a position greater
    than the maximum damper position.
    When zone demand is less than 1.5É F, the zone controller
    modulates the zone damper to maintain a percentage pro-
    portional to zone demand. The damper cannot close to a po-
    sition less than the Minimum Damper Position. See Fig. 11
    for an example of damper modulation.
    To con®gure the zone controller for damper modulation
    (Pressure Dependent Operation), set the Zone Pressure
    Independent Operation option (category 3, option 4) to
    OFF.
    When the zone controller is chosen as the reference zone
    by the associated system control (monitor thermostat), it modu-
    lates the zone damper to the Damper Maximum Open
    Position. The zone controller operates at the maximum
    position until it is no longer the reference zone.
    NOTE: Regardless of zone demand or Ventilation position
    setting, the zone controller will not close the zone damper
    beyond the Minimum Damper Position.
    If the zone damper supply-air temperature is within the
    temperature range of 65 to 80 F, and the Ventilation Position
    is set higher than the Minimum Damper Position, the zone
    controller modulates its zone damper to the Ventilation
    Position.
    If the zone damper supply-air temperature is not within
    the temperature range of 65 to 80 F, the zone controller modu-
    lates its zone damper to the Minimum Damper Position.
    When the zone controller is in the damper minimum air-
    ¯ow mode, it modulates the zone damper to the Minimum
    Damper Position.
    Pressure Independent Damper Modulation
    (33CSZC--PI Only) Ð
    During pressure independent
    damper modulation, the zone controller will modulate its zone
    damper to maintain the air¯ow (cfm) set point. Air¯ow to
    the zone is maintained between the Minimum Air¯ow Set
    Point and the Maximum Air¯ow Set Point.
    13 
    						
    							When zone demand is 1.5É F or greater, the zone con-
    troller modulates the zone damper open, until air¯ow through
    the damper equals the Air¯ow Set Point or until the Damper
    Maximum Open Position is reached. When zone demand is
    less than 1.5É F, the zone controller modulates the zone damper
    to maintain a percentage of the Air¯ow Set Point propor-
    tional to zone demand.
    To con®gure the zone controller for pressure independent
    damper modulation, set the Zone Pressure Independent
    Operation option to ON. The Minimum and Maximum Air-
    ¯ow Set Points, Velocity Pressure Probe Gain, Pressure
    Sensor Range, and the Damper Size must all be con®gured
    correctly for independent pressure modulation.
    When the zone controller is chosen as the reference zone
    by the associated system control (monitor thermostat, sys-
    tem controller, etc.), it modulates the zone damper open
    until air¯ow through the damper equals the Air¯ow Set Point
    or the Damper Maximum Open Position is reached. The zone
    controller operates at the maximum air¯ow condition until it
    is no longer the reference zone.
    NOTE: When the Ventilation Position is set to 0 (ventilation
    mode is off) and the zone controller is in occupied mode,
    regardless of zone demand, the zone controller will not close
    the zone damper beyond the Damper Minimum Air¯ow
    Position.
    PRESSURE INDEPENDENT DAMPER MODULATION
    DURING DAMPER VENTILATION MODE Ð If the zone
    damper supply-air temperature is within the temperature range
    of 65 to 80 F, the zone controller modulates its zone damper
    to maintain a percentage of the Air¯ow Set Point propor-
    tional to the damper ventilation position.
    If the zone damper supply-air temperature is not within
    the temperature range of 65 to 80 F, the zone controller modu-
    lates its zone damper to the minimum air¯ow set point.
    When the zone controller is in the damper minimum air-
    ¯ow mode, the zone controller modulates the zone damper
    to maintain a percentage of the Air¯ow Set Point propor-
    tional to the damper minimum air¯ow position.
    NOTE: During the ventilation mode, the zone controller will
    not close the zone damper past the setting of the Damper
    Minimum Air¯ow Position option.PRESSURE INDEPENDENT OPERATION Ð If the Pres-
    sure Independent Operation option is set to ON, the zone
    controller modulates its zone damper using pressure inde-
    pendent damper modulation. If the Pressure Independent
    Operation option is set to OFF, the zone controller modu-
    lates its zone damper using pressure dependent damper
    modulation.
    To con®gure the Pressure Independent Operation option,
    set category 3, option 4. Use the left set point buttons to
    toggle the display ON or OFF. The default is OFF.
    SUPPLEMENTAL HEAT
    The operation of supplemental heat for each zone is con-
    trolled by the zone controller. The zone controller works in
    conjunction with the associated monitor thermostat to:
    · lock out supplemental heat based on outside-air temperature
    · utilize central heat and supplemental heat to satisfy zone
    heating demands
    When air¯ow into the zone is necessary during supple-
    mental heat operation the monitor thermostat can be con-
    ®gured to energize the supply air fan. The zone controller
    can be con®gured to open the zone damper and allow the
    required amount of supply air into the zone.
    The zone controller can be con®gured to control a variety
    of supplemental heat sources:
    · Fan Powered Mixing Box
    · Perimeter Baseboard Heat
    · Radiant Heating Panel
    · Duct Mounted Heat
    · Hydronic Heat
    The zone controller can be con®gured to energize the
    primary air fan in series fan powered mixing boxes con-
    tinuously during occupied mode and to satisfy a zone heat-
    ing or cooling demand during unoccupied mode. If the zone
    controller is an IAQ participant and has an exhaust fan, the
    zone controller cannot control supplemental heat damper
    positioning.
    Fig. 11 Ð Damper Modulation
    14 
    						
    							Supplemental Heat Interface ÐThe zone supple-
    mental heat source is interfaced to the zone controller through
    a Heating Relay Pack. With the relay pack the zone con-
    troller can control a fan and two stages of supplemental heat.
    See Fig. 12.
    For side pocket fan powered mixing boxes (parallel fan
    box), the zone controller can control three stages of heat. At
    1.5É F demand, the zone controller energizes the fan relay.
    At 2.0É F demand the zone controller energizes the H1 heat
    relay. At 2.5É F demand the zone controller energizes the H2
    heat relay.
    For series fan powered mixing boxes, the zone controller
    can control the primary air fan and two stages of heat. The
    fan relay (FAN) controls the mixing box primary air fan. The
    ®rst stage heat relay (H1) controls the mixing box ®rst stage
    electric or hot water heat. The second stage heat relay (H2)
    controls the mixing box second stage electric or hot water
    heat.
    Supplemental Heat Operation ÐThe zone con-
    troller can use supplemental heat to satisfy the zone heating
    demand when the Zone Supplemental Heat function is set to
    ON.
    The zone controller uses the Heating Relay Pack to:
    · energize ®rst stage supplemental heat (H1) when zone heat-
    ing demand is 1.5É F
    · energize second stage supplemental heat (H2) when zone
    heating demand is 2.0É F.
    Once a stage of supplemental heat is energized, it remains
    on until zone heating demand is 0.5É F or less.
    NOTE: When equipped with a parallel fan box, there are
    3 heating stages: energize fan when zone heating demand
    is 1.0É F, energize ®rst stage of supplemental heat (H1)
    when zone heating demand is 2.0É F, energize second stage
    of supplemental heat (H2) when zone heating demand is
    2.5É F.
    NOTE: Supplemental Heat Operation can be disabled by the
    monitor thermostat.
    ZONE SUPPLEMENTAL HEAT Ð When the Zone Supple-
    mental Heat option is set to ON, the zone controller can use
    supplemental heat operation to satisfy zone heating demand.
    When the Zone Supplemental Heat option is set to OFF, the
    zone controller will not energize supplemental heat.
    To con®gure the Zone Supplemental Heat option, set cat-
    egory 6, option 1. Use the left set point buttons to toggle the
    setting to ON or OFF. The default is OFF.SUPPLEMENTAL HEAT TIME GUARD Ð The zone con-
    troller has a system time limit (Time Guard) which prevents
    supplemental heat from being energized directly after supple-
    mental heat has been deenergized, the zone controller re-
    ceives power, or the zone controller resets.
    The power-up or reset time guard determines how long
    the zone controller will wait before starting the supplemen-
    tal heat when the zone controller is powered up or reset. The
    length of the time guard is 30 seconds plus 0 to 189 seconds
    (determined by the ®rst 6 bits of the address of the zone con-
    troller). This keeps the supplemental heating equipment from
    starting simultaneously with other equipment which keeps
    peak energy usage down. The system fan controlled by the
    zone controller has a power-up or reset time guard of
    30 seconds.
    After the supplemental heat has been deenergized, the zone
    controller will wait 30 seconds before allowing the system
    fan to be energized, and 2 minutes before allowing the heat
    relay to be energized.
    SUPPLEMENTAL HEAT TIME GUARD OVERRIDE Ð
    When the Supplemental Heat Time Guard Override option
    is set to ON, the zone controller supplemental heat time guards
    are reset to 30 seconds. If the time guard is less than
    30 seconds, it is unaffected.
    NOTE: When Supplemental Heat Time Guard Override is
    set to ON, the zone controller resets it to OFF after the time
    guards have been reset.
    When the Supplemental Heat Time Guard Override op-
    tion is set to OFF, the Supplemental Heat Time Guard de-
    termines time guard length based on normal operation.
    To con®gure the Supplemental Heat Time Guard Over-
    ride option, set category 6, option 3. Use the left set point
    buttons to turn the option ON or OFF. The default is OFF.
    Supplemental Heating Damper Modulation Ð
    Prior to energizing supplemental heat the zone controller will
    modulate the Zone Damper to the Supplemental Heat Damper
    Position.
    When the zone controller monitor thermostat has selected
    a system heating mode:
    · if supplemental heat is energized, the zone controller modu-
    lates the damper to the Damper Maximum Open Position
    (or to the Air¯ow Set Point if the Zone Pressure Indepen-
    dent Operation option is ON)
    · if supplemental heat is deenergized, the zone controller modu-
    lates the damper using Damper Modulation (pressure de-
    pendent operation) or Pressure Independent Damper
    modulation functions.
    SUPPLEMENTAL HEAT DAMPER FACTOR Ð The Supple-
    mental Heat Damper Factor option speci®es the damper po-
    sition during supplemental heat damper modulation.
    If the Pressure Independent Operation option is set to OFF,
    the Supplemental Heat Damper Factor is a percentage of the
    15 damper positions.
    If the Pressure Independent Operation option is set to ON,
    the Supplemental Heat Damper Factor is speci®ed as a per-
    centage of the Air¯ow Set Point.
    To con®gure the Supplemental Heat Damper Factor set-
    ting, set category 6, option 2. The zone controller supple-
    mental heat damper position will be displayed.
    The position is shown in the top left corner. Use the left
    set point buttons to raise or lower the position setting. The
    range of values is 0 to 10, where 10 is the maximum damper
    factor and 0 is the minimum damper factor. The default is 0.
    Fig. 12 Ð Supplemental Heat Interface
    15 
    						
    							As an example, if the Maximum Damper Position is set to
    13 and the Minimum Damper Position is set to 5. Subtract
    5 from 13 to get 8. Divide 8 by 10 to get 0.8. Supplemental
    Heat Damper Factor 0 is 5 (Minimum Damper Position).
    Use this formula is determine the Supplemental Heat Damp-
    er Factors: Minimum Position + (((Maximum Position þ
    Minimum Position)/10) * supplement heat damper posi-
    tion). Factor 01 is 5 + (0.8 * 1) = 5 (all values are truncated).
    Factor 02 is 5 + (0.8 * 2) = 6. Factor 10 will be 13 (Maxi-
    mum Damper Position).
    NOTE: If the Minimum or Maximum Damper Position op-
    tions are changed, the Supplemental Heat Damper Factor will
    be automatically recalculated.
    FAN POWERED MIXING BOX Ð The zone controller will
    operate a fan powered mixing box.
    To con®gure the Fan Powered Mixing Box option, set cat-
    egory 6, option 4. Use the left set point buttons to toggle the
    display from 0 to 2. When the option is set to 0, the zone
    controller will not use a fan powered mixing box. When the
    option is set to 1, the zone controller will function with a
    series fan powered mixing box. When the option is set to 2,
    the zone controller will function with a parallel fan powered
    mixing box. The default is 0.
    If the Fan Powered Mixing Box option is set to 0, the zone
    controller will not operate as a Fan Powered Mixing Box.
    When the Fan Powered Mixing Box option is set to 1 (Se-
    ries Fan Box), the zone controller will energize the fan relay
    continuously during Occupied mode. The Heat1 relay en-
    ergizes at 1.5É F demand. The Heat2 relay energizes at
    2.0É F demand.
    When the Fan Powered Mixing Box option is set to 2 (Par-
    allel Fan Box), the zone controller will energize the fan re-
    lay as ®rst stage heating when there is 1.5É F heating demand.
    The Heat1 relay will energize for second stage heat when
    there is a 2.0É F demand. The Heat2 relay will energize as
    third stage when there is a 2.5É F demand.
    NOTE: The zone controller will not deenergize the fan relay
    until zone demand is less than 0.5É F.
    HYDRONIC HEAT Ð When the zone controller is con®g-
    ured for Hydronic Heat and the Fan Powered Mixing Box
    option is set to 0, the zone controller assumes that hot water
    is being used for supplemental heat. The Hydronic Heat
    algorithm allows ®rst stage to be energized before the sys-
    tem fan is requested in order to allow the heating coils to
    attain proper temperature. This prevents cold air at the be-
    ginning of a Supplemental Heat Operation from entering the
    zone.
    When the Hydronic Heat option is set to ON, the zone
    controller will energize the supplemental heat stages accord-
    ing to the Hydronic Heat staging algorithm, provided the
    Fan Powered Mixing Box option is set to 0, the ``No Box
    option.
    When the Hydronic Heat option is set to OFF, the zone
    controller will not energize the supplemental heat stages
    according to the Hydronic Heat staging algorithm.
    To con®gure the Hydronic Heat option, set category 6,
    option 5. Use the left set point buttons to toggle the setting
    to ON or OFF. The default is OFF.
    SUPPLEMENTAL HEAT LOCKOUT OVERRIDE Ð The
    zone controller can be con®gured to ignore a Supplemental
    Heat Lockout command sent by the associated monitor
    thermostat.
    When the Supplemental Heat Lockout Override option is
    set to ON the zone controller will ignore the Supplemental
    Heat Lockout command sent by the associated System
    Controller.When the Supplemental Heat Lockout Override option is
    set to OFF, the zone controller will accept the Supplemental
    Heat Lockout command sent by the System Controller.
    To con®gure the Supplemental Heat Lockout option, set
    category 6, option 6. Use the left set point buttons to toggle
    the setting to ON or OFF. The default is OFF.
    METERING
    The zone controller has zone metering capabilities. The
    zone controller can meter zone usage in three ways:
    · usage of the zone in addition to the normal occupied sched-
    ule (amount of time the zone is in Unoccupied Override).
    · usage of the heating/cooling equipment to maintain zone
    temperature conditions (amount of time the zone demand
    matches the System Mode).
    · usage of the supplemental heating equipment to maintain
    zone temperature conditions during unoccupied override.
    HVAC Usage Meter ÐThe zone controller has a
    usage meter that can accumulate up to 32,767 minutes
    (22.75 days) of zone usage. Through communication, the
    amount of time accumulated in the meter can be accessed,
    recorded, and reset to zero. Once the maximum amount of
    time has been accumulated, the zone controller stops me-
    tering and an HVAC Usage Meter Full Error is generated.
    To reset the meter, force the value to zero through Carrier
    Network Access Software.
    To disable the zone controller HVAC Usage Meter, set the
    HVAC Usage Meter option to OFF. No metering occurs. To
    Enable the HVAC Usage Meter, set the option to ON. To
    con®gure the HVAC usage meter option, set category 7, op-
    tion 5. Use the left set point buttons to toggle the option ON
    or OFF. The default is OFF.
    Override Usage Meter ÐThe zone controller has an
    override usage meter that can accumulate up to 32,767 min-
    utes (22.75 days) of override usage. When the Override
    Usage Meter option is set to ON, zone metering will occur
    when the zone controller is in Unoccupied Override. When
    the Override Usage Meter option is set to OFF, zone me-
    tering for override usage will not occur. Once the maximum
    amount of time has been accumulated, the zone controller
    stops metering and an Override Usage Meter Full Error is
    generated. To reset the meter, force the value to zero through
    Carrier Network Access Software.
    To con®gure the Override Usage Meter option, set cat-
    egory 7, option 6. Use the left set point buttons to toggle the
    setting to ON or OFF. The default is OFF.
    Supplemental Heat Override Usage Meter ÐThe
    zone controller has a supplemental heat override usage meter
    that can accumulate up to 32,767 minutes (22.75 days) of
    supplemental heat override usage. When the Supplemental
    Heat Override Usage Meter option is set to ON, zone me-
    tering occurs when the zone controller uses supplemental heat
    during unoccupied override. When the Supplemental Heat
    Override Usage Meter option is set to OFF, zone meter-
    ing will not occur for supplemental heat usage in unoc-
    cupied override. Once the maximum amount of time has
    been accumulated, the zone controller stops metering and a
    Supplemental Heat Override Usage Meter Full Error is
    generated. To reset the meter, force the value to zero through
    Carrier Network Access Software.
    To con®gure the Supplemental Heat Override Usage Meter
    option, set category 7, option 7. Use the left set point but-
    tons to toggle the setting to ON or OFF. The default is OFF.
    16 
    						
    							DIAGNOSTICS
    The zone controller has diagnostic capabilities for com-
    ponents, information, zone comfort, and usage.
    Diagnostic problems, called errors or alarms, are divided
    into 3 categories: Hardware Failure (HF) errors, Storage Fail-
    ure (SF) errors, and System Errors (SE). The zone controller
    tracks the operating conditions in the zone.
    Error Code Display ÐAn error code representing the
    SE, SF, and HF diagnostic functions can be displayed to in-
    dicate which error has been declared. The 2 letters located in
    the left of the display represent the type of error. The 3 num-
    bers located in the right of the display identify the speci®c
    error.
    When the Error Code Display option is ON, an error
    code will be displayed when the associated error occurs. Any
    previous error codes that occurred when the Error Code Dis-
    play was con®gured OFF will be displayed.
    NOTE: When an error is cleared, any other errors remaining
    in memory will be displayed, until all errors are cleared.
    When the Error Code Display option is set to OFF, no
    error codes will be displayed by the zone controller.
    To con®gure the Error Code Display option, set category
    7, option 1. Use the left set point buttons to toggle the set-
    ting to ON or OFF. The default is OFF.
    System Errors (SE) ÐSystem Errors occur when the
    zone controller detects a zone operating problem or system
    operating problem. See Table 3 for System Errors.
    COMFORT TREND ERROR (Space Temperature Alarm)
    (SE01) Ð A Comfort Trend error is a system error that pro-
    vides information on the ability of the system to maintain
    temperature conditions in its reference zone.
    When the zone demand exceeds the Comfort Trend
    Demand Set Point, the zone controller begins tracking the
    Temperature Trend of the zone.
    The zone controller declares a Comfort Trend Error for
    the zone when the Temperature Trend is continuously zero
    (zone temperature conditions are not improving) or positive
    (zone temperature conditions are becoming worse) for the
    entire Comfort Trend Time Limit.
    To clear a Comfort Trend Error, use the Unit Reset func-
    tion. The Unit Reset function is in category 7, option 8. The
    default is OFF. Use the left set point buttons to set the option
    to ON. The zone controller will reset all errors and return to
    the OFF con®guration. The error can also be cleared by set-
    ting the Comfort Trend Demand set point to 0.
    By indicating when zone heating or cooling set points can-
    not be satis®ed, a Comfort Trend Error helps identify zone
    heating or cooling problems.
    When the system is commissioned, this information can
    be used by the installing contractor to recognize zone air-
    ¯ow or supply-air temperature problems in the system.During system operation, Comfort Trend Errors can be con-
    tinuously monitored by the servicing contractor through a
    local network access device to determine when system or
    equipment problems are affecting zone comfort.
    To troubleshoot a Comfort Trend Error:
    1. Check the quantity of air¯ow into the zone controllers
    zone.
    a. Check the con®guration of the zone controller Damper
    Maximum Open Position setting (category 3, option 1)
    and the position of any balancing dampers used by the
    zone. Dampers may need to be adjusted further open
    to allow additional air¯ow into the zone. The allow-
    able range for the Damper Maximum Open Position
    setting is 15 to 8, with 15 being full open and 8 being
    approximately 50% open.
    b. Check the ductwork running to the zone controllers
    zone. Loose connections, obstructions, or poorly in-
    sulated duct can result in reduced air volume or tem-
    peratures causing the zone not to satisfy within the
    Comfort Trend Time Limit.
    c. Check the bypass controller con®guration. If the by-
    pass controller is not con®gured correctly, it can keep
    the system static pressure too low to meet the zone
    design load air¯ow requirements.
    d. After the previous steps have been completed, the
    performance of the supply air fan should be checked.
    During full load situations, the fan must produce an
    adequate quantity of supply air at the necessary static
    pressure to meet the zone design requirements. Reset
    the zone controller to clear error.
    2. Check the temperature of supply air into the zone. If the
    temperature is above the zone design conditions during
    system cooling mode, or below design conditions during
    system heating mode, the operation of the equipment should
    be checked. Reset the zone controller to clear error.
    Comfort Trend Demand Set Point Ð The Comfort Trend De-
    mand Set Point establishes the minimum zone demand level
    that must exist in the zone, before it can declare a Comfort
    Trend Error.
    The Comfort Trend Demand set point is con®gured in
    category 7, option 3. Use the left set point buttons to raise
    or lower the set point. The range of values is 0 to 25.5É F in
    1/10É F increments. The default is 0É F. The function is dis-
    abled if it is set to 0É F.
    NOTE: The Comfort Trend Demand set point is always dis-
    played in Fahrenheit, even if the Fahrenheit Display option
    is set to OFF.
    Comfort Trend Time Limit Ð The Comfort Trend Time Limit
    establishes the continuous amount of time that must elapse
    before the zone controller can declare a Comfort Trend
    Error.
    The Comfort Trend Time Limit set point is con®gured from
    category 7, option 4. The range of values is 2 to 255 minutes
    in 1-minute increments. The default is 2.
    Table 3 ± System Errors
    ERROR CODE SYSTEM ERROR DESCRIPTION ALARM PRIORITY LEVEL
    SE01Comfort Trend (Space Temperature Alarm) 2
    SE02HVAC Usage Meter Full 4
    SE03Override Usage Meter Full 4
    SE04Supplemental Heat Override Usage Meter Full 4
    SE10IAQ Exceeded Limit 2
    17 
    						
    							METER FULL ERROR (SE02,03,04) Ð System Errors SE02,
    SE03, and SE04 indicate when a zone meter is full.
    NOTE: During a meter full error, the full usage meter stops
    recording and retains its maximum value until cleared.
    To clear an SE02, SE03, or SE04 error, reset the full meter
    to zero by using network access software. The meter can be
    reset by forcing the value to zero through Carrier Network
    Access Software.
    IAQ EXCEEDED LIMIT ERROR (SE10) Ð When the CO
    2level exceeds the preset level, the sensor signals the zone
    controller. The zone controller will wait until the IAQ Alarm
    Delay time (category 14, option 4) has expired, then it will
    issue an SE10. The system (if con®gured) will bring in fresh
    outdoor air to meet IAQ requirements. If the IAQ Alarm De-
    lay is not set to give the system enough time to correct IAQ
    problems, the SE10 will be issued every time the IAQ mode
    is entered.
    To clear a system error, set the IAQ Alarm Delay time
    (category 14, option 4) to 0. When the error clears, reset the
    time to the desired set point.
    Storage Failure (SF) Errors ÐA Storage Failure
    error is an indication that the zone controller has invalid
    information. The zone controller stores its information in non-
    volatile memory. If the zone controller determines that a piece
    of stored information is incorrect, it generates a storage fail-
    ure error.
    When an SF Error occurs, the zone controller replaces the
    invalid data in memory with factory selected default values
    and the invalid information is not used by the associated sys-
    tem control.
    To clear an SF Error, enter correct data at the zone con-
    troller. See Table 4 for a description of Storage Failure
    Errors.
    EXAMPLE OF CLEARING AN SF ERROR Ð The zone
    controller displays a SF19 error. Look up SF19 in Table 4.
    The affected con®guration is Maximum Damper Position.
    The default value is 15. The desired setting is 12.
    To clear the SF19 error manually, recon®gure the Maxi-
    mum Damper Position option to 12. The SF19 error should
    be cleared.
    NOTE: If the SF error cannot be cleared, replace the zone
    controller and con®gure the new thermostat to match de-
    sired settings.
    Table 4 Ð Storage Failure (SF) Errors
    ERROR INFORMATION AFFECTEDDEFAULT
    VALUE(S)
    SF01 Occupied Cooling Set Point 72
    SF02 Occupied Heating Set Point 68
    SF03 Cooling Set Point Low Limit 68
    SF04 Heating Set Point High Limit 75
    SF05 Unoccupied Cooling Set Point 80
    SF06 Unoccupied Heating Set Point 65
    SF07 Rotating Display OFF
    SF08 Fahrenheit Temperature Display ON
    SF09 Occupancy Period 1MTWTHF
    6:00AM-6:00PM
    SF10 Occupancy Period 2MTWTHF
    6:00AM-6:00PM
    SF11 Occupancy Period 3MTWTHF
    6:00AM-6:00PM
    SF12 Occupancy Period 4MTWTHF
    6:00AM-6:00PM
    SF13 Occupancy Period 5MTWTHF
    6:00AM-6:00PM
    SF14 Occupancy Period 6MTWTHF
    6:00AM-6:00PM
    SF15 Occupancy Period 7MTWTHF
    6:00AM-6:00PM
    SF16 Occupancy Period 8MTWTHF
    6:00AM-6:00PM
    SF17 Schedule Number 0
    SF18 Override Time Limit 1
    SF19 Maximum Damper Position 15
    SF20 Minimum Damper Position 0
    SF21 Pressure Independent Operation OFF
    SF22 Ventilation Position 5
    SF23 ZD/RD Actuator ON
    SF24 Counterclockwise Open ON
    SF25 Maximum Air¯ow Set Point 0
    SF26 Minimum Air¯ow Set Point 0
    SF27 Damper Size 0
    SF46Zone Temperature Sensor
    CalibrationFactory Calibrated
    SF47Remote Room Sensor
    CalibrationFactory Calibrated
    SF48Duct Temperature Sensor
    CalibrationFactory CalibratedERROR INFORMATION AFFECTEDDEFAULT
    VALUE(S)
    SF49 Pressure Sensor Calibration Factory Calibrated
    SF51 Room Sensor 1
    SF59 Zone Supplemental Heat OFF
    SF60Supplemental Heat Damper
    Position0
    SF61 Alarm System Name Network Con®gured
    SF62 Fan Powered Mixing Box 0
    SF63 Hydronic Heat OFF
    SF64Supplemental Heat Lockout
    OverrideOFF
    SF65 Error Code Display OFF
    SF67 Alternate Information OFF
    SF68 Occupied Trend Demand 0
    SF69 Occupied Trend Time Limit 2
    SF70 HVAC Usage Meter Data OFF
    SF71 Override Usage Meter Data OFF
    SF72Supplemental Heat Override
    Usage Meter DataOFF
    SF75 Device Element Address 0
    SF76 Security Level 1
    SF77 Device Bus Number 0
    SF82 Broadcast Acknowledge OFF
    SF83 Global Schedule Broadcast OFF
    SF85 Holiday Schedules 0
    SF86 Equipment Priority 7
    SF87Communication Failure Retry
    Time10
    SF88 Re-Alarm Time 30
    SF89 IAQ System OFF
    SF93 Local IAQ Sensor OFF
    SF95IAQ Maximum Space
    Temperature Reset0
    SF98 Alarm Routing ControlNetwork Con®gured
    (00000000)
    SF100 HVAC Meter Enable ON
    SF101 Override Meter Enable ON
    SF103Supplemental Heat Override
    Meter EnableON
    18 
    						
    							Hardware Failure (HF) Errors ÐA Hardware Fail-
    ure (HF) error is an error that corresponds to a hardware
    failure at the zone controller, associated sensors, or zone damper.
    To clear an HF Error, the component responsible for ini-
    tiating the HF Error must be adjusted, repaired, or replaced.
    See Table 5 for a description of HF errors.
    Table 5 Ð Hardware Failure (HF) Errors
    ERROR HARDWARE PROBLEMS PRIORITY LEVEL
    HF01 Cannot Detect Closed Damper 2
    HF02 Cannot Detect Open Damper 2
    HF03 Zone Temperature Sensor
    Out of Range2
    HF04 Remote Room Sensor
    Out of Range2
    HF05 Duct Temperature Sensor
    Out of Range2
    HF06 Hardware NOVRAM Failure 2
    HF07 Hardware Analog/Digital Failure 2
    HF08 Pressure Sensor Out of Range 2
    CANNOT DETECT CLOSED DAMPER Ð An HF01 error
    is issued when the thermostat attempts to position the damper
    closed, but the position sensor indicates the damper is not at
    the fully closed position.
    To clear the error, correct the damper problem and use the
    Unit Reset function. The Unit Reset function is in category 7,
    option 8. The default is OFF. Use the left set point buttons
    to set the option to ON. The zone controller will reset all
    errors.
    To correct the damper problem:
    1. Check the damper for mechanical binding. An obstruc-
    tion in the damper or a bent damper blade can prohibit
    the damper from modulating closed. Remove the source
    of binding.
    2. Check the actuator-to-damper alignment. If the damper
    shaft is out of alignment with the actuator crank arm po-
    sition, the damper may reach the fully closed position be-
    fore the actuator.
    Align the damper and the actuator so both fully closed
    positions coincide. Prior to alignment, the Minimum Damper
    Position (category 3, option 2) setting should be con®g-
    ured to zero. This will ensure the actuator will be in the
    fully closed position when the zone controller demand is
    zero.
    3. Check the damper actuator position to see if the traveler
    arm has moved past the position sensor. If the traveler
    arm is stuck at full open or full closed position, use the
    following steps to correct the problem:
    a. Disconnect the zone controller from the wiring con-
    nector board.
    b. At the damper, using a ¯at head screw driver, turn the
    traveler screw (located on the stepper motor) until the
    traveler arm is midway between the fully closed and
    fully open positions.
    c. Reconnect the zone controller.
    4. Check for excessive inlet static pressure beyond the rated
    ability of the damper actuator.
    · ZD and RD zone dampers are rated for 18 in.-lb.
    · The MA-08 actuator is rated for 18 in.-lb.
    · The HTA-02 actuator is rated for 80 in.-lb.
    · The HTA-03 actuator is rated for 45 in.-lb.
    5. Check the con®guration of the zone controller Counter-
    clockwise Open option (category 3, option 6). For
    Carrier dampers, which the damper blade modulatescounterclockwise to open, the option should be con®g-
    ured correctly.
    6. Check the wiring between the damper actuator and zone
    controller. If the green wire between the damper actuator
    and the zone controller has lost continuity, the zone con-
    troller will constantly receive the indication that the damper
    is fully closed.
    To check the wiring, disconnect the zone controller and
    wiring connector board. Connect the zone controller and
    wiring connector board directly at the damper board. If
    the error disappears, the ®eld wiring or the connections
    should be checked.
    If the error is still present, the zone controller circuit board,
    the wiring connector board, or the damper actuator cir-
    cuit board is bad. To isolate the defective component, re-
    place components, one at a time, until the error disappears.
    CANNOT DETECT OPEN DAMPER Ð An HF02 error is
    issued when the zone controller attempts to open the damper,
    but the position sensor indicates the damper is fully closed.
    To clear the error, correct the damper problem and use the
    Unit Reset function. The Unit Reset function is in category 7,
    option 8. The default is OFF. Use the left set point buttons
    to set the option to ON. The zone controller will reset all
    errors.
    To correct the damper problem:
    1. Check the damper for mechanical binding. An obstruc-
    tion in the damper or a bent damper blade can prohibit
    the damper from modulating open. Remove the source of
    binding.
    2. Check the damper actuator position to see if the traveler
    arm has moved past the position sensor. If the traveler
    arm is stuck at full open or full closed position, use the
    following steps to correct the problem:
    a. Disconnect the zone controller from the wiring con-
    nector board.
    b. At the damper, using a ¯at head screw driver, turn the
    traveler screw (located on the stepper motor) until the
    traveler arm is midway between the full closed and
    full open positions.
    c. Reconnect the zone controller.
    3. Check for excessive inlet static pressure beyond the rated
    ability of the damper actuator.
    · ZD and RD zone dampers are rated for 18 in.-lb.
    · The MA-08 actuator is rated for 18 in.-lb.
    · The HTA-02 actuator is rated for 80 in.-lb.
    · The HTA-03 actuator is rated for 45 in.-lb.
    4. Check the wiring between the damper actuator and zone
    controller. If the green wire between the damper actuator
    and the zone controller has lost continuity, the zone con-
    troller will constantly receive the indication that the damper
    is fully closed.
    To check the wiring, disconnect the zone controller and
    wiring connector board. Connect the zone controller and
    wiring connector board directly at the damper board. If
    the error disappears, the ®eld wiring or the connections
    should be checked.
    If the error is still present, the zone controller circuit board,
    the wiring connector board, or the damper actuator cir-
    cuit board is bad. To isolate the defective component, re-
    place components, one at a time, until the error disappears.
    ZONE TEMPERATURE SENSOR OUT OF RANGE Ð An
    HF03 error is issued when the zone temperature sensor is
    reading below 30 F or greater than 180 F. The zone tem-
    perature sensor can be recalibrated. The HF03 error will
    automatically clear when the sensor reading is back within
    the allowable range.
    19 
    						
    							To check the zone temperature sensor:
    1. Check that the zone temperature sensor is physically in-
    tact on the zone controller printed circuit board. Ensure
    the sensor is not shorted against the zone controller printed
    circuit board.
    2. a. Ensure the Room Sensor option (category 5, option 1)
    has been con®gured correctly.
    b. Check for other wiring running parallel to and less than
    12 in. from the remote room sensor wiring. Avoid
    running AC, control, or communication bus near the
    remote room sensor wiring. Maintain a minimum sep-
    aration of 12 in. or more between other wiring and
    remote room sensor wiring.
    3. Check the zone temperature sensor calibration. Calibrate
    the sensor by manual calibration at the zone controller
    using the Zone Temperature Sensor Calibration function
    (category 5, option 2) and an accurate thermometer. Mea-
    sure the temperature at the zone controller zone tempera-
    ture sensor location using the accurate thermometer. Wait
    for the reading to stabilize. Using the set point buttons,
    increase or decrease the temperature display to match the
    reading of the thermometer. If the zone temperature sen-
    sor cannot be recalibrated, replace the zone controller.
    REMOTE ROOM SENSOR OUT OF RANGE Ð An HF04
    error is issued when the remote room temperature sensor is
    reading below 30 F or greater than 180 F. The remote room
    temperature sensor can be recalibrated. The HF04 error will
    automatically clear when the sensor reading is back within
    the allowable range.
    To check the remote room sensor:
    1. Check that the remote room sensor wiring and connec-
    tions to the circuit board are physically intact. Ensure the
    5-conductor control wiring running between the damper
    actuator and the zone controller is not run near AC, con-
    trol, or communication bus wiring. Maintain a minimum
    separation of 12 in. or more between other wiring and
    remote room sensor wiring. A resistor must be added in
    parallel if using more than one remote room sensor.
    2. Check for proper wiring connections (red to +, black
    to þ). A 9.2 k ohm resistor must be added in parallel if
    using more than one remote room sensor.
    3. Verify that category 5, option 1, Room Sensor, is set
    correctly.
    4. Check the remote room sensor calibration. Calibrate the
    sensor by manual calibration at the zone controller using
    the Remote Room Sensor Calibration function (category
    5, option 3) and an accurate thermometer. Measure the
    temperature at the remote room temperature sensor
    location using the accurate thermometer. Wait for the read-
    ing to stabilize. Using the set point buttons, increase or
    decrease the temperature display to match the reading of
    the thermometer.
    DUCT TEMPERATURE SENSOR OUT OF RANGE Ð An
    HF05 error is issued when the duct temperature sensor is
    reading below 30 F or greater than 180 F. The duct tem-
    perature sensor can be recalibrated. The HF05 error will
    automatically clear when the sensor reading is back within
    the allowable range.
    To check the duct temperature sensor:
    1. Check that the duct temperature sensor wiring and con-
    nections to the damper actuator circuit board are physi-
    cally intact. Ensure the 5-conductor control wiring run-
    ning between the damper actuator and the zone controller
    is not run near AC, control, or communication bus wir-
    ing. Maintain a minimum separation of 12 in. or more
    between other wiring.2. Check the duct temperature sensor calibration. Calibrate
    the sensor by manual calibration at the zone controller
    using the Duct Temperature Sensor Calibration function
    (category 5, option 4) and an accurate thermometer. Mea-
    sure the temperature at the duct temperature sensor
    location using the accurate thermometer. Wait for the read-
    ing to stabilize. Using the set point buttons, increase or
    decrease the temperature display to match the reading of
    the thermometer. If the duct temperature cannot be re-
    calibrated, replace the damper board or duct sensor.
    3. Check the wiring between the damper actuator and the
    zone controller. If the green wire between the damper
    actuator and the zone controller has lost continuity, the
    zone controller will not function properly.
    HARDWARE NOVRAM FAILURE Ð An HF06 error is
    issued when the zone controller detects a problem in its non-
    volatile memory. If the zone controller is able to correct the
    problem, the error will clear in approximately 10 minutes. If
    the condition persists, the zone controller must be replaced.
    HARDWARE A/D FAILURE Ð An HF07 error is issued
    when the zone controller detects a problem with its analog/
    digital converter circuitry. If the zone controller is able to
    correct the problem, the error will clear in approximately
    10 minutes. If the condition persists, the zone controller must
    be replaced.
    PRESSURE SENSOR OUT OF RANGE Ð An HF08
    error is issued when the pressure sensor is reading below
    0.00 in. wg or greater than 5.0 in. wg. The pressure sensor
    can be recalibrated. The HF08 error will automatically clear
    when the sensor reading is back within the allowable range.
    To clear the HF08 error:
    1. Check for excessive static pressure or excessive differ-
    ential pressure at the pressure sensor pressure pickup. The
    33CSPS-01 is rated for a maximum of 0.5 in. wg. The
    33CSPS-02 is rated for a maximum of 2.0 in. wg. When
    the pressure sensor is operating at or above the rated pres-
    sure, the sensor readings will be unstable, causing an HF08
    error.
    2. Check the connection of hoses running from the PSP pres-
    sure pickup and the pressure sensor. Incorrect or faulty
    connections with the PSP pressure pickup can result in an
    HF08 error.
    3. Check to ensure the pressure sensor wiring connection to
    the damper actuator is complete and well connected. En-
    sure the connections labeled ``O on the pressure sensor
    wiring harness are not used or shorted to ground. For the
    zone controller, the two wires marked ``O on the pres-
    sure sensor wiring harness are not used and can be clipped
    to prevent possible connection to ground.
    4. Check the wiring from the pressure sensor to the damper
    actuator printed circuit board. If improperly wired the zone
    controller will be unable to communicate with the pres-
    sure sensor. This will result in an HF08 error. To check
    the wiring:
    a. Remove the pressure sensor from location and wire it
    directly to the factory supplied six-wire harness. The
    harness should be connected to the damper actuator
    printed circuit board.
    b. If the HF08 error disappears, then the ®eld-wiring or
    connections should be checked.
    c. If the HF08 error still appears, the damper circuit board
    or the pressure sensor may have failed.
    d. To determine the defective component, replace the com-
    ponents one at a time until the problem is isolated.
    20 
    						
    All Carrier manuals Comments (1)